6 Energy saving tips

Operation manual

17

ELSH/X(B)12P30+50E
Daikin Altherma 3 R MT ECH

O

4P708485-1 – 2023.01

5.9.4

Using weather-dependent curves

Configure weather-dependent curves as following:

To define the setpoint mode

To use the weather-dependent curve, you need to define the correct
setpoint mode:

Go to setpoint mode …

Set the setpoint mode to …

Main zone – Heating

[2.4] 

EN20190625

 > 

Setpoint

mode

WD heating, fixed cooling

OR 

Weather dependent

Main zone – Cooling

[2.4] 

EN20190625

 > 

Setpoint

mode

Weather dependent

Additional zone – Heating

[3.4] 

Additional zone

 >

Setpoint mode

WD heating, fixed cooling

OR 

Weather dependent

Additional zone – Cooling

[3.4] 

Additional zone

 >

Setpoint mode

Weather dependent

Tank

[5.B] 

Tank

 > 

Setpoint mode

Restriction: 

Only available to

installers.

Weather dependent

To change the type of weather-dependent curve

To change the type for all zones (main + additional) and for the tank,
go to [2.E] 

EN20190625

 > 

WD curve type

.

Viewing which type is selected is also possible via:

▪ [3.C] 

Additional zone

 > 

WD curve type

▪ [5.E] 

Tank

 > 

WD curve type

Restriction: 

Only available to installers.

To change the weather-dependent curve

Zone

Go to …

Main zone – Heating

[2.5] 

EN20190625

 > 

Heating WD

curve

Main zone – Cooling

[2.6] 

EN20190625

 > 

Cooling WD

curve

Additional zone – Heating

[3.5] 

Additional zone

 >

Heating WD curve

Additional zone – Cooling

[3.6] 

Additional zone

 >

Cooling WD curve

Tank

Restriction: 

Only available to

installers.

[5.C] 

Tank

 > 

WD curve

INFORMATION

Maximum and minimum setpoints

You cannot configure the curve with temperatures that are
higher  or  lower  than  the  set  maximum  and  minimum
setpoints for that zone or for the tank. When the maximum
or minimum setpoint is reached, the curve flattens out.

To fine-tune the weather-dependent curve: slope-offset curve

The  following  table  describes  how  to  fine-tune  the  weather-
dependent curve of a zone or tank:

You feel …

Fine-tune with slope and

offset:

At regular outdoor

temperatures …

At cold outdoor

temperatures …

Slope

Offset

OK

Cold

You feel …

Fine-tune with slope and

offset:

At regular outdoor

temperatures …

At cold outdoor

temperatures …

Slope

Offset

OK

Hot

Cold

OK

Cold

Cold

Cold

Hot

Hot

OK

Hot

Cold

Hot

Hot

To fine-tune the weather-dependent curve: 2-points curve

The  following  table  describes  how  to  fine-tune  the  weather-
dependent curve of a zone or tank:

You feel …

Fine-tune with

setpoints:

At regular outdoor

temperatures …

At cold outdoor

temperatures …

Y2

(a)

Y1

(a)

X1

(a)

X2

(a)

OK

Cold

OK

Hot

Cold

OK

Cold

Cold

Cold

Hot

Hot

OK

Hot

Cold

Hot

Hot

(a)

See 

"5.9.2 2-points curve"

 [

4

 16].

6

Energy saving tips

Tips about room temperature

▪ Make  sure  the  desired  room  temperature  is  NEVER  too  high  (in

heating  mode)  or  too  low  (in  cooling  mode),  but  ALWAYS
according  to  your  actual  needs.  Each  saved  degree  can  save  up
to 6% of heating/cooling costs.

▪ Do  NOT  increase/decrease  the  desired  room  temperature  to

speed up space heating/cooling. The space will NOT heat up/cool
down faster.

▪ When  your  system  layout  contains  slow  heat  emitters  (example:

underfloor  heating),  avoid  large  fluctuation  of  the  desired  room
temperature  and  do  NOT  let  the  room  temperature  drop  too  low/
rise  too  high.  It  will  take  more  time  and  energy  to  heat  up/cool
down the room again.

▪ Use  a  weekly  schedule  for  your  normal  space  heating  or  cooling

needs. If necessary, you can easily deviate from the schedule:

▪ For  shorter  periods:  You  can  overrule  the  scheduled  room

temperature  until  the  next  scheduled  action. 

Example: 

When

you have a party, or when you are leaving for a couple of hours.

▪ For longer periods: You can use the holiday mode.

Tips about DHW temperature

▪ Make  sure  the  desired  DHW  temperature,  reflected  by  storage

tank  temperature,  is  NOT  too  high. 

Example: 

After  installation,

lower the tank temperature daily by 1°C and check if you still have
enough hot water.

Содержание Altherma 3 RMT ECH2O

Страница 1: ...n manual Daikin Altherma 3 R MT ECH O English Operation manual Daikin Altherma 3 R MT ECH O ELSH12P30E ELSH12P50E ELSHB12P30E ELSHB12P50E ELSX12P30E ELSX12P50E ELSXB12P30E ELSXB12P50E 1 2 3 9 A B C Z...

Страница 2: ...be filled in by installer 20 11 1 Configuration wizard 20 11 2 Settings menu 20 1 About this document Thank you for purchasing this product Please Read the documentation carefully before operating th...

Страница 3: ...nce Cleaning and user maintenance SHALL NOT be made by children without supervision WARNING To prevent electrical shocks or fire Do NOT rinse the unit Do NOT operate the unit with wet hands Do NOT pla...

Страница 4: ...ors Before you purge air from heat emitters or collectors check if or is displayed on the home screen of the user interface If not you can purge air immediately If yes make sure that the room where yo...

Страница 5: ...ernal room thermostat control the protection is NOT guaranteed 1 Go to C 2 Operation Space heating cooling Operation Space heating cooling Tank Off On C 2 2 Set operation to On or Off To change the de...

Страница 6: ...e temperatures Change the temperature Go to the next temperature Confirm changes and proceed More information For more information see also 5 4 Turning operation ON or OFF 411 5 6 Space heating coolin...

Страница 7: ...e display Dials and buttons You use the dials and buttons To navigate through the screens menus and settings of the LCD screen To set values a b c d e Item Description a Left dial The LCD shows an arc...

Страница 8: ...ar Month Day Daylight savings time Format 7 3 Holiday Activation From Till 7 4 Quiet Mode Schedule Level 7 5 Electricity price High Medium Low Schedule 5 Tank Powerful operation Schedule 1 9 Room comf...

Страница 9: ...p failure and system operates in Emergency mode or heat pump is forced off d Current date and time e Smart energy e1 Smart energy is available via solar panels or smart grid e2 Smart energy is current...

Страница 10: ...symbol for your main zone emitter type Set the leaving water temperature for the main zone 3 Additional zone Restriction Only displayed if there are two leaving water temperature zones Shows the appl...

Страница 11: ...tection Even if you turn OFF space heating cooling operation C 2 Operation Space heating cooling room frost protection operation if enabled can still activate However for leaving water temperature con...

Страница 12: ...to the Operation mode schedule 4 2 To restrict automatic changeover according to a schedule Conditions You set the space operation mode to Automatic 1 Go to 4 2 Space heating cooling Operation mode s...

Страница 13: ...perature drops below a preset value set temperature hysteresis value example 40 C the tank is heated up to 50 C During the afternoon and evening you consume hot water again and the DHW tank temperatur...

Страница 14: ...day of which you want to clear the content For example Friday Mon Sat Wed Fri Thu Tue Sun User defined 1 C 2 Select Delete Delete Edit Copy 3 Select OK to confirm To program the schedule for Monday 1...

Страница 15: ...operation The unit operates weather dependent if the desired leaving water or tank temperature is determined automatically by the outdoor temperature It therefore is connected to a temperature sensor...

Страница 16: ...temperature is heated increasingly more at decreasingly lower ambient temperatures Change the offset to equally increase or decrease the temperature of the leaving water for different ambient temperat...

Страница 17: ...s how to fine tune the weather dependent curve of a zone or tank You feel Fine tune with slope and offset At regular outdoor temperatures At cold outdoor temperatures Slope Offset OK Cold You feel Fin...

Страница 18: ...eater WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cleaning materials or means to accelerate the defrosting process other than those recommended by the manufacturer Be aware that t...

Страница 19: ...larly as in Manual mode the unit can take the full load with the backup heater or boiler if the user activates this via the Malfunctioning main menu screen When the heat pump fails or will appear on t...

Страница 20: ...s 4 4 Solar 9 2 4 Backup heater Voltage 9 3 2 Configuration 9 3 3 Capacity step 1 9 3 4 Additional capacity step 2 9 3 5 if applicable EN20190625 Emitter type 2 7 Control 2 9 Setpoint mode 2 4 Schedul...

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ...4P708485 1 2023 01 Copyright 2023 Daikin 4P708485 1 0000000U Verantwortung f r Energie und Umwelt...

Отзывы: