Operation manual

11

E(D/B)(H/L)Q011~0W1

Unit for air to water heat pump system and options

4PW51122-1

5

Save the new value by pressing the 

pr

 button.

6

Repeat step 2 through 4 to change other field settings as
required.

7

When finished, press the 

z

 button to exit FIELD SET MODE.

Detailed description

[0] User permission level

If required, certain user interface buttons can be made unavailable for
the user.

Three permission levels are defined (see the table below). Switching
between level 1 and level 2/3 is done by simultaneously pressing
buttons 

pfi

  and 

pfj

  immediately followed by

simultaneously pressing buttons 

s

  and 

ba

, and keeping all 4

buttons pressed for at least 5 seconds (in normal mode). Note that no
indication on the user interface is given. When level 2/3 is selected,
the actual permission level — either level 2 or level 3 — is
determined by the field setting [0-00].

[1] Weather dependent set point (heating operation only)

The weather dependent set point field settings define the parameters
for the weather dependent operation of the unit. When weather
dependent operation is active the water temperature is determined
automatically depending on the outdoor temperature: colder outdoor
temperatures will result in warmer water and vice versa. During
weather dependent operation, the user has the possibility to shift up
or down the target water temperature by a maximum of 5°C. See

"Selecting weather dependent set point operation (only in heating
mode)" on page 6

 more details on weather dependent operation.

[1-00] Low ambient temperature (Lo_A): low outdoor
temperature.

[1-01] High ambient temperature (Hi_A): high outdoor
temperature.

[1-02] Set point at low ambient temperature (Lo_Ti): the
target outgoing water temperature when the outdoor
temperature equals or drops below the low ambient
temperature (Lo_A). 
Note that the Lo_Ti value should be higher than Hi_Ti, as for
colder outdoor temperatures (i.e. Lo_A) warmer water is
required.

[1-03] Set point at high ambient temperature (Hi_Ti): the
target outgoing water temperature when the outdoor
temperature equals or rises above the high ambient
temperature (Hi_A). 
Note that the Hi_Ti value should be lower than Lo_Ti, as for
warmer outdoor temperatures (i.e. Hi_A) less warm water
suffices.

[2] Disinfection function

Applies only to installations with a domestic hot water tank.

The disinfection function disinfects the domestic hot water tank by
periodically heating the domestic water to a specific temperature.

[2-00] Operation interval: day(s) of the week at which the
domestic water should be heated.

[2-01] Status: defines whether the disinfection function is
turned on (1) or off (0).

[2-02] Start time: time of the day at which the domestic water
should be heated.

[2-03] Set point: high water temperature to be reached.

[2-04] Interval: time period defining how long the set point
temperature should be maintained.

NOTE

Changes made to a specific field setting are only
stored when the 

pr

 button is pressed. Navigating to a

new field setting code or pressing the 

z

  button will

discard the change made.

NOTE

Before shipping, the set values have been set as
shown under 

"Field settings table" on page 16

.

When exiting FIELD SET MODE, "

88

" may be

displayed on the user interface LCD while the unit
initialises itself.

Button

Permission level

1

2

3

Quiet mode button 

s

operable

Weather dependent 
set point button

ba

operable

Schedule timer 
enable/disable button 

pr

operable

operable

Programming button 

<

operable

Time adjust buttons

pf

i

pf

j

operable

Inspection/test 
operation button 

z

operable

T

t

Target water temperature

T

A

Ambient (outdoor) temperature

= Shift value

The disinfection function field settings must be configured
by the installer according to national and local regulations.

T

DHW

Domestic hot water temperature

T

U

User set point temperature (as set on the user interface)

T

H

High set point temperature [2-03]

t

Time

Lo_Ti

Lo_A

Hi_A

T

A

T

t

+ 05

00

– 05

Hi_Ti

Shift value

00.00

22.00

24.00

01.00

23.00

t

T

DHW

T

H

T

U

[2-02]

[2-03]

[2-04]

Содержание Alterma EBHQ011AA6V3

Страница 1: ...AA6W1 EDLQ011AA6V3 EDLQ014AA6V3 EDLQ016AA6V3 EDLQ011AA6W1 EDLQ014AA6W1 EDLQ016AA6W1 EBHQ011AA6V3 EBHQ014AA6V3 EBHQ016AA6V3 EBHQ011AA6W1 EBHQ014AA6W1 EBHQ016AA6W1 EBLQ011AA6V3 EBLQ014AA6V3 EBLQ016AA6V3 EBLQ011AA6W1 EBLQ014AA6W1 EBLQ016AA6W1 Unit for air to water heat pump system and options ...

Страница 2: ...nits and heating only units The AD outdoor monoblock unit range consists of two main versions a heating cooling EB version and a heating only ED version Both versions are delivered with an integrated backup heater for additional heating capacity during cold outdoor temperatures The backup heater also serves as a backup in case of malfunctioning of the unit and for freeze protection of the outside ...

Страница 3: ...th low electricity cost tariffs in mind To do this program both the domestic water heating and booster heating schedule timer Refer to Programming in chapter Programming and consulting the schedule timer on page 7 OPERATING THE DIGITAL CONTROLLER Operating the unit comes down to operating the digital controller Features and functions The digital controller is a state of the art controller that off...

Страница 4: ... is required on the installation Consult your dealer 11 SET TEMPERATURE DISPLAY 9 The display shows the current set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whenever a non installed option is addressed or a function is not available 14 DEFROST STARTUP MODE ICON d This icon indicates that the defrost startup mode is...

Страница 5: ...oller is set in permission level 2 or 3 refer to Field settings on page 10 the quiet mode button will not be operable Setting up the controller After initial installation the user can set the clock and day of the week The controller is equipped with a schedule timer that enables the user to schedule operations Setting the clock and day of the week is required to be able to use the schedule timer S...

Страница 6: ... C during commissioning of the installation When set lower than 25 C only the backup heater will operate In order to avoid overheating space heating is not operable when the outdoor ambient temperature rises above a certain temperature as set through field setting 4 02 refer to Field settings on page 10 Temperature range for cooling 5 C to 22 C 3 Switch on the unit by pushing the y button The oper...

Страница 7: ...ther dependent or manually set Five actions per weekday can be programmed totalling 35 actions 2 Quiet mode refer to Programming quiet mode booster heating or domestic water heating on page 9 Switch the mode on or off at a scheduled time Five actions can be programmed per mode These actions are repeated daily 3 Booster heating refer to Programming quiet mode booster heating or domestic water heati...

Страница 8: ...ot a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will be executed You can always alter add or remove the programmed actions later When programming heating actions time and set point cooling actions are added automatically at the same time but with the p...

Страница 9: ...n to select x to switch cooling or heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 10 Use the pi and pj buttons to set the correct action time 11 Repeat steps 8 to 10 to program the other actions of the selected day When all actions have been programmed make sure that the display shows the hig...

Страница 10: ...ant to consult 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to consult by means of the pi and pj buttons The selected day is blinking 5 Press the button to confirm the selected day The first programmed action of the selected day appears 6 Use the pi and pj buttons to consult the other progr...

Страница 11: ...g or heating mode 1 Use the button to select the operation mode cooling or heating you want to delete 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to delete by means of the pi and pj buttons The selected day is blinking 5 Press the and ba button simultaneously for 5 seconds to delete the se...

Страница 12: ...der outdoor temperatures i e Lo_A warmer water is required 1 03 Set point at high ambient temperature Hi_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi_A Note that the Hi_Ti value should be lower than Lo_Ti as for warmer outdoor temperatures i e Hi_A less warm water suffices 2 Disinfection function Applies only to install...

Страница 13: ...ture equals or drops below the specified equilibrium temperature When the function is disabled operation of the backup heater is possible at all outdoor temperatures Enabling this function reduces the working time of the backup heater 5 00 Equilibrium temperature status specifies whether the equilibrium temperature function is enabled 1 or disabled 0 5 01 Equilibrium temperature outdoor temperatur...

Страница 14: ...tra degrees are specified by the domestic hot water step length field setting Correct setting prevents the booster heater from repeatedly turning on and off i e chattering to maintain the domestic hot water set point temperature Note the booster heater will turn back on when the domestic hot water temperature drops 2 C fixed value below the booster heater OFF temperature 7 00 Domestic hot water st...

Страница 15: ... water temperature for cooling operation 9 04 Overshoot setting defines how much the water temperature may rise above the setpoint before the compressor stops This function is only applicable in heating mode A Quiet mode This field setting allows to select the desired quiet mode Two quiet modes are available quiet mode A and quiet mode B In quiet mode A priority is given to the unit operating quie...

Страница 16: ...that contact will open and the unit will go in forced off mode 1 When parameter D 01 2 at the moment that the benefit kWh rate signal is sent by the electricity company that contact will close and the unit will go in forced off mode 2 E Unit information readout E 00 Readout of the software version example 23 E 01 Readout of the EEPROM version example 23 E 02 Readout of the unit model identificatio...

Страница 17: ...heating off temperature 25 14 25 1 C 03 Booster heater operation 1 0 1 04 Freeze up protection function 0 active Read only 5 Equilibrium temperature and space heating priority temperature 00 Equilibrium temperature status 1 ON 0 1 01 Equilibrium temperature 0 15 35 1 C 02 Space heating priority status 0 OFF 0 1 03 Space heating priority temperatures 0 15 20 1 C 04 Set point correction for domestic...

Страница 18: ...off heaters 0 0 1 2 3 01 Unit connection to benefit kWh rate power supply 0 OFF 0 1 2 02 Not applicable Do not change the default value 0 E Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Read only 03 Liquid refrigerant temperature Read only C 04 Inlet water temperature Read only C First code Second code Setting name Installer setting...

Страница 19: ...o late or too early Check if the clock and the day of the week are set correctly correct if necessary DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation Your product is marked with this symbol This means that electrical and electronic products shall not be mixed with unsorted h...

Страница 20: ...NOTES NOTES ...

Страница 21: ......

Страница 22: ...4PW51122 1 Copyright Daikin ...

Отзывы: