6 Commissioning

Installation manual

19

EBLQ+07CAV3
Daikin Altherma low temperature monobloc
4P403578-1F – 2018.06

NOTICE

When  purging  air  with  the  manual  air  purge  valve  of  the
unit, collect any fluid that might leak out of the valve. If this
fluid is NOT collected, it might drip on internal components
and damage the unit.

INFORMATION

▪ To  purge  air,  use  all  air  purge  valves  present  in  the

system. This includes the manual air purge valve of the
outdoor unit, as well as any field-supplied valves.

▪ If the system contains a backup heater, also use the air

purge valve of the backup heater.

▪ If  the  system  contains  valve  kit  EKMBHBP1,  it  is

required to – during the air purge – manually switch the
position  of  the  valve  kit's  3‑way  valve  by  turning  its
knob, this to prevent air from remaining in the bypass.
For  more  information,  refer  to  the  instruction  sheet  of
the valve kit.

6.2.2

To perform a test run

Prerequisite: 

Make  sure  that  the  leaving  water  temperature  home

page, room temperature home page, and domestic hot water home
page are turned OFF.

1

Set the user permission level to Installer. See 

"To set the user

permission level to Installer" on page 12

.

2

Go  to  [A.7.1]: 

  >  Installer  settings  >  Commissioning  >  Test

run.

3

Select a test and press 

Example: 

Heating.

4

Select OK and press 

.

Result: 

The  test  run  starts.  It  stops  automatically  when  done

(±30 min). To stop it manually, press 

, select OK and press 

.

INFORMATION

When  starting  up  the  system  in  a  cold  climate,  and  NO
backup heater kit was installed, it may be required to start
up  with  a  small  water  volume.  To  do  this,  gradually  open
the  heat  emitters.  As  a  result,  the  water  temperature  will
gradually  rise.  Monitor  the  inlet  water  temperature  ([6.1.6]
in  the  menu  structure)  and  make  sure  it  does  NOT  drop
below 15°C.

INFORMATION

If  2  user  interfaces  are  present,  you  can  start  a  test  run
from both user interfaces.

▪ The user interface used to start the test run displays a

status screen.

▪ The other user interface displays a "busy" screen. You

cannot  use  the  user  interface  as  long  as  the  "busy"
screen is shown.

6.2.3

To perform an actuator test run

Prerequisite: 

Make  sure  that  the  leaving  water  temperature  home

page, room temperature home page, and domestic hot water home
page are turned OFF.

1

Set the user permission level to Installer. See 

"To set the user

permission level to Installer" on page 12

.

2

Make  sure  the  room  temperature  control,  the  leaving  water
temperature  control  and  the  domestic  hot  water  control  are
turned OFF via the user interface.

3

Go  to  [A.7.4]: 

  >  Installer  settings  >  Commissioning  >

Actuator test run.

4

Select an actuator and press 

Example: 

Pump.

5

Select OK and press 

.

Result: 

The  actuator  test  run  starts.  It  automatically  stops  when

finished. To stop it manually, press 

, select OK and press 

.

Possible actuator test runs

▪ Booster heater test

▪ Backup heater (step 1) test

▪ Backup heater (step 2) test

▪ Pump test

INFORMATION

Make  sure  that  all  air  is  purged  before  executing  the  test
run. Also avoid disturbances in the water circuit during the
test run.

▪ 2-way valve test

▪ 3-way valve test

▪ Alarm output test

▪ Cooling/heating signal test

▪ Quick heat-up test

▪ Circulation pump test

6.2.4

To perform an underfloor heating screed
dryout

Prerequisite: 

Make sure there is ONLY 1 user interface connected

to your system to perform an underfloor heating screed dryout.

Prerequisite: 

Make  sure  that  the  leaving  water  temperature  home

page, room temperature home page, and domestic hot water home
page are turned OFF.

1

Go  to  [A.7.2]: 

  >  Installer  settings  >  Commissioning  >  UFH

screed dryout.

2

Set a dryout program.

3

Select Start dryout and press 

.

4

Select OK and press 

.

Result: 

The  underfloor  heating  screed  dryout  starts.  It  stops

automatically  when  done.  To  stop  it  manually,  press 

,  select  OK

and press 

.

NOTICE

To perform an underfloor heating screed dryout, room frost
protection needs to be disabled ([2‑06]=0). By default, it is
enabled  ([2‑06]=1).  However,  due  to  the  "installer-on-site"
mode  (see  "Checklist  before  commissioning"),  room  frost
protection  will  be  automatically  disabled  for  36  hours  after
the first power-on.

If  the  screed  dryout  still  needs  to  be  performed  after  the
first  36  hours  of  power-on,  manually  disable  room  frost
protection  by  setting  [2‑06]  to  "0",  and  KEEP  it  disabled
until the screed dryout has finished. Ignoring this notice will
result in cracking of the screed.

NOTICE

For the underfloor heating screed dryout to be able to start,
make sure the following settings are met:

▪ [4‑00]=1

▪ [C‑02]=0

▪ [D‑01]=0

▪ [4‑08]=0

▪ [4‑01]≠1

Содержание Altherma EBLQ07CAV3

Страница 1: ...Installation manual Daikin Altherma low temperature monobloc English Installation manual Daikin Altherma low temperature monobloc EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3...

Страница 2: ...mi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 1...

Страница 3: ...t during commissioning 18 6 2 1 To perform an air purge 18 6 2 2 To perform a test run 19 6 2 3 To perform an actuator test run 19 6 2 4 To perform an underfloor heating screed dryout 19 7 Hand over t...

Страница 4: ...726 The diffusion of oxygen into the piping can lead to excessive corrosion 3 2 1 To check the water volume and flow rate Minimum water volume If Then The system contains a backup heater The minimum w...

Страница 5: ...ngle user interface and dual user interface connection c Minimum cable section 0 75 mm d Cable section 0 75 mm till 1 25 mm maximum length 20 m e If valve kit EKMBHBP1 is part of the system then the r...

Страница 6: ...e unit Additionally make sure the unit is positioned at least 100 mm above the maximum expected level of snow mm 1 5 0 1 5 0 a 330 300 283 7 4 0 0 mm 100 a Maximum snowfall height It is possible to in...

Страница 7: ...iding drainage therefore make sure to cover the entire unit NOTICE If the unit is installed in a cold climate take adequate measures so that the evacuated condensate CANNOT freeze INFORMATION For info...

Страница 8: ...wever in case of a power failure these functions cannot guarantee protection It is therefore recommended to add glycol to the water circuit The required concentration depends on the lowest expected ou...

Страница 9: ...m For more information refer to the chapter To check the water volume and flow rate in the installer reference guide 4 3 3 To fill the water circuit 1 Connect the water supply hose to the drain and fi...

Страница 10: ...3 X4M 2 3 1 1 GND 2 L 3 N 4 4 3 To connect the user interface INFORMATION If control box EKCB07CAV3 is NOT part of the system connect the user interface directly to the outdoor unit If control box EK...

Страница 11: ...trol box To do this connect outdoor unit terminals X3M 1 2 to control box terminals X8M 6 7 and then connect the shut off valve to control box terminals X8M 6 7 X2M X8M 6 7 X5M X3M M2S 1 2 4 4 5 To co...

Страница 12: ...r more than 1 hour or press again for more than 4 seconds the installer permission level switches back to End user To set the user permission level to Advanced end user 1 Go to the main menu or any of...

Страница 13: ...See also illustrations below Domestic hot water pump installed for Instant hot water Disinfection c f a g h b c h b a d f e g a Outdoor unit b Tank c Domestic hot water pump d Heater element e Non ret...

Страница 14: ...so table below Alarm output logic A 2 2 F 3 D 08 Optional external kWh meter 1 0 No NOT installed 1 Installed 0 1 pulse kWh 2 Installed 1 pulse kWh 3 Installed 10 pulse kWh 4 Installed 100 pulse kWh 5...

Страница 15: ...erature difference between entering and leaving water In case a minimum temperature difference is required for the good operation of the heat emitters in cooling mode Leaving water temperature Modulat...

Страница 16: ...ater Type 0 Reheat only Only reheat operation is allowed 1 Reheat sched Same as 2 but between the scheduled heatup cycles reheat operation is allowed 2 Scheduled only The domestic hot water tank can O...

Страница 17: ...ration mode Power saving possible User interface location Options DHW pump External sensor Control box Option box Leaving water Main Additional Delta T source Room thermostat Room temp range Room temp...

Страница 18: ...ox of the control box is turned ON The correct pipe size is installed and the pipes are properly insulated There are no water leaks inside the outdoor unit The shut off valves are properly installed a...

Страница 19: ...ing water temperature home page room temperature home page and domestic hot water home page are turned OFF 1 Set the user permission level to Installer See To set the user permission level to Installe...

Страница 20: ...the maintenance of the unit Explain the user about energy saving tips as described in the operation manual 7 1 About locking and unlocking If required it is possible to lock the buttons of the main us...

Страница 21: ...CuT 1 4 3 2 t 12 7 CuT 12 7 CuT R4T 9 5 CuT 6 4 CuT 6 4 CuT M 6 4 CuT 6 4 CuT Discharge pipe thermistor Accumulator Compressor High pressure switch Muffler Muffler 4 way valve Pressure sensor Refrige...

Страница 22: ...nnector X1M X2M Terminal strip Y1E Electronic expansion valve coil Y1R Reversing solenoid valve coil Z1C Z4C Ferrite core Field wiring Terminal strip Connector Terminal Protective earth BLK Black BLU...

Страница 23: ...mostat PC power circuit A3P Heat pump convector A4P Extension PCB control optional A5P User interface PCB A7P Receiver PCB wireless On OFF thermostat F2B Overcurrent fuse booster heater K3M Contactor...

Страница 24: ...ection voltage supplied by PCB Power limitation digital inputs 5 V DC detection voltage supplied by PCB Space C H On OFF output Space cooling heating On OFF output 2 Legend 2 Legend A4P Extension PCB...

Страница 25: ...a 2 Only for heat pump convector Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 2 core 3m included signal R2T External sensor floor or ambient Only for KRTETS External indo...

Страница 26: ......

Страница 27: ......

Страница 28: ...4P403578 1F 2018 06 Copyright 2015 Daikin...

Отзывы: