background image

4 Installation

Installation manual

6

3(A)MXM+3(A)MXF+4MXM+5MXM

R32 Split series

3P600450-1C – 2020.05

It  is  recommended  to  provide  at  least  150  mm  of  free  space  below
the unit (300 mm for heavy snowfall areas). Additionally, make sure
the unit is positioned at least 100 mm above the maximum expected
level of snow. If necessary, construct a pedestal. See 

"4.1 Mounting

the outdoor unit" 

[

4

 6] for more details.

In  heavy  snowfall  areas  it  is  very  important  to  select  an  installation
site  where  the  snow  will  NOT  affect  the  unit.  If  lateral  snowfall  is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.

3.1.3

Refrigerant piping length and height
difference

INFORMATION

For the Hybrid for Multi application and the DHW generator
for  Multi,  see  the  indoor  unit  installation  manual  for  the
maximum  allowable  refrigerant  piping  length  and  height
difference.

The shorter the refrigerant piping, the better the performance of the
system.

The  piping  length  and  height  differences  must  comply  with  the
following requirements.

Model

Minimum required space

3MXM40, 3MXM52, 3AMXM52,
3MXF52, 3AMXF52

4.7 m

2

3MXM68, 3MXF68

5.5 m

2

4MXM68

6.5 m

2

4MXM80

9.8 m

2

5MXM90

10.4 m

2

Shortest allowable length per room is 3 m.

Outdoor unit

Refrigerant piping
length to each indoor
unit

Refrigerant piping
total length

3MXM40,
3MXM52,
3AMXM52,
3MXM68,
3MXF52,
3AMXF52,
3MXF68

≤25 m

≤50 m

4MXM68

≤60 m

4MXM80

≤70 m

5MXM90

≤75 m

Height difference
outdoor-indoor

Height difference
indoor-indoor

Outdoor unit installed
higher than indoor
unit

≤15 m

≤7.5 m

Outdoor unit installed
lower than at least 1
indoor unit

≤7.5 m

≤15 m

4

Installation

WARNING

Installation  shall  be  done  by  an  installer,  the  choice  of
materials  and  installation  shall  comply  with  the  applicable
legislation. In Europe, EN378 is the applicable standard.

4.1

Mounting the outdoor unit

4.1.1

To provide the installation structure

Use a vibration-proof rubber (field supply) in cases where vibrations
may be transmitted to the building.

The unit may be installed directly on a concrete veranda or another
solid surface as long as it provides proper drainage.

Prepare  4  sets  of  M8  or  M10  anchor  bolts,  nuts  and  washers  (field
supply).

20 mm

(mm)

353

600

240

240

a

a

100 mm above expected level of snow

4.1.2

To install the outdoor unit

4× M8/M10

4.1.3

To provide drainage

NOTICE

In cold areas, do NOT use a drain socket, hose and caps
(large,  small)  with  the  outdoor  unit.  Take  adequate
measures  so  that  the  evacuated  condensate  CANNOT
freeze.

Содержание 4MXM-N9

Страница 1: ...ation manual R32 Split series English Installation manual R32 Split series 3AMXM52N2V1B9 3MXM40N2V1B9 3MXM52N2V1B9 3MXM68N2V1B9 4MXM68N2V1B9 4MXM80N2V1B9 5MXM90N2V1B9 3AMXF52A2V1B9 3MXF52A2V1B9 3MXF68...

Страница 2: ...r Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18...

Страница 3: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Страница 4: ...ioning 13 5 3 Trial operation and testing 13 5 3 1 About wiring error check 13 5 3 2 To perform a test run 14 5 4 Starting up the outdoor unit 14 6 Disposal 14 6 1 To pump down 14 6 2 To start and sto...

Страница 5: ...he room in which the appliances are installed operated and stored must be larger than the minimum floor area This applies to Indoor units without refrigerant leakage sensor in case of indoor units wit...

Страница 6: ...MXM68 3MXF68 5 5 m2 4MXM68 6 5 m2 4MXM80 9 8 m2 5MXM90 10 4 m2 Shortest allowable length per room is 3 m Outdoor unit Refrigerant piping length to each indoor unit Refrigerant piping total length 3MXM...

Страница 7: ...during shipment During installation of the refrigeration system joining of parts with at least one part charged shall be performed taking into account the following requirements inside occupied spaces...

Страница 8: ...9 62 75 NOTICE Use an appropriate wrench to avoid damaging the connection thread by overtightening the flare nut Be careful NOT to overtighten the nut or the smaller pipe may be damaged about 2 3 1 t...

Страница 9: ...egislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GW...

Страница 10: ...ide of the outdoor unit near the gas and liquid stop valves 4 5 Connecting the electrical wiring DANGER RISK OF ELECTROCUTION WARNING Appliance shall be installed in accordance with national wiring re...

Страница 11: ...door units so that the terminal numbers match Make sure to match the symbols for piping and wiring 3 Make sure to connect correct wiring to correct room e B e E e C e D a A e A a C a D a E a B b c d a...

Страница 12: ...r indoor units enter the standby mode Priority during high power operation If the indoor unit on which the priority room function is set operates at high power the other indoor units will run with red...

Страница 13: ...signals of the user interface The specified wires are used for the interconnection cable The fuses circuit breakers or locally installed protection devices are installed according to this document and...

Страница 14: ...ON Test run can be disabled if necessary After the unit is turned OFF it cannot be started again for 3 minutes When the test run is started in the heat mode right after turning the safety breaker on i...

Страница 15: ...s the forced cooling operation switch SW1 to begin forced cooling 9 Press the forced cooling operation switch SW1 to stop forced cooling A 1 2 3 4 5 7 SW1 6 1 4 5 NOTICE Take care that while running f...

Страница 16: ...gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Symbol Meaning Q M Thermo switch Q R Residual current device R Resistor R T Thermistor RC Re...

Страница 17: ...9CuT 15 9CuT 15 9CuT 7 9CuT 9 5CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT MV MV MV A B C 6 4CuT 6 4CuT 6 4CuT 6 4CuT 6 4CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 7 9CuT S1PH d e f k a b c g i d r s t v A v B v C...

Страница 18: ...uT 7 9CuT 7 9CuT MV MV MV A B C 6 4CuT 6 4CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT S1PH SV 9 5CuT 9 5CuT 6 4CuT 12 7CuT 7 9CuT MVD 6 4CuT 15 9CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT...

Страница 19: ...4CuT 6 4CuT 15 9CuT 12 7CuT 15 9CuT 9 5CuT 9 5CuT 9 5CuT d e f k a a b c g i j d r s t v A u A u B u C u D u E v B v C v D v E u d p o o n l m l l w x q h y y 5MXM90 a Heat exchanger h Distributor o A...

Страница 20: ...3P600450 1C 2020 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...

Отзывы: