 Status and configuration flag registers:

You can set the mode and view the alarms and status of the controller via the relevant flags of some registers.
 
 Operation mode setting register PRG, address 201

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

-

-

-

-

-

-

-

-

Stby

-

-

LOCK

-

PRG

 

– 

PRG:

 000=Sutomatic; 001=Silent; 010=Night; 011=Maximum

– 

LOCK: 

0= Keyboard enabled; 1= Keyboard disabled locally

– 

Stby: 

0=Normal operation; 1=Stand-by mode

– 

8-15:

 System Flags reserved, do not change the status

 
 Output status relay register OUT, address 009

7

6

5

4

3

2

1

0

-

-

-

-

BOILER

CHILLER

EV2

EV1

 
 Flag STAT status, address 104

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

H4

asnt

H2

asnt

Com

err.

stby

test

alrm

Antig

0

B.A.

F.V.

H4

F.V.

H2

Mod.

Risc.

Mod.

Raff.

 

– 

Mod. Risc./Mod. Rafr:

 Active mode;

– 

F.V. H2:

 Fan stop water not suitable on H2;

– 

F.V. H4:

 Fan stop water not suitable on H4;

– 

B.A.:

 Stop for unsuitable water (machine in standby for 45 minutes)

– 

Antig.: 

Device in antifreeze mode

– 

Alrm:

 At least one alarm present

– 

Test:

 Instrument in test mode for testing

– 

Stby: 

Device in standby

– 

Com err:

 Timeout master (vers. Centralised B32) of 300sec

– 

H2 asnt:

 on board with H2 probe, the probe is absent on start up

– 

H4 asnt:

 on board with H4 probe, the probe is absent on start up

 
 Alarm flag ALR_STAT, address 105

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

0

0

0

2 AIR

M5

Filter

H2

n. id

SW

GRL

Mot

Hi

Res

H4

n. id

H2

Acq.

Dan.

H4

AIR

Com.

 

– 

Com.:

 “Blind” version communication error

– 

AIR:

 AIR probe

– 

H4:

 H4 probe

– 

Acq. Dan.:

 Block for harmful water

– 

H2:

 H2 probe

– 

H4 n. id:

 Coil hot water temperature not suitable (version 2 and 4 pipes)

– 

Hi Res: 

High temperature resistance

– 

Mot.: 

Motor fault

– 

GRID:

 GRID contact open

– 

H2 n. id:

 Main coil water temperature not suitable (version 2 and 4 pipes)

– 

Filtro: 

Maintenance required (dirty filter)

– 

2 AIR M4 (only for M4 control panel): 

Communication error with fancoil with remote air probe or presence of more than 

one board with air probe ('E2’ displayed)

Содержание Altherma EKWHCTRL1

Страница 1: ...third parties with out the express authorization of the manufacturer Description The terminal board AB of the INN FR B32 Printed circuit board allows the connection of the same present in the con tro...

Страница 2: ...ation network follow the indication on the connection diagram collegarsi al connettore ModBus con serigrafia presente sulla scheda connect respecting the indication A and B For all other connections r...

Страница 3: ...n with a minimum section of 0 35 mm Keeping the bipolar cable separate from power supply cables Chase out the wall in order to minimize the length of the leads Complete the line with the 120 resistanc...

Страница 4: ...in MIN and Minimum in MAX R W 1 680 230 MVVP3 MVV5 MVVP1 Maximum speed in MIN and Minimum in MAX with Performance enabled R W 1 920 213 MVV2 MVV4 1500 Maximum speed in AUTO R W 1 1100 234 MVVP2 MVV4...

Страница 5: ...le water machine in standby for 45 minutes Antig Device in antifreeze mode Alrm At least one alarm present Test Instrument in test mode for testing Stby Device in standby Com err Timeout master vers C...

Страница 6: ...nt within SPL_W SPH_W preventing off scale values at the same time Pressing the SET and SET keys outside the limits makes the icon flash temporarily FLAG 6 247 6 Disables all keys The user cannot perf...

Страница 7: ...9 register is set to 0 when the CP contact presence closes the PCB goes into standby mode Check the input status You cannot turn off the appliance using the button or change function All the keys are...

Отзывы: