
15
|
Troubleshooting
Installer reference guide
65
2(A)MXM40+50 + 2(A)MXF40+50
R32 Split series
4P600463-2C – 2020.08
15 Troubleshooting
15.1 Overview: Troubleshooting
This chapter describes what you have to do in case of problems.
It contains information about solving problems based on symptoms.
Before troubleshooting
Carry out a thorough visual inspection of the unit and look for obvious defects such
as loose connections or defective wiring.
15.2 Precautions when troubleshooting
WARNING
▪
When carrying out an inspection on the switch box of the unit, ALWAYS make
sure that the unit is disconnected from the mains. Turn off the respective circuit
breaker.
▪
When a safety device was activated, stop the unit and find out why the safety
device was activated before resetting it. NEVER shunt safety devices or change
their values to a value other than the factory default setting. If you are unable to
find the cause of the problem, call your dealer.
DANGER: RISK OF ELECTROCUTION
WARNING
Prevent hazards due to inadvertent resetting of the thermal cut-out: power to this
appliance MUST NOT be supplied through an external switching device, such as a
timer, or connected to a circuit that is regularly turned ON and OFF by the utility.
DANGER: RISK OF BURNING/SCALDING
15.3 Solving problems based on symptoms
15.3.1 Symptom: Indoor units fall, vibrate or make noise
Possible causes
Corrective action
The indoor units are not installed
securely
Install the indoor units securely.
Содержание 2MXM40M4V1B
Страница 75: ......
Страница 76: ...4P600463 2C 2020 08 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...