background image

5 Operation

Operation manual

16

ELSH/X(B)12P30+50E

Daikin Altherma 3 R MT ECH

O

4P708485-1 – 2023.01

INFORMATION

To  operate  weather-dependent,  correctly  configure  the
setpoint  of  the  main  zone,  additional  zone  or  tank.  See

"5.9.4 Using weather-dependent curves"

 [

4

 17].

5.9.2

2-points curve

Define the weather-dependent curve with these two setpoints:

▪ Setpoint (X1, Y2)

▪ Setpoint (X2, Y1)

Example

Y1

Y2

X1

X2

a

Item

Description

a

Selected weather-dependent zone:

: Main zone or additional zone heating

: Main zone or additional zone cooling

: Domestic hot water

X1, X2

Examples of outdoor ambient temperature

Y1, Y2

Examples of desired tank temperature or leaving water
temperature. The icon corresponds to the heat emitter
for that zone:

: Underfloor heating

: Fan coil unit

: Radiator

: Storage tank

Possible actions on this screen

Go through the temperatures.

Change the temperature.

Go to the next temperature.

Confirm changes and proceed.

5.9.3

Slope-offset curve

Slope and offset

Define the weather-dependent curve by its slope and offset:

▪ Change  the 

slope

  to  differently  increase  or  decrease  the

temperature  of  the  leaving  water  for  different  ambient
temperatures.  For  example,  if  leaving  water  temperature  is  in
general  fine  but  at  low  ambient  temperatures  too  cold,  raise  the
slope  so  that  leaving  water  temperature  is  heated  increasingly
more at decreasingly lower ambient temperatures.

▪ Change  the 

offset

  to  equally  increase  or  decrease  the

temperature  of  the  leaving  water  for  different  ambient
temperatures. For example, if leaving water temperature is always
a bit too cold at different ambient temperatures, shift the offset up
to  equally  increase  the  leaving  water  temperature  for  all  ambient
temperatures.

Examples

Weather-dependent curve when slope is selected:

X1

X2

c

d

e

Y1

Y2

Y3

Y4

a

b

Weather-dependent curve when offset is selected:

Y1

Y2

Y3

Y4

X1

X2

a

b

c

d

e

Item

Description

a

WD curve before changes.

b

WD curve after changes (as example):

▪ When  slope  is  changed,  the  new  preferred

temperature  at  X1  is  unequally  higher  than  the
preferred temperature at X2.

▪ When  offset  is  changed,  the  new  preferred

temperature  at  X1  is  equally  higher  as  the  preferred
temperature at X2.

c

Slope

d

Offset

e

Selected weather-dependent zone:

: Main zone or additional zone heating

: Main zone or additional zone cooling

: Domestic hot water

X1, X2

Examples of outdoor ambient temperature

Y1, Y2,

Y3, Y4

Examples of desired tank temperature or leaving water
temperature. The icon corresponds to the heat emitter
for that zone:

: Underfloor heating

: Fan coil unit

: Radiator

: Storage tank

Possible actions on this screen

Select slope or offset.

Increase or decrease the slope/offset.

When slope is selected: set slope and go to offset.

When offset is selected: set offset.

Confirm changes and return to the submenu.

Содержание Altherma 3 RMT ECH2O

Страница 1: ...n manual Daikin Altherma 3 R MT ECH O English Operation manual Daikin Altherma 3 R MT ECH O ELSH12P30E ELSH12P50E ELSHB12P30E ELSHB12P50E ELSX12P30E ELSX12P50E ELSXB12P30E ELSXB12P50E 1 2 3 9 A B C Z...

Страница 2: ...be filled in by installer 20 11 1 Configuration wizard 20 11 2 Settings menu 20 1 About this document Thank you for purchasing this product Please Read the documentation carefully before operating th...

Страница 3: ...nce Cleaning and user maintenance SHALL NOT be made by children without supervision WARNING To prevent electrical shocks or fire Do NOT rinse the unit Do NOT operate the unit with wet hands Do NOT pla...

Страница 4: ...ors Before you purge air from heat emitters or collectors check if or is displayed on the home screen of the user interface If not you can purge air immediately If yes make sure that the room where yo...

Страница 5: ...ernal room thermostat control the protection is NOT guaranteed 1 Go to C 2 Operation Space heating cooling Operation Space heating cooling Tank Off On C 2 2 Set operation to On or Off To change the de...

Страница 6: ...e temperatures Change the temperature Go to the next temperature Confirm changes and proceed More information For more information see also 5 4 Turning operation ON or OFF 411 5 6 Space heating coolin...

Страница 7: ...e display Dials and buttons You use the dials and buttons To navigate through the screens menus and settings of the LCD screen To set values a b c d e Item Description a Left dial The LCD shows an arc...

Страница 8: ...ar Month Day Daylight savings time Format 7 3 Holiday Activation From Till 7 4 Quiet Mode Schedule Level 7 5 Electricity price High Medium Low Schedule 5 Tank Powerful operation Schedule 1 9 Room comf...

Страница 9: ...p failure and system operates in Emergency mode or heat pump is forced off d Current date and time e Smart energy e1 Smart energy is available via solar panels or smart grid e2 Smart energy is current...

Страница 10: ...symbol for your main zone emitter type Set the leaving water temperature for the main zone 3 Additional zone Restriction Only displayed if there are two leaving water temperature zones Shows the appl...

Страница 11: ...tection Even if you turn OFF space heating cooling operation C 2 Operation Space heating cooling room frost protection operation if enabled can still activate However for leaving water temperature con...

Страница 12: ...to the Operation mode schedule 4 2 To restrict automatic changeover according to a schedule Conditions You set the space operation mode to Automatic 1 Go to 4 2 Space heating cooling Operation mode s...

Страница 13: ...perature drops below a preset value set temperature hysteresis value example 40 C the tank is heated up to 50 C During the afternoon and evening you consume hot water again and the DHW tank temperatur...

Страница 14: ...day of which you want to clear the content For example Friday Mon Sat Wed Fri Thu Tue Sun User defined 1 C 2 Select Delete Delete Edit Copy 3 Select OK to confirm To program the schedule for Monday 1...

Страница 15: ...operation The unit operates weather dependent if the desired leaving water or tank temperature is determined automatically by the outdoor temperature It therefore is connected to a temperature sensor...

Страница 16: ...temperature is heated increasingly more at decreasingly lower ambient temperatures Change the offset to equally increase or decrease the temperature of the leaving water for different ambient temperat...

Страница 17: ...s how to fine tune the weather dependent curve of a zone or tank You feel Fine tune with slope and offset At regular outdoor temperatures At cold outdoor temperatures Slope Offset OK Cold You feel Fin...

Страница 18: ...eater WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cleaning materials or means to accelerate the defrosting process other than those recommended by the manufacturer Be aware that t...

Страница 19: ...larly as in Manual mode the unit can take the full load with the backup heater or boiler if the user activates this via the Malfunctioning main menu screen When the heat pump fails or will appear on t...

Страница 20: ...s 4 4 Solar 9 2 4 Backup heater Voltage 9 3 2 Configuration 9 3 3 Capacity step 1 9 3 4 Additional capacity step 2 9 3 5 if applicable EN20190625 Emitter type 2 7 Control 2 9 Setpoint mode 2 4 Schedul...

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ...4P708485 1 2023 01 Copyright 2023 Daikin 4P708485 1 0000000U Verantwortung f r Energie und Umwelt...

Отзывы: