Setting the Time and Day of the Week

TODAY

MON

5.  Press the 

FAN

 (right) button once to select day of the week (TODAY flashing).

 

Press the 

up

 or 

down

 button to select current day of the week.

 

 

Note:

 At any time, press the 

SYS

 (left) button to return to the previous screen or 

press the 

FAN

 (right) button to advance to the next screen.

Press the 

PROG

 button in for 2 seconds to lock values into memory and return to the 

OFF mode or press the 

FAN

 (right) button once to enter programming.  

4.  Press the 

FAN

 (right) button once to select minutes (minutes flashing).

 

Press the 

up

 or 

down

 button to adjust the minutes.

3.  Time displays (hour flashing).
 

Press the 

up

 or 

down

 button to adjust the hour.

2.  Press and hold the 

PROG

 button (

SYS

 (left) and 

FAN

 (right) buttons pressed 

simultaneously) in for 6 seconds.

1.  Press the 

SYS

 (left) button until you are in the OFF mode.

The time and day of the week must be set for your program schedule to operate correctly.

Testing the Thermostat

Once the thermostat is configured, it should be thoroughly tested.

 

CAUTION!

Do not energize the air conditioning system when the outdoor temperature is below 50 
degrees. It can result in equipment damage or personal injury.

Heat Test

1. Press 

SYS

 (left) button until heat mode is displayed.

2. Adjust the set temperature so it is 5 degrees above the room temperature.
3. Heat should come on within a few seconds.
4. Adjust the set temperature 2 degrees below the room temperature and the heat 

should turn off. There may be a fan delay on your system.

PM

Cool Test

1. Press 

SYS

 (left) button until cool mode is displayed. 

2. Adjust set temperature so it is 5 degrees below room temperature.
3. A/C should come on within a few seconds.
4. Adjust the set temperature 2 degrees above the room temperature and the A/C 

should turn off. There may be a fan delay on your system.

PM

Fan Test

1.  Press 

FAN

 (right) button. Fan displays. Indoor fan turns ON.

2.  Press 

FAN

 (right) button. Indoor fan turns OFF.

PM

OFF

Program Mode

•  In this mode, the program function is on (PROG displays), and the thermostat 

will automatically be controlled by the set program schedule. Program mode can 
function with heat mode, cool mode, or heat & cool mode. The program schedule 
can  be overridden by changing the set temperature (up or down button). After 2 
hours, the program schedule will automatically be resumed. To manually return to 
the program schedule, press the PROG button twice.

PROG

PROG

PROG

Operating Modes

There are five possible operating modes for the 

910121748

. Off, Cool, Heat, and Cool & Heat modes are accessed 

by pressing the 

SYS

 (left) button. Program mode is accessed by pressing the 

SYS

 (left) and 

FAN

 (right) buttons 

simultaneously.

OFF Mode

•  In this mode, the thermostat will not turn on the heating or cooling devices
 

 

Note:

 

The indoor fan can be turned on manually in every operating mode by 
pressing the 

FAN

 (right) button. The word 

FAN 

shows on the display and 

the fan icon   appears when the fan operates.

OFF

Heat Mode

•  In this mode, the thermostat controls the heating system. When the heat outputs, 

the flame icon   apprears on the display.

Cool Mode

•  In this mode, the thermostat controls the cooling system. When the cooling 

outputs, the snowflake icon   apprears on the display.

Cool and Heat Mode (Auto Changeover)

•  In this mode, the thermostat controls the cooling and heating systems, automatically 

changing over from one to the other as needed.

•  The timing display alternates with the set temperature every 10 seconds in the cool 

and heat mode.

Programming

From this screen you have 2 options: 
1.  Press the 

FAN

 (right) button to begin programming all 7 days at one time, or

2.  Press the up button to see the other programming options.

  

Note:

 The days of the week shown on the display will be programmed simultaneously. 

 

The screens are listed below.

Program Overview

The 

910121748

 programmable thermostat has four periods (MORN, DAY, EVE, NITE) that are customizable for 

each day of the week. Each period will have a start time, heat temperature, cool temperature and programmable fan 
option. The 

910121748

 monitors the day and time, while maintaining the specific conditions you have chosen for 

each period in your program.
Setting the program schedule:
1.  Press the 

SYS

 (left) button until you are in 

OFF

 mode.

2.  Press and hold the 

PROG

 button (

SYS

 and 

FAN

 buttons pressed simultaneously) for 6 seconds.

3.  Press the 

FAN

 (right) button 3 times.

4.  SUN thru SAT are blinking.

SUN MON TUE WED THU FRI SAT

PROG

Screen 1

SUN

MON

TUE

WED

THU

FRI

SAT

Screen 2

MON

TUE

WED

THU

FRI

Screen 3

MON

Screen 4

TUE

Screen 5

WED

Screen 6

THU

Screen 7

FRI

Screen 8

SUN

SAT

Screen 9

SAT

Screen 10

SUN

From any of the screens on above, you can press the 

FAN

 (right) button to begin entering your program schedule. 

The days shown on the display will all be programmed simultaneously.

Once the 

FAN

 (right) button is pressed, 

MORN

 blinks.

Use the 

up

 or 

down

 button to select a different period (

MORN

DAY

EVE

NITE

).

Press 

FAN

 (right) button to advance to the next screen. Transition time 

hour

 blinks.

Use the 

up

 or 

down

 button to select a different hour. 

Press 

FAN

 (right) button to advance to the next screen. Transition time 

minutes

 blink.

Use the 

up

 or 

down

 button to select different minutes. 

Press 

FAN

 (right) button to advance to the next screen. 

Heat set temperature

 displays.

Use the 

up

 or 

down

 button to adjust the heat set temperature.

Press 

FAN

 (right) button to advance to the next screen. 

Cool set temperature

 displays.

Use the 

up

 or 

down

 button to adjust the cool set temperature.

Press 

FAN

 (right) button to advance to the next screen. 

Programmable fan

 screen displays.

Use the 

up

 or 

down

 button to select:

Choose: 

Off

 – Programmable fan disabled

 

On

 – Indoor fan on continuously

  

Note:

 Programmable fan operates in Program mode only.

Repeat above steps to program the four periods per day.

When the program schedule is complete, press and hold the 

PROG

 button (

SYS

 and 

FAN

 buttons pressed 

simultaneously) in for 2 seconds to return to the 

OFF

 mode.

Symptom

Remedy

No display

Check for 24 VAC at thermostat; display is blank when 24 VAC is not 
present
Time and day of week must be reset after extended power loss

All thermostat buttons are inoperative

Verify 24 VAC is present; unit locks out when 24 VAC is not present

No response with first button press

First button press activates backlight only

Program schedule activates at the 
wrong time

Check time (AM/PM) set on thermostat (see Setting the Time)

Thermostat turns on and off too 
frequently

Adjust temperature differential (see Configuration Mode Settings 2 & 3)

Thermostat does not follow program

Verify it is operating in program mode (PROG displays); check time 
(AM/PM); check if in 2 hour program override

Fan runs continuously

Press FAN (right) button to turn fan off

Fan turns on occasionally

Program Mode: Check programmable fan setting in program schedule

Status indicator on

WSHP status blink code

Room temperature is not correct

Calibrate thermostat (see Configuration Mode Setting 8) 
If remote sensor is used, check S1 and S2 terminal connections

on display instead of room 
temperature

Check for a bad connection at S1 and S2 terminals, if used 
(see Configuration Mode Setting 9)

Heat or Cool not coming on

Verify wiring is correct, gently pull on each wire to verify there is a good 
connection at terminal block

Alarm light on

Unit in alarm lockout condition

Problem not listed above

Press Reset button once*

* Reset Button Function

: Time and day are reset, configuration and program settings are unchanged.

Troubleshooting

THURSDAY

4

FRIDAY

5

SATURDAY

6

SUNDAY

7

MORN

DAY

EVE

NITE

HEAT

HEAT

HEAT

HEAT

COOL

COOL

COOL

COOL

FAN

FAN

FAN

FAN

MORN

DAY

EVE

NITE

HEAT

HEAT

HEAT

HEAT

COOL

COOL

COOL

COOL

FAN

FAN

FAN

FAN

MORN

DAY

EVE

NITE

HEAT

HEAT

HEAT

HEAT

COOL

COOL

COOL

COOL

FAN

FAN

FAN

FAN

MORN

DAY

EVE

NITE

HEAT

HEAT

HEAT

HEAT

COOL

COOL

COOL

COOL

FAN

FAN

FAN

FAN

MORN

DAY

EVE

NITE

HEAT

HEAT

HEAT

HEAT

COOL

COOL

COOL

COOL

FAN

FAN

FAN

FAN

MORN

DAY

EVE

NITE

HEAT

HEAT

HEAT

HEAT

COOL

COOL

COOL

COOL

FAN

FAN

FAN

FAN

MORN

DAY

EVE

NITE

HEAT

HEAT

HEAT

HEAT

COOL

COOL

COOL

COOL

FAN

FAN

FAN

FAN

Personal Program Schedule

MONDAY

1

TUESDAY

2

WEDNESDAY

3

Factory Preprogramming

MORN

6:00 AM

DAY

8:00 AM

EVE

6:00 PM

NITE

10:00 PM

HEAT

70°F

HEAT

62°F

HEAT

70°F

HEAT

62°F

COOL

78°F

COOL

85°F

COOL

78°F

COOL

82°F

FAN

Off

FAN

Off

FAN

Off

FAN

Off

MONDAY

thru

SUNDAY

The 

910121748

 comes preprogrammed with the following schedule:

Use the following personal program schedule to record your settings:

Daikin Training and Development
Now that you have made an investment in modern, efficient 

Daikin equipment, its care should be a high priority. For 

training information on all 

Daikin HVAC products, please visit us at www.DaikinApplied.com and click on Training, 

or call 540-248-9646 and ask for the Training Department.
 
Warranty
All 

Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product 

Warranty. Consult your local Daikin Representative for warranty details. Refer to Form 933-430285Y. To find your 
local 

Daikin Representative, go to www.DaikinApplied.com.

 
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 

800-37PARTS (800-377-2787). To find your 

local service office, visit

 www.DaikinApplied.com or call 800-432-1342. This document contains the most current 

product information as of this printing. For the most up-to-date product information, please go to  
www.DaikinApplied.com.
 
Products manufactured in an ISO certified facility.

LIAF178-1

10-15-13

Отзывы: