 Electrical connections EKWHCTRL1 with on-board Printed circuit board EKWHCTRL0

ModBus RTU Serial Connection

Serial connection for fancoil

+ A B -

A A B B -

A

B

For connection of the electronic board to a "Modicon Mod-
Bus" RTU serial communication network:
–  connect to the terminal block on the wall control unit

For all other connections, refer to the diagrams and in-
structions in the installation manual.

The choice of materials and the routing of the connection 

are fundamental for correct operation.

Use a bipolar shielded cable suitable for the RS485 serial 
connection with a minimum section of 0,35 mm².

Keeping the bipolar cable separate from power supply 
cables.

Chase out the wall in order to minimize the length of the 
leads.

Complete the line with the 120 Ω resistance.

It is forbidden make "star" connections.

1. 

Terminal block for device connection

2. 

The terminal block for CP presence contact connection

3. 

PCB

3

1

2

3

CP

+ A B -

A A B B -

N540022B

N540022B

L

N

 Serial Port Features

 Protocol

The serial communication protocol is “Modicon Modbus” in 
RTU mode with the following settings:
•  baudrate=9600
•  data bits=8
•  parità=nessuna
•  stop bit=1
 
The implemented functions are:

•  “03” and “06” respectively for the reading and writing of a 

single register

•  the main adjustment parameters (R/W), the acquired tem-

perature and the operating status are made available

Содержание Altherma EKWHCTRL1

Страница 1: ...third parties with out the express authorization of the manufacturer Description The terminal board AB of the INN FR B32 Printed circuit board allows the connection of the same present in the con tro...

Страница 2: ...ation network follow the indication on the connection diagram collegarsi al connettore ModBus con serigrafia presente sulla scheda connect respecting the indication A and B For all other connections r...

Страница 3: ...n with a minimum section of 0 35 mm Keeping the bipolar cable separate from power supply cables Chase out the wall in order to minimize the length of the leads Complete the line with the 120 resistanc...

Страница 4: ...in MIN and Minimum in MAX R W 1 680 230 MVVP3 MVV5 MVVP1 Maximum speed in MIN and Minimum in MAX with Performance enabled R W 1 920 213 MVV2 MVV4 1500 Maximum speed in AUTO R W 1 1100 234 MVVP2 MVV4...

Страница 5: ...le water machine in standby for 45 minutes Antig Device in antifreeze mode Alrm At least one alarm present Test Instrument in test mode for testing Stby Device in standby Com err Timeout master vers C...

Страница 6: ...nt within SPL_W SPH_W preventing off scale values at the same time Pressing the SET and SET keys outside the limits makes the icon flash temporarily FLAG 6 247 6 Disables all keys The user cannot perf...

Страница 7: ...9 register is set to 0 when the CP contact presence closes the PCB goes into standby mode Check the input status You cannot turn off the appliance using the button or change function All the keys are...

Отзывы: