8 Configuration
Installer reference guide
55
ERGA04~08DAV3(A) + 08S23DAV
Daikin Altherma – Low temperature split
4P499573-1A – 2018.11
#
Code
Description
Leaving water temperature range for the main leaving water
temperature zone (= the leaving water temperature zone with the
lowest leaving water temperature in heating operation)
[2.8.1]
[9-01]
Heating minimum 15°C~37°C
[2.8.2]
[9-00]
Heating maximum
▪ [2‑0C]=2 (emitter type main zone =
radiator)
37°C~65°C
▪ Otherwise: 37°C~55°C
Control
For the control of the unit there are 3 possibilities:
Control
In this control...
Leaving water
Unit operation is decided based on the leaving
water temperature regardless the actual room
temperature and/or heating demand of the
room.
External room
thermostat
Unit operation is decided by the external
thermostat or equivalent (e.g. heat pump
convector).
Room thermostat
Unit operation is decided based on the ambient
temperature of the user interface used as a
room thermostat.
#
Code
Description
[2.9]
[C‑07]
▪ 0: Leaving water
▪ 1: External room thermostat
▪ 2: Room thermostat
Thermostat type
Only applicable in external room thermostat control.
NOTICE
If an external room thermostat is used, the external room
thermostat will control the room frost protection. However,
the room frost protection is only possible if the leaving
water temperature control on the unit's user interface is
turned ON.
#
Code
Description
[2.A]
[C‑05]
External room thermostat type for the
main zone:
▪ 1: 1 contact: The used external room
thermostat can only send a thermo
ON/OFF condition. There is no
separation between heating or cooling
demand. The room thermostat is
connected to only 1 digital input
(X2M/35).
Select this value in case of a
connection to the heat pump convector
(FWXV).
▪ 2: 2 contacts: The used external room
thermostat can send a separate
heating/cooling
thermo
ON/OFF
condition. The room thermostat is
connected to 2 digital inputs (X2M/35
and X2M/34).
Select this value in case of a
connection to the wired (EKRTWA) or
wireless (EKRTR1) room thermostat
Leaving water temperature: Delta T
The target delta T in heating for the main zone depends on the
emitter type for the main zone selected above. In heating, this
setting indicates the temperature difference between the leaving
water setpoint and entering water.
The unit is designed to support under floor loops operation. The
recommended leaving water temperature for under floor loops is
35°C. In such case, the unit will be controlled to realize a
temperature difference of 5°C which means that the unit entering
water temperature is around 30°C. Depending on the installed
application (radiators, heat pump convector, under floor loops) or
situation, it can be possible to change the difference between
entering and leaving water temperature. Note that the pump will
regulate its flow to keep the delta T. In some special cases, the
measured delta T can be different from the set value.
INFORMATION
When only the anti‑legionella heater is active in heating,
delta T will be controlled according to the fixed capacity of
the anti‑legionella heater. It is possible that this delta T is
different from the selected target delta T.
INFORMATION
In heating, the target delta T will only be achieved after
some operation time, when the setpoint is being reached,
because of the big difference between leaving water
temperature setpoint and inlet temperature at startup.
INFORMATION
If the main zone or the additional zone has a heating
demand, and this zone is equipped with radiators, then the
target delta T that the unit will use in heating operation will
be 10°C fixed.
If the zones are not equipped with radiators, then in
heating the unit will give priority to the target delta T for the
additional zone, if there is a heating demand in the
additional zone.
#
Code
Description
[2.B.1]
[1‑0B]
Delta T heating: A minimum temperature
difference is required for the good
operation of heat emitters in heating
mode.
▪ If [2-0C]=2, this is fixed to 10°C
▪ Else: 3°C~10°C