background image

Specifications

Electrical rating:

  •  24 VAC (18-30 VAC) 

 

•  1 amp maximum per terminal 

 

•  3 amp maximum total load

Temperature control range: 

55°F to 90°F (13°C to 32°C)   

Accuracy:

 ± 1°F (± 0.5°C)

System configurations:

 2-stage heat, 2-stage cool

Timing:

  Anti-short Cycle: 4 minutes (bypass anti-short cycle delay by returning to OFF mode for 5 seconds)

 

Backlight Operation: 10 seconds

Terminations:

 A, L, S1, S2, R, C, W1, Y1, W2, Y2, G, O 

Package Contents/Tools Required

Package includes:

 

910121748

 thermostat on base, thermostat cover, wiring labels, screws and wall anchors, 

Installation, Operation and Application Guide

Tools required for installation:

 Drill with 3/16” bit, hammer, screwdriver

Important Safety Information

WARNING!

Always turn off power at the main power supply before installing, cleaning, or removing 
thermostat.

•  This thermostat is for 24 VAC applications only; do not use on voltages over 30 VAC
•  All wiring must conform to local and national electrical and building codes
•  Do not use air conditioning when the outdoor temperature is below 50 degrees; this can damage your A/C system 

and cause personal injuries

•  Use this thermostat only as described in this manual

To Remove Existing Thermostat

ELECTRICAL SHOCK HAZARD

 – Turn off power at the main service panel by removing the fuse 

or switching the appropriate circuit breaker to the OFF position before removing the existing 
thermostat.

1.  Turn off power to the heating and cooling system by removing the fuse or switching the appropriate circuit 

breaker off.

2.  Remove cover of old thermostat. This should expose the wires.
3.  Label the existing wires with the enclosed wire labels before removing wires.
4.  After labeling wires, remove wires from wire terminals.
5.  Remove existing thermostat base from wall.
6.  Refer to the following section for instructions on how to install this thermostat.

To Install Thermostat

ELECTRICAL SHOCK HAZARD

 – Turn off power at the main service panel by removing the fuse 

or switching the appropriate circuit breaker to the OFF position before removing the existing 
thermostat.
IMPORTANT:

 

Thermostat installation must conform to local and national building and electrical codes and 
ordinances.

 

 

Note:

 

Mount the thermostat about five feet above the floor. Do not mount the thermostat on an outside wall, in 
direct sunlight, behind a door, or in an area affected by a vent or duct.

1. Turn off power to the heating and cooling system by removing the fuse or switching the appropriate circuit breaker 

off.

2. To remove cover, pull gently at the seam at the top.
3. Put thermostat base against the wall where you plan to mount it (Be sure wires will feed through the wire opening 

in the base of the thermostat).

4. Mark the placement of the mounting holes.
5. Set thermostat base and cover away from working area.
6. Using a 3/16” drill bit, drill holes in the places you have marked for mounting.
7. Use a hammer to tap supplied anchors in mounting holes.
8. Align thermostat base with mounting holes and feed the control wires through slit in thermal intrusion barrier and 

into wire opening.

9. Use supplied screws to mount thermostat base to wall.
10. Insert stripped, labeled wires in matching wire terminals. 

 

CAUTION!

Be sure exposed portion of wires does not touch other wires.

11.  Gently tug wire to be sure of proper connection. Double check that each wire is connected to the proper 

terminal. 

12. Turn on power to the system at the main service panel.
13. Configure thermostat to match the type of system you have.
14. Replace cover on thermostat by snapping it in place.
15. Test thermostat operation as described in “Testing the Thermostat”.

Parts Diagram

Icon Descriptions

Cooling operation icon

Fan operation icon

Heating operation icon

Room temperature 
offset activated

1

ST

 Cool

2

ND

 Cool

1

ST

 Heat

2

ND

 Heat

Heat/Cool

Y1

YI, Y2

W1

W1, W2

The 

910121748

 thermostat is configurable for all systems. The configuration directly affects the outputs.

Use the output chart to correctly configure and wire the thermostat to your system.

910121748 Output Chart

Configuration Mode

OFF

PM

1.  Verify the 

910121748

 is in the 

OFF

 mode.

 

Press the 

SYS

 (left) button until off mode displays.

2.  Remove the cover of the thermostat by gently pulling near one of the corners at 

the top of the thermostat.

3.  Press the 

CONFIG

 button for 1 second while the 

910121748

 is in 

OFF 

mode.

To exit configuration mode, press the 

CONFIG

 switch for 1 second.

Press the 

up

 or 

down

 button to change settings within each screen.

Down button

Up button

Press the 

right

 button to advance to the next screen.

 

Note:

 

Pressing the 

left

 button will return you to the previous screen.

Left 

button

Right 

button

The configuration mode is used to set the 

910121748

 to match your heating/cooling system. To configure the 

910121748

, perform the following steps:

CONFIG

S1 S2 R

C

W

O/B

G

Y1 W2

W3

Y2

RESET

CONFIG

FP

6. 

Maximum Heat Setpoint

 (55°F to 90°F) (13°C to 32°C) 

 

Adjust to control the maximum heat set temperature allowed.

 

Press the 

up

 or 

down

 button to select.

 

Press the 

right

 button to advance to the next screen.

7. 

Minimum Cool Setpoint

 (55°F to 90°F) (13°C to 32°C) 

 

Adjust to control the minimum cool set temperature allowed.

 

Press the 

up

 or 

down

 button to select.

 

Press the 

right

 button to advance to the next screen.

9. 

Temperature Sensor

 (1-4) 

 

1. Only on-board sensor determines room temperature.

 

2. Only remote sensor determines room temperature.

 

3. Average temperature of on-board and remote sensor.

 

4. Only on-board sensor will be used until NITE period, and then only remote 

sensor is used.

 

 

Note:

 

If there is no remote sensor, option 1 must be selected.

 

Press the 

up

 or 

down

 button to select.

 

Press the 

configuration

 button for two seconds to exit configuration.

8. 

Room Temperature Offset

 (+9°F to -9°F) (+4.5°C to -4.5°C) 

 

Adjust to calibrate displayed room temperature to match actual room temperature. 

 

 

Note:

 

When not set to 0, 

 

will display.

 

Press the 

up

 or 

down

 button to select.

 

Press the 

right

 button to advance to the next screen.

Configuration Mode Settings

The setup screens for Configuration Mode are as follows:

1. 

Temperature Scale 

(F or C)

 

Choose Fahrenheit or Celsius.

  Press the 

up

 or 

down

 button to select.

  Press the 

right

 button to advance to the next screen.

2. 

1

st

 Stage Temperature Differential

 (1°F to 5°F) (0.5°C to 2.5°C)

Set the number of degrees between your “setpoint” temperature and your “turn on” 
temperature.

  Press the 

up

 or 

down

 button to set differential value.

  Press the 

right 

button to advance to the next screen.

4. 

Staged Off Outputs

  

  Select whether the outputs for heating and cooling are staged off independently or 

are satisfied simultaneously.

  1 = outputs staged off independently     
  0 = outputs off simultaneously
  Press the 

up

 or 

down

 button to set.

  Press the 

right 

button to advance to the next screen.

5. 

Minimum Deadband

 (1°F to 9°F) (1°C to 5°C) 

  Set the minimum separation between heat setpoint and cool setpoint in 

Auto 

Changeover

 Mode.

  Press the 

up

 or 

down

 button to set deadband value.

  Press the 

right 

button to advance to the next screen.

3. 

2

nd

 Stage Temperature Differential

 (1°F to 5°F) (0.5°C to 2.5°C) 

  Set the number of degrees between when stage 1 turns on and when stage 2 turns on.
  Press the 

up

 or 

down

 button to set differential value.

  Press the 

right 

button to advance to the next screen.

Wiring Diagrams

Configuration 

switch

Reset switch

Right (fan) button

Down button

Up button

S1 S2 R

C

G

Y1 W2 Y2

RESET

CONFIG

Mode of Operation

The 

910121748

 is a programmable, manual or auto changeover, 2-stage heat, 2-stage cool thermostat. An outdoor 

sensor can be used to monitor the outdoor temperature.

The thermostat activates the heating appliance when the room temperature is below the set heat temperature (by 
the differential temperature). The 

910121748

 will stop outputting when the call for heat has been satisfied. 

When the room temperature is greater than the set cool temperature (by the differential temperature), the cooling 
device is activated. The 

910121748

 will stop outputting when the call for cooling is satisfied. 

The 

910121748

 has five possible operating modes: 

OFF

Heat

Cool

Heat & Cool

, and 

Program

 mode. In off 

mode, the thermostat will not turn on heating or cooling devices. The manual fan can be turned on in all operating 
modes using the fan button. In heat mode, the thermostat controls the heating system. In the cool mode, the 
thermostat controls the cooling system. In heat & cool mode, the thermostat controls both the heating and cooling 
systems. In program mode, the thermostat will automatically be controlled by the set program. Program mode can 
function with heat mode, cool mode, or heat & cool mode. The clock display alternates with the set temperature 
display for heat & cool mode.

The program schedule can be overridden by changing the set temperature (up or down button). This puts the 

910121748

 thermostat into a 2-hour temporary hold. After 2 hours, it will automatically return to the program 

schedule.

The programmable fan feature can be used to recirculate air while in 

Program

 mode. It is activated during the 

program schedule set up.

Pressing the UP and DOWN buttons simultaneously for 2 seconds then releasing them causes the thermostat to 
output from the “O” terminal for 5 seconds. “ Or” will show on the display. This will result in the unit going into a night 
set-back override.

Pressing the UP and DOWN buttons simultaneously for 5 seconds causes the thermostat to output from the “O” 
terminal for 10 seconds. “ rS” will show on the display. This will result in the unit being reset.

Button Functions

UP

 – Used to increase the time, set temperatures and to adjust configuration 

settings. 

DOWN

 – Used to decrease the time, set temperatures and to adjust 

configuration settings.

SYS (left)

 –  Used to change from OFF, HEAT, COOL and AUTO changeover 

modes

FAN (right)

 – Used to turn on and off the indoor fan.

PROG (SYS and FAN)

 – Used to change from program operation to manual operation.

DOWN and SYS

 – Pressed simultaneously to display outdoor remote temperature if remote sensor is 

connected.

UP and DOWN

 –  Used to override night set back or reset the unit.

PROG

FAN

 

(right)

Down

 

button

Up

 

button

SYS

tem 

(left)

Terminals S1 and S2 can be used for an indoor remote sensor. 
The indoor remote sensor is used to read the indoor temperature 
in a different location. This is beneficial when the thermostat is not 
mounted in the ideal location. The remote sensor P/N is 910116773.
1.  Remove cover from remote sensor housing.
2.  Select an appropriate location for mounting the remote sensor.
3.  Mount remote sensor unit using hardware provided.
4.  Install two strand shielded wire between remote sensor and 

thermostat. Shielded wire is recommended.  

Do not

 run remote sensor wire in conduit with other wires.

  • 

Wire 1

 should run between the S1 terminal on the thermostat 

and the S1 terminal on the remote sensor

  • 

Wire 2

 should run between the S2 terminal on the thermostat and the S2 terminal on the remote sensor

  •  Connect the shielding of the wire to the S2 terminal on the thermostat
5.  Configure the thermostat to operate with the remote indoor sensor (see Configuration Mode setting 9).

Remote Sensor Installation (Optional)

 

Note:

  Remote or outdoor sensor reading can be 

displayed by simultaneously pressing the 

Down

 and 

SYS

 buttons.

Remote Sensor:

 

(Contact Daikin for optional remote sensor.)

Terminal Designator Descriptions

 R –  24 VAC hot
 C –  24 VAC common

 W1 –  1st stage heat
 Y1 –  1st stage cool

 W2 –  2nd stage heat
 Y2 –  2nd stage cool 

  G  –  Fan
  A  –  Alarm input

  L  –  Status input
  O  –  Override/reset

L

S1

S2

R

C

W1

Y1

W2

Y2

G

A

O

O

G

Y1

Y2

W1

W2

A

R

C

4

3

2

1

5

O

G

Y1

Y2

W1

W2

A

R

C

ICM 

Thermostat 

Terminal

TB2

TB1

ICM 

Thermostat 

Terminal

WSHP Main Control Board 

Terminals TB1 and TB2

Daikin P/N (910121748)

Installation, Operation & Application Guide

• 7-Day, 5-2-Day or 5-1-1-Day 

Programmable

• Configurable
• 2-Stage Heat/2-Stage Cool Systems
• Large Display With Backlight
• Selectable Fahrenheit or Celsius
• Status Indicator Light
• Relay Outputs  

(minimum voltage drop in thermostat)

• Remote Sensor Compatible

Version B: 10-15-13

2 Heat/2 Cool, 7-Day Programmable, Auto Changeover, Hardwired

Programmable Electronic Thermostat

Отзывы: