background image

IM 955-3 / Page 3 of 6

Pre-Installation

Inspection

Visually inspect the carton for damages. If it is damaged, 

notify the appropriate carrier immediately.
Open the carton and visually inspect the device for obvious 

defects. Return damaged or defective products.

Required Installation Items:

•  Wiring diagram for MicroTech III Unit Controller

Tools

  ■  Appropriate screwdriver(s) for cover, terminals, and 

mounting screws

  ■  Wire stripper/cutter

The following only if wallboard mounting:

  ■  Appropriate drill and drill bits
  ■  Appropriate mounting screws and plastic anchors 

Wiring

3-lead NEC Class II low voltage wiring for temperature sen

-

sor 669529001, 5-lead for sensor 669529101 and 669529201.

Notes:

 1. Do not install the wire cables in the same conduit  

  with power wiring.

 

2. Never apply external voltage of any type to any  

  terminal or damage will result.

 

3. Do not exceed ratings of the device. This is a low  

  voltage device:

 

4. Always use 22-gauge wire and never locate the  

  room temperature sensor more than 250' from the  

 unit:

Wiring must be installed in accordance with the National 

Electrical Code and all local codes and ordinances, which can 

require the use of plenum rated cable or conduit.

Mounting Location

Locate the sensor on a wall where exposure to unrestricted air 

circulation represents the average temperature of the space. A 

common mistake is to mount the sensor too close to the sup

-

ply air diffuser in a room. This causes short cycling of the air 

conditioning unit and large room temperature swings.

Installation

 DANGER

Hazardous Voltage!

This  equipment  presents  hazards  of  electricity. 

 

Failure to read and follow these instructions can re

-

sult in property damage, severe personal injury or 

death.

1.  Turn off power at the main service panel by removing the 

fuse or switching the appropriate circuit breaker to the 

OFF position.

2.  Remove the sensor cover by inserting a screwdriver and 

gently twisting it in the slots on the sides of the wall 

temperature sensor (669529101 & 669529201 only). 

To remove the cover on sensor 669529001, loosen two 

allen-wrench set screws located on the underside of the 

cover.

Note:

  Mount the sensor five feet above the floor. Do not 

mount the sensor on an outside wall, in direct sunlight, 

behind a door, or in an area affected by a vent or duct.

3.  Place the wall sensor mounting base against the wall 

where the sensor where be located. Using the base as a 

template trace the mounting holes onto the wall.

4.  Drill a 3/16" hole at each mounting hole mark.
5.  Insert wall anchors into mounting holes and tap in to the 

wall surface.

6.  Feed wires through the back of the sensor mounting base 

and align sensor mounting holes with wall anchors.

7.  Use supplied screws to secure sensor base to wall.

 CAUTION

  Be certain that exposed portions of wires do not come in contact 

with each other.

8.  Connect stripped, labeled wires to matching terminals on 

the temperature sensor. Refer to either 

Figure 1

 or 

Figure 

2 on page 4 

for wiring details.

9.  Tighten screws on terminal connections. Gently tug wire 

to check for secure connections. Confirm that each wire 

is connected to the proper terminal.

10.  Seal the hole where the wire enters through the wall 

behind the temperature sensor, with non-flammable 

insulation or putty.

11.  Replace cover on wall temperature sensor by snapping it 

in place.

12.  Turn on power to the system at the main service panel
13.  Test wall temperature sensor operation as described in 

 

"Testing" on page 4.

Note:

  Sensor 669529001 has two allen wrench set-screws 

on the underside of the sensor cover to secure it in 

place. Do not overtighten.

Содержание 669529101

Страница 1: ...ce Heat Pump Wall Mounted Room Temperature Sensors Sensor Kit P N 669529101 669529201 669529001 Group WSHP Part Number 910144730 Date October 2013 IM 955 3 Sensor 669529101 Sensor 669529201 Sensor 669529001 2013 Daikin Applied www DaikinAP com 800 432 1342 ...

Страница 2: ...Microtech III Wall Mounted Room Tem perature Sensor For installation and commissioning instructions and general information on a particular unit refer to its model specific installation manual Table 1 MicroTech III Sensor Kits Water Source Heat Pump 10 kW Sensor Kit P N Tenant Override Button SPT Adj Pot Status LED Fan and Mode Switches 669529001 Yes No Yes No 669529101 Yes Yes Yes Yes 55º to 95ºF...

Страница 3: ...njury or death 1 Turn off power at the main service panel by removing the fuse or switching the appropriate circuit breaker to the OFF position 2 Remove the sensor cover by inserting a screwdriver and gently twisting it in the slots on the sides of the wall temperature sensor 669529101 669529201 only To remove the cover on sensor 669529001 loosen two allen wrench set screws located on the undersid...

Страница 4: ...ot affect wiring Figure 1 Temperature Sensor Wiring to MicroTech III Unit Controller Temperature Sensor Terminals MicroTech III Unit Con troller TB1 Terminals Temperature Sensor 669529001 Figure 2 Temperature Sensor Wiring to MicroTech III Unit Controller MicroTech III Unit Con troller TB1 Terminals Temperature Sensor Terminals Testing Temperature Sensors 669529101 669529201 Cool Test 1 Slide Mode...

Страница 5: ...ve 5 minutes Status indicator may come on 3 Using the BMS adjust the set temperature 2 degrees above the room temperature and the A C should turn off There may be a fan delay on your system Table 2 WSHP Unit Status LED Definitions Status LED Unit Status Unit Operation ON OFF 0 5 seconds 0 5 seconds Controller Off or Network Wink operation active Alarm 0 0 seconds Continuous Unit running in Night S...

Страница 6: ...s at www DaikinAP com and click on Training or call 540 248 9646 and ask for the Training Department Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty details Refer to Form 933 430285Y To find your local Daikin Representative go to www DaikinAP com Aftermarket Services...

Отзывы: