5
|
Application guidelines
Installer reference guide
30
EPRA14~W1 + ETVH/9W(G)
Daikin Altherma 3 H HT F
4P587502-1 – 2019.07
Configuration
Setting
Value
Unit temperature control:
▪
#: [2.9]
▪
Code: [C-07]
1 (
External room thermostat
):
Unit operation is decided by the
external thermostat.
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7-02]
0 (
Single zone
): Main
External room thermostat for the
main
zone:
▪
#: [2.A]
▪
Code: [C-05]
1 (
1 contact
): When the used
external room thermostat or heat pump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
Benefits
▪
Wireless.
The Daikin external room thermostat is available in a wireless version.
▪
Efficiency.
Although the external room thermostat only sends ON/OFF signals, it
is specifically designed for the heat pump system.
▪
Comfort.
In case of underfloor heating, the wireless external room thermostat
prevents condensation on the floor during cooling operation by measuring the
room humidity.
Heat pump convectors
Setup
A
B
a
A
Main leaving water temperature zone
B
One single room
a
Heat pump convectors (+ controllers)
▪
For more information about connecting the electrical wiring to the unit, see:
-
"8.2 Connections to the outdoor unit"
-
"8.3 Connections to the indoor unit"
▪
The heat pump convectors are directly connected to the indoor unit.
▪
The desired room temperature is set via the controller of the heat pump
convectors. There are different controllers and setups possible for the heat pump
convectors. For more information, see:
-
The installation manual of the heat pump convectors
-
The installation manual of the heat pump convector options
-
The addendum book for optional equipment