![Daikin Altherma EHVZ04S18DA6V Скачать руководство пользователя страница 50](http://html.mh-extra.com/html/daikin/altherma-ehvz04s18da6v/altherma-ehvz04s18da6v_installers-reference-manual_501272050.webp)
8 Configuration
Installer reference guide
50
ERGA04~08DAV3(A) + 08S18+23DA
Daikin Altherma – Low temperature split
4P495249-1 – 2017.12
NOTICE
The maximum setpoint in space heating depends on the
emitter type as can be seen in above table. If there are 2
water temperature zones, then the maximum setpoint is
the maximum of the 2 zones.
CAUTION
If there are 2 zones, it is important that the zone with the
lowest water temperature is configured as the main zone,
and the zone with the highest water temperature is
configured as the additional zone. Not configuring the
system in this way could cause damage to the heat
emitters.
CAUTION
If there are 2 zones and the emitter types are wrongly
configured, water of high temperature can be sent towards
a low temperature emitter (underfloor heating). To avoid
this:
▪ Install an aquastat/thermostatic valve to avoid too high
temperatures towards a low temperature emitter.
▪ Make sure you set the emitter types for the main zone
[2.7] and for the additional zone [3.7] correctly in
accordance with the connected emitter.
INFORMATION
Depending on the target delta T, the average emitter
temperature will vary. To counteract the effect on the
average emitter temperature due to a higher delta T target,
the leaving water setpoint (fixed or weather dependent)
can be adjusted.
Setpoint range
You can limit the range of the leaving water temperature for the main
leaving water temperature zone. The purpose of this setting is to
prevent a wrong (i.e. too hot or too cold) leaving water temperature.
Therefore, the available desired heating temperature range can be
configured.
NOTICE
In case of a floor heating application it is important to limit
the maximum leaving water temperature at heating
operation according to the specifications of the floor
heating installation.
INFORMATION
Only for EHVZ: If the indoor unit is connected to a high
temperature emitter system, and simultaneous demand
exists on both emitter zones, and if the high emitter system
leaving water setpoint is chosen bigger than 60°C in the
complete operation range, there can be an increased
power consumption.
NOTICE
▪ When adjusting the leaving water temperature ranges,
all desired leaving water temperatures are also
adjusted to guarantee they are between the limits.
▪ Always balance between the desired leaving water
temperature with the desired room temperature and/or
the capacity (according to the design and selection of
the heat emitters). The desired leaving water
temperature is the result of several settings (preset
values, shift values, weather dependent curves,
modulation). As a result, too high or too low leaving
water temperatures could occur which lead to
overtemperatures or capacity shortage. By limiting the
leaving water temperature range to adequate values
(depending on the heat emitter), such situations can be
avoided.
Example:
Set the minimum leaving water temperature to 28°C to
avoid NOT to be able to heat up the room: leaving water
temperatures MUST be sufficiently higher than the room
temperatures (in heating).
#
Code
Description
Leaving water temperature range for the main leaving water
temperature zone (= the leaving water temperature zone with the
lowest leaving water temperature in heating operation)
[2.8.1]
[9-01]
Heating minimum 15°C~37°C
[2.8.2]
[9-00]
Heating maximum
▪ [2‑0C]=2 (emitter type main zone =
radiator)
37°C~65°C
▪ Otherwise: 37°C~55°C
Control
For the control of the unit there are 3 possibilities:
Control
In this control...
Leaving water
Unit operation is decided based on the leaving
water temperature regardless the actual room
temperature and/or heating demand of the
room.
External room
thermostat
Unit operation is decided by the external
thermostat or equivalent (e.g. heat pump
convector).
Room thermostat
Unit operation is decided based on the ambient
temperature of the user interface used as a
room thermostat.
#
Code
Description
[2.9]
[C‑07]
▪ 0: Leaving water
▪ 1: External room thermostat
▪ 2: Room thermostat
Thermostat type
Only applicable in external room thermostat control.
Following combinations are possible to control the unit (not
applicable when [C‑07]=0):
When [C‑07]=2 (RT control)
Содержание Altherma EHVZ04S18DA6V
Страница 100: ...4P495249 1 2017 12 Copyright 2017 Daikin ...