5 Electrical installation
Installation manual
12
EGSAH/X06+10DA9W(G)
Daikin Altherma 3 GEO
4P569811-1 – 2019.02
#
Power supply
(a)
Operation
(b)
1
Combined power supply
(1N~, 50 Hz, 230 V AC)
C1
1N~, 50 Hz,
230 V AC
Normal or emergency
2
Split power supply
(2×(1N~, 50 Hz, 230 V AC))
C1
C5
1N~, 50 Hz,
230 V AC
1N~, 50 Hz,
230 V AC
Emergency
(a)
For details of C1 and C5, see
.
(b)
Normal operation:
backup heater = maximum 3 kW
Emergency operation:
backup heater = maximum 6 kW
5.2
Overview of electrical connections
for external and internal actuators
Item
Description
Power supply
"5.3 To connect the main power
Remote outdoor
sensor
"5.4 To connect the remote outdoor
.
Shut-off valve
"5.5 To connect the shut-off valve" on
Electricity meter
"5.6 To connect the electricity
Domestic hot water
pump
"5.7 To connect the domestic hot water
.
Alarm output
"5.8 To connect the alarm output" on
Space cooling/heating
operation control
"5.9 To connect the space cooling/
heating ON/OFF output" on page 17
Changeover to
external heat source
control
"5.10 To connect the changeover to
external heat source" on page 18
Power consumption
digital inputs
consumption digital inputs" on page 18
.
Safety thermostat
"5.12 To connect the safety thermostat
(normal closed contact)" on page 19
Brine low pressure
switch
"5.13 To connect the brine low
.
LAN adapter
connections
.
Item
Description
Room thermostat
(wired or wireless)
See:
▪ Installation manual of the room
thermostat (wired or wireless)
▪ Addendum
book
for
optional
equipment
Wires for wired room thermostat: (3
for cooling/heating operation; 2 for
heating only operation)×0.75 mm²
Wires for wireless room thermostat: (5
for cooling/heating operation; 4 for
heating only operation)×0.75 mm²
Maximum running current: 100 mA
For the main zone:
▪ [2.9]
Control
▪ [2.A]
Thermostat type
For the additional zone:
▪ [3.A]
Thermostat type
▪ [3.9] (read-only)
Control
Heat pump convector
See:
▪ Installation manual of the heat
pump convectors
▪ Addendum
book
for
optional
equipment
Wires: 4×0.75 mm²
Maximum running current: 100 mA
For the main zone:
▪ [2.9]
Control
▪ [2.A]
Thermostat type
For the additional zone:
▪ [3.A]
Thermostat type
▪ [3.9] (read-only)
Control
Remote indoor sensor
See:
▪ Installation manual of the remote
indoor sensor
▪ Addendum
book
for
optional
equipment
Wires: 2×0.75 mm²
[9.B.1]=2 (
External sensor
=
Room
)
[1.7]
Room sensor offset
Current sensors
See the installation manual of the
current sensors.
Wires: 3×2. Use part of the cable
(40 m) delivered as accessory.
[9.9.1]=3 (
Power consumption
control
=
Current sensor
)
[9.9.E]
Current sensor offset