9
|
Configuration
Installer reference guide
193
EPRA14~W1 + ETVH/9W(G)
Daikin Altherma 3 H HT F
4P587502-1B – 2020.12
To enable the power saving function setting, [E‑08] needs to be enabled on the
user interface.
#
Code
Description
[9.F]
[E‑08]
Power saving function
for outdoor unit:
▪
0:
No
▪
1:
Yes
Disable protections
INFORMATION
Protective functions – "Installer-on-site mode".
The software is equipped with
protective functions, such as room antifrost. The unit automatically runs these
functions when necessary.
During installation or service this behaviour is undesired. Therefore, the protective
functions can be disabled:
▪
At first power-on:
The protective functions are disabled by default. After 36 h
they will be automatically enabled.
▪
Afterwards:
An installer can manually disable the protective functions by setting
[9.G]:
Disable protections
=
Yes
. After his work is done, he can enable the
protective functions by setting [9.G]:
Disable protections
=
No
.
#
Code
Description
[9.G]
N/A
Disable protections
:
▪
0:
No
▪
1:
Yes
Forced defrost
Forced defrost
Manually start a defrost operation.
#
Code
Description
[9.H]
N/A
Do you want to start a defrost operation?
▪
Back
▪
OK
NOTICE
Forced defrost start-up.
You can only start forced defrost when the heating
operation has been running for a while.
Overview field settings
All settings can be done using the menu structure. If for any reason it is required to
change a setting using the overview settings, then the overview settings can be
accessed in the field settings overview [9.I]. See
117].