Daikin altherma ERHQ014BAV3 Скачать руководство пользователя страница 15

ERHQ011~W1 + ERLQ011~W1

Outdoor unit for air to water heat pump

4PW57794-1 – 08.2010

Installation manual

12

6.3.

Installation method for prevention of falling over

If it is necessary to prevent the unit from falling over, install as shown
in the figure.

prepare all 4 wires as indicated in the drawing

unscrew the top plate at the 4 locations indicated A and B

put the screws through the nooses and screw them back tight

7.

I

NSTALLATION

 

SERVICING

 

SPACE

The numerical figures used in the figures represent the dimensions in
mm.

(Refer to 

"6. Precautions on installation" on page 11

)

Precaution

(A) In case of non-stacked installation (see 

figure 1

  for ERHQ,

see 

figure 1

 for ERLQ)

(B) In case of stacked installation (for ERHQ only)

1.

In case obstacles exist in front of the outlet side.

2.

In case obstacles exist in front of the air inlet.

Do not stack more than one unit.

About 100 mm is required as the dimension for laying the upper
outdoor unit's drain pipe. Get the portion A sealed so that air from the
outlet does not bypass.

(C) In case of multiple-row installation (for roof top use, etc.)(for
ERHQ only)

1.

In case of installing one unit per row.

2.

In case of installing multiple units (2 units or more) in lateral
connection per row.

Relation of dimensions of H, A and L are shown in the table below.

A

Location of the 2 fixation holes on the front side of the unit

B

Location of the 2 fixation holes on the rear side of the unit

C

Wires: field supply

Suction side obstacle

Obstacle is present

Discharge side obstacle

1

In these cases, close the 
bottom of the installation 
frame to prevent the 
discharged air from 
being bypassed

Left side obstacle

Right side obstacle

2

In these cases, only 
2 units can be installed.

Top side obstacle

3

Recommended 
installation setup.

(a)

(a) Specific for ERLQ to prevent exposure to wind or that the heat exchanger 

coil is affected by snow.

This situation is not 
allowed

C

B

A

A

1000

100

A

L

A

L

H

0<L

1/2H

250

1/2H<L

300

H<L

Installation not allowed

300

100

A

1000

200

2000

100

1500

600

3000

A

H

L

Содержание altherma ERHQ014BAV3

Страница 1: ...STALLATION MANUAL ERHQ011BAV3 ERHQ014BAV3 ERHQ016BAV3 ERHQ011BAW1 ERHQ014BAW1 ERHQ016BAW1 ERLQ011CAV3 ERLQ014CAV3 ERLQ016CAV3 ERLQ011CAW1 ERLQ014CAW1 ERLQ016CAW1 Outdoor unit for air to water heat pum...

Страница 2: ...150 500 500 500 500 750 100 100 100 100 200 200 200 300 300 300 300 250 300 250 300 1000 1000 1000 1000 1000 1000 1000 1000 1000 1250 1500 1500 1000 100 250 500 1000 1000 1000 500 500 500 500 500 500...

Страница 3: ...le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr e...

Страница 4: ...nal refrigerant charge for ERLQ models 18 12 5 Complete recharging 19 For ERHQ only 19 For ERLQ only 19 13 Pump down operation 19 14 Electrical wiring work 19 14 1 Precautions on electrical wiring wor...

Страница 5: ...ctivities described in this manual shall be carried out by an installer Be sure to wear adequate personal protection equipment protection gloves safety glasses when performing installation maintenance...

Страница 6: ...r the refrigerant after the pump down operation Refer to chapter 13 Pump down operation on page 19 Never directly touch any accidental leaking refrigerant This could result in severe wounds caused by...

Страница 7: ...pecial equipment insulation bottom plate heater to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions In such conditions the ERHQ models may...

Страница 8: ...t ERLQ Standard a a Factory mounted Not applicable c c No drain socket available for ERLQ ERHQ Optional kit b b Combination of both options is prohibited Optional kit b Snow cover Demand pcb ERLQ EK01...

Страница 9: ...nd power supply 3 Reactor coil s 13 Gas stop valve 4 4 way valve 14 Liquid stop valve 5 Noise filter pcb only for V3 models 15 Electronic expansion valve main 6 Service pcb only for V3 models 16 Solen...

Страница 10: ...1HC S1NPH S1PH W1 R1T R4T R5T 1 Indoor unit EKHBH X016 14 Stop valve with service port 5 16 2 Outdoor unit 15 Crank case heater 3 Heat exchanger 16 Fan motor 4 Service port 5 16 17 Injection valve 5 C...

Страница 11: ...door unit 16 Fan motor 3 Heat exchanger 17 Electronic expansion valve injection 4 Service port 5 16 18 Capillary tube 5 Compressor 19 Solenoid valve hot gas pass 6 Accumulator R1T Thermistor air 7 Pre...

Страница 12: ...and this may have the following consequences Deterioration of the operational capacity Frequent frost acceleration in heating operation Disruption of operation due to rise of high pressure When a stro...

Страница 13: ...tion site where the snow will not affect the unit and set the outlet side at a right angle to the direction of the wind For ERLQ only Follow the procedure as described below for modifying the position...

Страница 14: ...ERHQ Check in the combination table under Possible options on page 5 whether drain work is allowed In case drain work on your unit is allowed and the installation site requires drain work then follow...

Страница 15: ...for laying the upper outdoor unit s drain pipe Get the portion A sealed so that air from the outlet does not bypass C In case of multiple row installation for roof top use etc for ERHQ only 1 In case...

Страница 16: ...rts shall comply with the applicable legislation and shall be suitable for refrigerant Use phosphoric acid deoxidised seamless copper for refrigerant Installation shall be done by a licensed refrigera...

Страница 17: ...her When connecting the piping always use a spanner and torque wrench together to tighten the flare nut to prevent flare nut cracking and leaks Not recommended but in case of emergency Should you be f...

Страница 18: ...ed where indicated by the arrow Take care not to damage it After handling the stop valve make sure to tighten the stem cap securely For the tightening torque refer to the table below Check for refrige...

Страница 19: ...stop valve can move to the indoor unit To avoid this please cover the stop valve with sealing material If the temperature is higher than 30 C and the humidity is higher than RH 80 then the thickness...

Страница 20: ...The stop valves can now be opened and or additional refrigerant can be charged see 12 Charging refrigerant on page 17 12 CHARGING REFRIGERANT 12 1 Important information regarding the refrigerant used...

Страница 21: ...tional amount of refrigerant to be charged using the table below Table 1 Additional charging of refrigerant unit kg For W1 models It is not necessary to charge additionally if the piping length is und...

Страница 22: ...unit wiring on page 20 so that it does not come in contact with the piping particularly on the high pressure side Make sure no external pressure is applied to the terminal connectors When installing t...

Страница 23: ...in properly 14 3 Precautions on wiring of power supply and inter unit wiring Use a round crimp style terminal for connection to the power supply terminal board In case it cannot be used due to unavoid...

Страница 24: ...ntroller ERHQ_V3 ERLQ_V3 ERHQ_W1 ERLQ_W1 Phase and frequency 1 50 Hz 3N 50 Hz Voltage 230 V 400 V Recommended field fuse 32 A 40 A 20 A Minimum circuit amps a a Stated values are maximum values see el...

Страница 25: ...al operation of the unit a number of checks and inspections should be carried out on the unit at regular intervals preferably yearly This maintenance shall be carried out by the installer or service a...

Страница 26: ...Painted galvanised steel Dimensions h x w x d mm 1170 x 900 x 320 1345 x 900 x 320 Weight kg 103 108 114 114 Operation range cooling min max C 10 46 heating min max C 20 a 35 a See operation range dat...

Страница 27: ...ransmission circuit for V3 models only V1R Power module for V3 models only V1R V2R Power module for W1 models only V2R V3R Diode module for V3 models only V3R Diode module for W1 models only V1T Insul...

Страница 28: ...NOTES NOTES...

Страница 29: ...NOTES NOTES...

Страница 30: ...NOTES NOTES...

Страница 31: ...5 6 1 2 3 16 16a V3 type 1 50 Hz 230 V R410A 1 2 4 5 6 3 W1 type 3N 50 Hz 400 V L1 L3 L2 L1 L3 L2 5 6 NOTES...

Страница 32: ...4PW57794 1 08 2010 Copyright 2010 Daikin...

Отзывы: