5 Start-up
WARNING!
A Daikin Altherma M ECH
2
O erected and
installed incorrectly may not operate properly
and can be dangerous for the health and safety
of individuals.
●
The Daikin Altherma M ECH
2
O must only be
commissioned by authorised and trained
heating specialists.
CAUTION!
If the Daikin Altherma M ECH
2
O is not started
up properly, it could lead to material or environ-
mental damage.
●
Observe the current technological regula-
tions to prevent corrosion products and
deposits. Minimum requirements regarding
the quality of filling and supplementary water:
– Water hardness (calcium and magnesium,
calculated as calcium carbonate):
≤
3 mmol/l
– Conductivity:
≤
1500
(ideally
≤
100)
μ
S/cm
– Chloride:
≤
250
mg/l
– Sulphate:
≤
250
mg/l
– pH value (heating water): 6.5 - 8.5.
●
If the above-mentioned minimum water
quality requirements set by the local water
supply company cannot be guaranteed,
suitable water treatment measures must be
taken.
●
The domestic water quality must comply with
the EU Guideline 98/83
EC and the
regionaly-applicable regulations.
●
The water pressure must be checked at
regular intervals during system operation. If
necessary, correct the pressure by topping
up with water
CAUTION!
●
Make sure that the parameter [Glycol] corre-
sponds to the fluid in the water circuit (0
=
water only, 1
= water
+ glycol). If the glycol
setting is NOT correct, the fluid inside the
pipes can freeze.
●
If glycol has been added to the system but
the glycol concentration is lower than
specified, the fluid can still freeze in the
pipes.