7 Installation
Installer reference guide
44
ERGA04~08DAV3(A) + 08S23DAV
Daikin Altherma – Low temperature split
4P499573-1A – 2018.11
7.9.8
To connect the main power supply
1
Connect the main power supply.
In case of normal kWh rate power supply
X1M
X2M
X5M
X11YB
X1A
X11Y
X11YA
1 2 3
1 2 3
a
1 2 3
Legend: see illustration below.
In case of preferential kWh rate power supply
Connect X11Y to X11YB.
X1M
X2M
X5M
X11Y
X11YB
X1A
1 2 3
1
N L
N L
2 3
S1S
a
b
c
X11YA
5
1 2 3
6
9 10
a
Interconnection cable (=main power supply)
b
Normal kWh rate power supply
c
Preferential power supply contact
2
Fix the cables with cable ties to the cable tie mountings.
INFORMATION
In case of preferential kWh rate power supply, connect
X11Y to X11YB. The necessity of separate normal kWh
rate power supply to indoor unit (b) X2M/5+6 depends on
the type of preferential kWh rate power supply.
Separate connection to the indoor unit is required:
▪ if preferential kWh rate power supply is interrupted
when active, OR
▪ if no power consumption of the indoor unit is allowed at
the preferential kWh rate power supply when active.
INFORMATION
The preferential kWh rate power supply contact is
connected to the same terminals (X5M/9+10) as the safety
thermostat. It is only possible for the system to have
EITHER preferential kWh rate power supply OR a safety
thermostat.
7.9.9
To connect the shut-off valve
1
Connect the valve control cable to the appropriate terminals as
shown in the illustration below.
NOTICE
Wiring is different for a NC (normal closed) valve and a NO
(normal open) valve.
X1M
X2M
X1M
X2M
NO
NC
M2S
M2S
21 28
21 29
2
Fix the cable with cable ties to the cable tie mountings.
7.9.10
To connect the electrical meters
INFORMATION
In case of an electrical meter with transistor output, check
the polarity. The positive polarity MUST be connected to
X5M/6 and X5M/4; the negative polarity to X5M/5 and
X5M/3.
1
Connect the electrical meters cable to the appropriate terminals
as shown in the illustration below.
X1M
X2M
X5M
S3S S2S
3456
2
Fix the cable with cable ties to the cable tie mountings.
7.9.11
To connect the domestic hot water pump
1
Connect the domestic hot water pump cable to the appropriate
terminals as shown in the illustration below.
X1M
X2M
X5M
1~
M
M2P
1 2
2
Fix the cable with cable ties to the cable tie mountings.
7.9.12
To connect the alarm output
1
Connect the alarm output cable to the appropriate terminals as
shown in the illustration below.