6
|
Unit installation
Installer reference guide
25
4MWXM-A
R32 Split series
4P678385-1A – 2022.02
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a well-
ventilated room without continuously operating ignition sources (e.g. open flames,
an operating gas appliance, or an operating electric heater). The room size shall be as
specified in the General safety precaution.
6.1.1 Installation site requirements of the outdoor unit
INFORMATION
Also read the following requirements:
▪
"2 General safety precautions"
▪
"7.1.3 Refrigerant piping length and height difference"
Mind the following spacing guidelines:
>100
>50
>350
(mm)
b
a
>100
>50
b
a
>100
b
a
b
a
>350
>350
>50
b
a
a
Air outlet
b
Air inlet
Allow 300 mm of work space below the ceiling surface and 250 mm for piping and
electrical servicing.
>250
>300
(mm)
NOTICE
▪
Do NOT stack the units on each other.
▪
Do NOT hang the unit on a ceiling.
Strong winds (≥18 km/h) blowing against the outdoor unit’s air outlet causes short
circuit (suction of discharge air). This may result in:
▪
deterioration of the operational capacity;
▪
frequent frost acceleration in heating operation;
▪
disruption of operation due to decrease of low pressure or increase of high
pressure;
Содержание 4MWXM52A2V1B
Страница 1: ...Installer reference guide R32 Split series 4MWXM52A2V1B...
Страница 32: ...6 Unit installation Installer reference guide 32 4MWXM A R32 Split series 4P678385 1A 2022 02...
Страница 77: ......
Страница 78: ......
Страница 79: ......
Страница 80: ...4P678385 1A 2022 02 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...