31

Setting the Vacation Timer

The vacation timer lets you set the date and time of your RETURN from vacation. Until that date/time, the system will remain at 

the VACATION heating and cooling setpoints specified in the configuration menu.
To use the EASY VACATION feature:

Press 

, then press the 

 to scroll to “Vacation” then press 

 again. The thermostat will automatically go into Vacation 

mode with the default return date 1 month later .

To set the vacation timer (and begin vacation setpoint mode): 

1.

 Press 

 to select operating mode. 

 

2.

 Press 

, then press 

 until VACATION appears. 

3.

Press 

 to enter date and time you plan to RETURN from vacation.

4.

 When your finished entering the date/time, press 

.

Schedule Override

The schedule override feature allows the user to override the program schedule for 1 to 5 hours. In addition, if selected, the 

schedule can be overridden only until the next transition period.

To access the Schedule override feature, enter the 

 screen, then use 

 to scroll through the menu options until you reach 

the SCHEDULE OVERRIDE screen. In the default setting, the Vacation & Schedule periods will be flashing in the upper right 

corner of the LCD. In this mode, the Vacation & Schedule will be overridden until the next transition period. To switch to the 1-5 

hour override, use the 

 arrow. This mode allows the user to override the Schedule set points for 1-5 hours.

Alarm Reset

This thermostat is equipped with unit fault reset capabilities when used with the Michrotech III WSHP unit controller.

If the water source heat pump enters a fault mode, the alarm icon will illuminate on the thermostat.  When the condition has 

been corrected, the unit can be reset from the thermostat.

1. Press the  

2. press the CONFIG  

 repeatedly until the alarm reset appears

3. Press the 

 arrow to change the display to Y, then press 

Содержание 910193130

Страница 1: ...ctable Fahrenheit or Celsius Icon Indicator Lights Relay Outputs Minimum Voltage Drop in Thermostat WSHP Alarm Indicator Remote Sensor Compatible Ideally Suited for Residential New Construction Replac...

Страница 2: ...ctrical Rating 24 VAC 18 30 VAC 1 amp maximum per output terminal 5 amp maximum total load Temperature Control Range 45 F to 90 F 7 C to 32 C Accuracy 1 F 0 5 C Anti short Cycle 4 minutes bypass anti...

Страница 3: ...he compressor come on for 4 minutes after it turns off to protect your compressor When the room temperature is greater than the set cool temperature by the differential temperature the cooling device...

Страница 4: ...t is in Setup Mode and is searching for a wireless network Flashing Wi Fi is busy Solid The thermostat is not connected to Wi Fi If the thermostat has successfully connected to Wi Fi previously and no...

Страница 5: ...screws to secure wires CAUTION Be sure exposed portion of wires do not touch other wires 9 Gently tug wire to be sure of proper connection Double check that each wire is connected to the proper termin...

Страница 6: ...nsor W1 1st stage heat W2 2nd stage heat W3 3rd stage heat Y1 1st stage cool Y2 2nd stage cool Y3 3rd stage cool Note 1 Not all terminals are used in every model Note 2 A connection to 24VAC common C...

Страница 7: ...1 Y2 Y1 G C RH RC W2 G2 A PROGRAMMABLE TOUCH SCREEN MICROTECH III CONTROLLER TERMINAL TB2 TERMINAL STRIP G2 910193130 W2 W1 Y2 Y1 G C R A W1 Y2 Y1 G C RH RC W2 G2 A PROGRAMMABLE TOUCH SCREEN MICROTECH...

Страница 8: ...1 Y2 Y1 G C RH RC W2 A PROGRAMMABLE TOUCH SCREEN MICROTECH III CONTROLLER TERMINAL TB2 910193132 Y1 I O EXPANSION MODULE TB1 1 W1 Y2 Y1 G C RH RC W2 A PROGRAMMABLE TOUCH SCREEN MICROTECH III CONTROLLE...

Страница 9: ...9 Wiring Diagrams continued W1 Y2 Y1 G C RH RC W2 A PROGRAMMABLE TOUCH SCREEN MICROTECH III CONTROLLER TERMINAL TB2 910193134 DH I O EXPANSION MODULE TB1 1 W2 W1 Y2 Y1 G C R A...

Страница 10: ...ng 2 Select an appropriate location for mounting the remote sensor 3 Mount the remote sensor using hardware provided 4 Install two strand shielded wire between the S1 terminal on the remote sensor and...

Страница 11: ...ressors Y1 G O Y1 Y2 G O Y1 G B Y1 Y2 G B Heat Pump Two Compressors w High Speed Fan Y1 G2 O Y1 Y2 G2 O Y1 G2 B Y1 Y2 G2 B 910193131 Output Chart 1st Cool 2nd Cool 1st Heat 2nd Heat Water Source Heat...

Страница 12: ...ors Y1 G O Y1 Y2 G O Y1 G B Y1 Y2 G B Y1 Y2 W2 G B 910193134 Output Chart 1st Cool 2nd Cool 1st Heat 2nd Heat Water Source Heat Pump Y1 G Y1 Y2 G W1 W1 W2 Electric Y1 G Y1 Y2 G W1 G W1 W2 G Heat Pump...

Страница 13: ...diagram is the code that will unlock the desired configuration setting The smaller numbers indicated by 93 and 82 in the diagram are codes used to lock and unlock your thermostat to prevent tampering...

Страница 14: ...the previous screen Press the or to change settings within each screen Changes are saved automatically To exit configuration mode press Auto exit occurs after two minutes with no icons touched To chan...

Страница 15: ...the or to set differential value Press to advance to the next screen CONFIG 3 2nd Stage Temperature Differential 1 F to 5 F 0 5 C to 2 5 C Set the number of degrees between when stage 1 turns on and w...

Страница 16: ...is set to Press the or to set Press to advance to the next screen CONFIG 7 Heat Source There are six heat source settings WARNING Incorrect settings can damage system and or cause potentially dangero...

Страница 17: ...ance to the next screen CONFIG HEAT 11 Minimum Cool Setpoint 45 F to 90 F 7 C to 32 C Adjust to control the minimum cool set temperature allowed Press the or to select Press to advance to the next scr...

Страница 18: ...no remote sensor option 1 L must be selected May only be used with remote temperature sensor 1 CONFIG Appears only for non heat pump systems and heat pumps without an outdoor sensor 1 L Only on board...

Страница 19: ...he dehumidifier to turn on Press or to select Press to advance to the next screen CONFIG HUMIDITY RH 19 Humidity Differential 1 to 10 Set the percent difference between the setpoint humidity and when...

Страница 20: ...o select Press to advance to the next screen CONFIG ON SCHEDULE FAN OFF 22 Relay Operation dehumidification only Set the relay function to match your system normally open normally closed Press or to s...

Страница 21: ...connect to the wireless network for the first time If you have previously connected the thermostat to the wireless network but have changed your password or installed a new wireless router you will h...

Страница 22: ...1 Without closing the Dakin App open phone s settings 2 Choose connections 3 Select Wi Fi 4 Select the thermostat s ID from the list of available networks thermostat ID s will begin with I3_ 5 Once co...

Страница 23: ...8 Press to save value and move to hour 9 Press or to select the hour Note As you move past 12 00 the AM PM symbol will change automatically 10 Press to save the value and move to minutes 11 Press or...

Страница 24: ...HEAT HEAT MODE The possible operating modes for the thermostat are OFF HEAT EM HEAT COOL and AUTO Use to select Auto Mode In this mode the thermostat controls either heating or cooling systems automat...

Страница 25: ...reen shows exclusively the current fan setting AUTO ON HOURLY and current fan speed HI LOW The FAN UP and DOWN buttons are enabled ON FAN Hi ON FAN Hi HOURLY FAN Hi AUTO FAN Hi Press icon fan setting...

Страница 26: ...n the FAN screen above ON SCHEDULE FAN COOL MODE PM ON Tue COOL Fan speed set for either mode will apply to all modes For example speed set to HI on AUTO mode will apply to ON and HOURLY mode If detai...

Страница 27: ...screen The icons will not flash in sleep mode Press the button the home screen will flash either the icon or the icon The number of flashes indicates the current stages of cooling or heating ON SCHEDU...

Страница 28: ...s displayed 2 Adjust set temperature so it is 5 degrees below room temperature 3 Cooling should come on within a few seconds 4 Adjust the set temperature 2 degrees above the room temperature and the c...

Страница 29: ...ash Use the or to select the minutes when you want the current period to begin 10 Press to continue 11 The HEAT temperature flashes Use the or to set the desired heat temperature 12 Press to continue...

Страница 30: ...ure if not used VIEW Remote Sensor VIEW View if locked or unlocked Unlocked Locked VIEW Day Month Year View month day and year VIEW View filter status Accumulated fan run time displays VIEW SLEEP Disp...

Страница 31: ...addition if selected the schedule can be overridden only until the next transition period To access the Schedule override feature enter the screen then use to scroll through the menu options until you...

Страница 32: ...The thermostat comes pre programmed with the following schedule TUESDAY 2 WAKE LEAVE RETURN SLEEP HEAT HEAT HEAT HEAT COOL COOL COOL COOL WEDNESDAY 3 WAKE LEAVE RETURN SLEEP HEAT HEAT HEAT HEAT COOL C...

Страница 33: ...o auto is continuous run Room temperature is not correct Calibrate thermostat see Configuration Mode Setting If remote sensor is used check S1 and SC terminal connections LOCK displays when any button...

Страница 34: ...eat or cool mode on the thermostat by the temperature differential Setpoints do not display all of the time Press MENU VIEW six times Problem finding app Apple devices require iOS 7 0 or newer softwar...

Страница 35: ...storage incorrect installation or servicing not performed by the Seller In order to permit the Seller to properly administer the warranty the Buyer shall 1 Notify the Seller promptly of any claim sub...

Страница 36: ...quivalent isotropically radiated power e i r p is not more than that necessary for successful communication Conform ment la r glementation d Industrie Canada le pr sent metteur radio peut fonctionner...

Отзывы: