8
|
Configuration
Installer reference guide
108
C08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
Quick wizard: Standard
Space heating settings
The system can heat up a space. Depending on the type of application, the space
heating settings must be made accordingly.
#
Code
Description
[A.2.1.7]
[C-07]
Unit temperature control:
▪
0 (
LWT control
): Not applicable.
▪
1 (
Ext RT control
): Unit operation is
decided by the external thermostat or
equivalent (e.g. heat pump convector).
▪
2 (
RT control
)(default): Unit operation is
decided based on the ambient temperature of
the user interface.
[A.2.1.B]
N/A
Only if there are 2 user interfaces (1 installed in
the room, 1 installed at the indoor unit):
a
b
▪
a: At unit
▪
b: In room as room thermostat
User interface location
:
▪
At unit
: this user interface is used to control
the unit. The other user interface is
automatically set to
In room
.
▪
In room
(default): this user interface acts as
room thermostat. The other user interface is
automatically set to
At unit