Operation manual

13

E(D/B)(H/L)Q011~0W1

Unit for air to water heat pump system and options

4PW51122-1

[5-04] Set point correction for domestic hot water
temperature: set point correction for the desired domestic hot
water temperature, to be applied at low outdoor temperature
when space heating priority is enabled. The corrected
(higher) set point will make sure that the total heat capacity of
the water in the tank remains approximately unchanged, by
compensating for the colder bottom water layer of the tank
(because the heat exchanger coil is not operational) with a
warmer top layer.

[6] DT for domestic water heating

Applies only to installations with a domestic hot water tank.

The 'DT (delta temperature) for domestic water heating' field settings
determine the temperatures at which heating of the domestic water
by  the heat pump will be started (i.e., the heat pump ON
temperature) and stopped (i.e., the heat pump OFF temperature).
When the domestic hot water temperature drops below the heat
pump ON temperature (

T

HP ON

), heating of the domestic hot water by

the heat pump will be started. As soon as the domestic hot water
temperature reaches the heat pump OFF temperature (

T

HP OFF

) or

the user set point temperature (

T

U

), heating of the domestic water by

the heat pump will be stopped (by switching the 3-way valve).

The heat pump OFF temperature, and the heat pump ON
temperature, and its relation with field settings [6-00] and [6-01] are
explained in the illustration below.

[6-00] Start: temperature difference determining the heat
pump ON temperature (

T

HP ON

). See illustration.

[6-01] Stop: temperature difference determining the heat
pump OFF temperature (

T

HP OFF

). See illustration.

[7] Domestic hot water step length

Applies only to installations with a domestic hot water tank.

When the domestic water is heated and the domestic hot water set
point temperature (as set by the user) has been reached, the booster
heater will continue to heat the domestic water to a temperature a
few degrees above the set point temperature, i.e. the booster heater
OFF temperature. These extra degrees are specified by the domestic
hot water step length field setting. Correct setting prevents the
booster heater from repeatedly turning on and off (i.e. chattering) to
maintain the domestic hot water set point temperature. Note: the
booster heater will turn back on when the domestic hot water
temperature drops 2°C (fixed value) below the booster heater OFF
temperature.

[7-00] Domestic hot water step length: temperature
difference above the domestic hot water set point
temperature before the booster heater is turned off.

T

set

Domestic hot water set point temperature

T

U

User set point (as set on the user interface)

T

A

Ambient (outdoor) temperature

Space heating priority

T

U

User set point temperature (as set on the user interface)

T

HP MAX

Maximum heat pump temperature at sensor in domestic hot 
water tank (55°C)

T

HP OFF

Heat pump OFF temperature

T

HP ON

Heat pump ON temperature

NOTE

T

HP MAX

 is a theoretical value. In reality the maximum

tank temperature that can be reached with the heat
pump is 53°C. It is advised to select T

HP OFF

 not higher

than 48°C in order to improve performance of the heat
pump during domestic water heating mode.

T

A

T

set

T

U

[5-03]

[5-04]

T

> T

HP MAX

T(

°

C)

70

T

U

55

T

HP MAX

48

T

HP OFF

41

T

HP ON

[6-01]

[6-00]

T

< T

HP MAX

T(

°

C)

45

T

U

 = T

HP OFF

55

T

HP MAX

38

T

HP ON

[6-00]

T

= 45

°

C

[6-01] =  7

°

C

[6-00] =  7

°

C

T

= 70

°

C

[6-01] =  7

°

C

[6-00] =  7

°

C

NOTE

If the schedule timer for booster heater (see the
operation manual) is active, the booster heater will only
operate if allowed by this schedule timer.

BH

Booster heater

HP

Heat pump. If heating up time by the heat pump takes too 
long, auxiliary heating by the booster heater can take place

T

BH OFF

Booster heater OFF temperature (T

U

 + [7-00]) 

T

BH ON

Booster heater ON temperature (T

BH OFF

 – 2°C)

T

HP MAX

Maximum heat pump temperature at sensor in domestic hot 
water tank

T

HP OFF

Heat pump OFF temperature (T

HP MAX

 – [6-01])

T

HP ON

Heat pump ON temperature (T

HP OFF

 – [6-00])

T

DHW

Domestic hot water temperature

T

U

User set point temperature (as set on the user interface)

t

Time

NOTE

If the booster heater operation is limited
([4-03]=0), then set point of field setting parameter
[7-00] has no meaning.

t

T

BH ON

T

DHW

T

HP ON

T

HP OFF

T

HP MAX

T

U

T

BH OFF

[6-01]
[6-00]

[7-00]

T

U

= 70

°

C

[7-00] =

3

°

C

[6-01] =

7

°

C

[6-00] =

7

°

C

HP

BH

HP

0

10

20

30

40

41

48

55

60

71
70

73

Содержание Alterma EBHQ011AA6V3

Страница 1: ...AA6W1 EDLQ011AA6V3 EDLQ014AA6V3 EDLQ016AA6V3 EDLQ011AA6W1 EDLQ014AA6W1 EDLQ016AA6W1 EBHQ011AA6V3 EBHQ014AA6V3 EBHQ016AA6V3 EBHQ011AA6W1 EBHQ014AA6W1 EBHQ016AA6W1 EBLQ011AA6V3 EBLQ014AA6V3 EBLQ016AA6V3 EBLQ011AA6W1 EBLQ014AA6W1 EBLQ016AA6W1 Unit for air to water heat pump system and options ...

Страница 2: ...nits and heating only units The AD outdoor monoblock unit range consists of two main versions a heating cooling EB version and a heating only ED version Both versions are delivered with an integrated backup heater for additional heating capacity during cold outdoor temperatures The backup heater also serves as a backup in case of malfunctioning of the unit and for freeze protection of the outside ...

Страница 3: ...th low electricity cost tariffs in mind To do this program both the domestic water heating and booster heating schedule timer Refer to Programming in chapter Programming and consulting the schedule timer on page 7 OPERATING THE DIGITAL CONTROLLER Operating the unit comes down to operating the digital controller Features and functions The digital controller is a state of the art controller that off...

Страница 4: ... is required on the installation Consult your dealer 11 SET TEMPERATURE DISPLAY 9 The display shows the current set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whenever a non installed option is addressed or a function is not available 14 DEFROST STARTUP MODE ICON d This icon indicates that the defrost startup mode is...

Страница 5: ...oller is set in permission level 2 or 3 refer to Field settings on page 10 the quiet mode button will not be operable Setting up the controller After initial installation the user can set the clock and day of the week The controller is equipped with a schedule timer that enables the user to schedule operations Setting the clock and day of the week is required to be able to use the schedule timer S...

Страница 6: ... C during commissioning of the installation When set lower than 25 C only the backup heater will operate In order to avoid overheating space heating is not operable when the outdoor ambient temperature rises above a certain temperature as set through field setting 4 02 refer to Field settings on page 10 Temperature range for cooling 5 C to 22 C 3 Switch on the unit by pushing the y button The oper...

Страница 7: ...ther dependent or manually set Five actions per weekday can be programmed totalling 35 actions 2 Quiet mode refer to Programming quiet mode booster heating or domestic water heating on page 9 Switch the mode on or off at a scheduled time Five actions can be programmed per mode These actions are repeated daily 3 Booster heating refer to Programming quiet mode booster heating or domestic water heati...

Страница 8: ...ot a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will be executed You can always alter add or remove the programmed actions later When programming heating actions time and set point cooling actions are added automatically at the same time but with the p...

Страница 9: ...n to select x to switch cooling or heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 10 Use the pi and pj buttons to set the correct action time 11 Repeat steps 8 to 10 to program the other actions of the selected day When all actions have been programmed make sure that the display shows the hig...

Страница 10: ...ant to consult 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to consult by means of the pi and pj buttons The selected day is blinking 5 Press the button to confirm the selected day The first programmed action of the selected day appears 6 Use the pi and pj buttons to consult the other progr...

Страница 11: ...g or heating mode 1 Use the button to select the operation mode cooling or heating you want to delete 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to delete by means of the pi and pj buttons The selected day is blinking 5 Press the and ba button simultaneously for 5 seconds to delete the se...

Страница 12: ...der outdoor temperatures i e Lo_A warmer water is required 1 03 Set point at high ambient temperature Hi_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi_A Note that the Hi_Ti value should be lower than Lo_Ti as for warmer outdoor temperatures i e Hi_A less warm water suffices 2 Disinfection function Applies only to install...

Страница 13: ...ture equals or drops below the specified equilibrium temperature When the function is disabled operation of the backup heater is possible at all outdoor temperatures Enabling this function reduces the working time of the backup heater 5 00 Equilibrium temperature status specifies whether the equilibrium temperature function is enabled 1 or disabled 0 5 01 Equilibrium temperature outdoor temperatur...

Страница 14: ...tra degrees are specified by the domestic hot water step length field setting Correct setting prevents the booster heater from repeatedly turning on and off i e chattering to maintain the domestic hot water set point temperature Note the booster heater will turn back on when the domestic hot water temperature drops 2 C fixed value below the booster heater OFF temperature 7 00 Domestic hot water st...

Страница 15: ... water temperature for cooling operation 9 04 Overshoot setting defines how much the water temperature may rise above the setpoint before the compressor stops This function is only applicable in heating mode A Quiet mode This field setting allows to select the desired quiet mode Two quiet modes are available quiet mode A and quiet mode B In quiet mode A priority is given to the unit operating quie...

Страница 16: ...that contact will open and the unit will go in forced off mode 1 When parameter D 01 2 at the moment that the benefit kWh rate signal is sent by the electricity company that contact will close and the unit will go in forced off mode 2 E Unit information readout E 00 Readout of the software version example 23 E 01 Readout of the EEPROM version example 23 E 02 Readout of the unit model identificatio...

Страница 17: ...heating off temperature 25 14 25 1 C 03 Booster heater operation 1 0 1 04 Freeze up protection function 0 active Read only 5 Equilibrium temperature and space heating priority temperature 00 Equilibrium temperature status 1 ON 0 1 01 Equilibrium temperature 0 15 35 1 C 02 Space heating priority status 0 OFF 0 1 03 Space heating priority temperatures 0 15 20 1 C 04 Set point correction for domestic...

Страница 18: ...off heaters 0 0 1 2 3 01 Unit connection to benefit kWh rate power supply 0 OFF 0 1 2 02 Not applicable Do not change the default value 0 E Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Read only 03 Liquid refrigerant temperature Read only C 04 Inlet water temperature Read only C First code Second code Setting name Installer setting...

Страница 19: ...o late or too early Check if the clock and the day of the week are set correctly correct if necessary DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation Your product is marked with this symbol This means that electrical and electronic products shall not be mixed with unsorted h...

Страница 20: ...NOTES NOTES ...

Страница 21: ......

Страница 22: ...4PW51122 1 Copyright Daikin ...

Отзывы: