8
|
Electrical installation
Installer reference guide
113
EPRA14~W1 + ETBH/9W
Daikin Altherma 3 H HT W
4P587501-1A – 2020.01
C
1 2
X2M
B
X2M
3
Fix the cable with cable ties to the cable tie mountings.
8.3.6 To connect the alarm output
Wires: (2+1)×0.75 mm²
Maximum load: 0.3 A, 250 V AC
[9.D]
Alarm output
1
Open the following (see
"6.2.5 To open the indoor unit"
1
Front panel
1
2
3
2
Switch box cover
3
Switch box
2
Connect the alarm output cable to the appropriate terminals as shown in the
illustration below.
7 9
YC
Y1
X2M
1
2
3
A4P
1+2
Wires connected to the alarm output
3
Wire between X2M and A4P
A4P
Installation of EKRP1HBAA is
required.
B
C
A
A
7
Y1