7 Installation
Installer reference guide
40
ERHQ+ERLQ011~016 + 16CBV
Daikin Altherma – Low temperature split
4P449970-1 – 2016.06
Typical workflow
Connecting the water piping typically consists of the following
stages:
1
Connecting the water piping to the indoor unit.
2
Connecting the water piping to the backup heater (if applicable).
3
Filling the water circuit.
4
Filling the domestic hot water tank.
5
Insulating the water piping.
7.9.2
Precautions when connecting the water
piping
INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
7.9.3
To connect the water piping
NOTICE
Do NOT use excessive force when connecting the piping.
Deformation of the piping can cause malfunctioning of the
unit.
To facilitate service and maintenance, 2 shut-off valves are provided.
Mount the valves on the water inlet and on the water outlet. Mind
their position: the integrated drain valves will only drain the side of
the circuit on which they are located. To be able to only drain the
unit, make sure the drain valves are positioned between the shut‑off
valves and the unit.
1
Install the shut-off valves on the water pipes.
a
b
a
Water inlet
b
Water outlet
NOTICE
To avoid damage to the surroundings in case of water
leakage, it is recommended to close the cold water inlet
shut‑off valves during periods of absence.
2
Screw the indoor unit nuts on the shut-off valves.
3
Connect the field piping on the shut-off valves.
4
In case of connection with the optional domestic hot water tank,
see the installation manual of the domestic hot water tank.
NOTICE
Install air purge valves at all local high points.
NOTICE
▪ A drain device and pressure relief device should be
installed on the cold water inlet connection of the
domestic hot water cylinder.
▪ To avoid back siphonage, it is recommended to install a
non-return valve on the water inlet of the domestic hot
water tank in accordance with the applicable legislation.
▪ It is recommended to install a pressure reducing valve
on the cold water inlet in accordance with the
applicable legislation.
▪ An expansion vessel should be installed on the cold
water inlet in accordance with the applicable legislation.
▪ It is recommended to install the pressure relief valve on
a higher position than the top of the domestic hot water
tank. Heating of the domestic hot water tank causes
water to expand and without pressure relief valve the
water pressure inside the tank can rise above the tank
design pressure. Also the field installation (piping,
tapping points, etc.) connected to the tank is subjected
to this high pressure. To prevent this, a pressure
relieve valve needs to be installed. The overpressure
prevention depends on the correct operation of the field
installed pressure relief valve. If this is NOT working
correctly, overpressure will deform the tank and water
leakage may occur. To confirm good operation, regular
maintenance is required.
7.9.4
To connect the water piping to the backup
heater
NOTICE
Do NOT use excessive force when connecting the piping.
Deformation of the piping can cause malfunctioning of the
unit. Make sure that the tightening torque does NOT
exceed 30 N•m.
1
Connect the water piping (field supply) to the water in- and
outlet of the backup heater.
b
a
a
Water inlet
b
Water outlet
INFORMATION
Inside the backup heater, an automatic air purge valve is
installed. For instructions on how to perform an air purge,
refer to
"9.4.2 Air purge function" on page 75
.
7.9.5
To fill the water circuit
1
Connect the water supply hose to the drain and fill valve.