Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Installer setting at variance with
default value
Field settings table
└─ Bivalent
9.C.1
[C-02]
R/W
0: No
1: Bivalent
9.C.2
[7-05]
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
9.C.3
[C-03]
R/W
-25~25°C, step: 1°C
0°C
9.C.4
[C-04]
R/W
2~10°C, step 1°C
3°C
Installer settings
9.D
[C-09]
R/W
0: Normally open
1: Normally closed
9.E
[3-00]
R/W
0: No
1: Yes
9.F
[E-08]
R/O
1: Enabled
9.G
R/W
0: No
1: Yes
└─ Overview field settings
9.I
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
9.I
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
50°C
9.I
[0-02]
R/W
10~25°C, step: 1°C
15°C
9.I
[0-03]
R/W
-40~5°C, step: 1°C
-10°C
9.I
[0-04]
8
9.I
[0-05]
12
9.I
[0-06]
35
9.I
[0-07]
20
9.I
[0-0B]
R/W
35~[6-0E]°C, step: 1°C
55°C
9.I
[0-0C]
R/W
45~[6-0E]°C, step: 1°C
6
0°C
9.I
[0-0D]
R/W
10~25°C, step: 1°C
15°C
9.I
[0-0E]
R/W
-40~5°C, step: 1°C
-10°C
9.I
[1-00]
R/W
-40~5°C, step: 1°C
-10°C
9.I
[1-01]
R/W
10~25°C, step: 1°C
15°C
9.I
[1-02]
R/W
[9-01]~[9-00], step: 1°C
35°C
9.I
[1-03]
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
25°C
9.I
[1-04]
1
9.I
[1-05]
1
9.I
[1-06]
20
9.I
[1-07]
35
9.I
[1-08]
22
9.I
[1-09]
18
9.I
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
9.I
[1-0B]
R/W
3~10°C, step: 1°C
5°C
9.I
[1-0C]
R/W
3~10°C, step: 1°C
5°C
9.I
[1-0D]
5
9.I
[1-0E]
5
9.I
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
9.I
[2-01]
R/W
0: No
1: Yes
9.I
[2-02]
R/W
0~23 hour, step: 1 hour
1
9.I
[2-03]
R/W
60°C
9.I
[2-04]
R/W
40~60 min, step: 5 min
40 min
9.I
[2-05]
R/W
4~16°C, step: 1°C
12°C
9.I
[2-06]
R/W
0: Disabled
1: Enabled
9.I
[2-09]
R/W
-5~5°C, step: 0,5°C
0°C
9.I
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
9.I
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
9.I
[2-0C]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.I
[2-0D]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
--
--
What is the desired delta T in heating for the main zone?
--
--
--
Low ambient temp. for DHW WD curve.
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
--
--
--
--
What is the disinfection target temperature?
What emitter type is connected to the main LWT zone?
What emitter type is connected to the additional LWT zone?
How long must the tank temperature be maintained?
Room antifrost temperature
Room frost protection
Adjust the offset on the measured room temperature
Adjust the offset on the measured room temperature
What is the required offset on the measured outdoor temp.?
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
High ambient temp. for DHW WD curve.
--
--
--
When should the disinfection function be executed?
Should the disinfection function be executed?
When should the disinfection function start?
Auto restart
Power saving function
Disable protections
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
What is the averaging time for the outdoor temp?
Bivalent
Boiler efficiency
Temperature
Hysteresis
Alarm output
What is the desired delta T in heating for the additional zone?
4P495259-1A - 2017.11
(#) Setting is not applicable for this unit.
(*1) *3V_
(*2) *6V_
(*3) *9W