7/11
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Installer setting at variance with
default value
Field settings table
9.A.2
[D-09]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
└─ Sensors
9.B.1
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
9.B.2
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
9.B.3
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
└─ Bivalent
9.C.1
[C-02]
R/W
0: No
1: Bivalent
9.C.2
[7-05]
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
9.C.3
[C-03]
R/W
-25~25°C, step: 1°C
0°C
9.C.4
[C-04]
R/W
2~10°C, step 1°C
3°C
Installer settings
9.D
[C-09]
R/W
0: Normally open
1: Normally closed
9.E
[3-00]
R/W
0: No
1: Yes
9.F
[E-08]
R/W
0: disabled
1: Enabled
9.G
R/W
0: No
1: Yes
└─ Overview field settings
9.I
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
[2-0C]=0
25°C
[2-0C]=1
35°C
[2-0C]=2
35°C
9.I
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
[2-0C]=0
35°C
[2-0C]=1
45°C
[2-0C]=2
65°C
9.I
[0-02]
R/W
10~25°C, step: 1°C
15°C
9.I
[0-03]
R/W
-40~5°C, step: 1°C
-15°C
9.I
[0-04]
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0C]=0
18°C(*3)
[2-0C]=1
7°C(*3)
[2-0C]=2
18°C(*3)
9.I
[0-05]
R/W
[9-07]~[9-08]°C, step: 1°C
22°C(*3)
9.I
[0-06]
R/W
25~43°C, step: 1°C
35°C(*3)
9.I
[0-07]
R/W
10~25°C, step: 1°C
20°C(*3)
9.I
[0-0B]
R/W
35~[6-0E]°C, step: 1°C
55°C
9.I
[0-0C]
R/W
45~[6-0E]°C, step: 1°C
6
0°C
9.I
[0-0D]
R/W
10~25°C, step: 1°C
15°C
9.I
[0-0E]
R/W
-40~5°C, step: 1°C
-10°C
9.I
[1-00]
R/W
-40~5°C, step: 1°C
-15°C
9.I
[1-01]
R/W
10~25°C, step: 1°C
15°C
9.I
[1-02]
R/W
[9-01]~[9-00], step: 1°C
[2-0C]=0
35°C
[2-0C]=1
45°C
[2-0C]=2
65°C
9.I
[1-03]
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
[2-0C]=0
25°C
[2-0C]=1
35°C
[2-0C]=2
35°C
9.I
[1-04]
R/W
0: Disabled
1: Enabled
9.I
[1-05]
R/W
0: Disabled
1: Enabled
9.I
[1-06]
R/W
10~25°C, step: 1°C
20°C(*3)
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Electricity meter 2
External sensor
Averaging time
Bivalent
Boiler efficiency
Temperature
Hysteresis
Alarm output
Auto restart
Power saving function
Disable protections
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Leaving water value for high ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
High ambient temp. for DHW WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
High ambient temp. for LWT add zone cooling WD curve.
Weather dependent cooling of the additional leaving water temperature zone
Low ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT main zone cooling WD curve.
Low ambient temp. for DHW WD curve.
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Weather dependent cooling of the main leaving water temperature zone.
Ext. amb. sensor offset
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
(*1) *6V_
(*2) *9W_
(*3) + EKHVCONV2
(#) Only applicable in Swedish language.