OM 1039-1 • VAV ACTUATOR ROOM SENSOR

o

peratIon

Operation Modes

Figure 1: Operation Mode Diagram    

Normal Mode

In Normal Mode, the display is updated with temperature, 

humidity and occupied status (all where applicable) on a set 

time cycle . 
The display shows temperature in the desired units (as set by 

the jumper on the PCA). Depending on the model, the humidity 

will be displayed as well . When both of these variables need 

to be displayed (temperature, relative humidity) the display will 

cycle through the required values at a rate of one change every 

three to five seconds.

Occupied Mode

If the BACnet VAV Actuator is currently in Unoccupied Mode 

(

Figure 2

), pressing the override button (

Figure 3

) results in 

the display showing the word OCCUPIED and the request is 

sent to the actuator to override the unoccupied mode . If the 

BACnet VAV Actuator does not get overridden and stays in the 

unoccupied mode, the display on the sensor reverts back to 

the unoccupied symbol as soon as possible .

If the BACnet VAV Actuator is currently in occupied mode, 

pressing the override button flashes the word OCCUPIED and 

does nothing else . This functionality is intended solely to let the 

user know that the button press was recognized .

Figure 2: Unoccupied Icon    

Figure 3: Occupied Icon       

Setpoint Adjustment Mode

The temperature setpoint is adjusted by using the plus and 

minus buttons . The resulting changes in setpoint are shown on 

the display in 1 .0°F or 0 .5°C increments . 

The setpoint adjustment will be displayed, and will stay on the 

screen for three seconds. If, during those three seconds, a 

setpoint button is pressed again, the setpoint will be adjusted 

accordingly and be displayed, and the three-second countdown 

will restart . If there is no user input for more than three 

seconds, the room unit will return to the Normal Mode.

Figure 4: Setpoint Icons    

Passkey Mode

Insert the passkey into the sensor HMI (Human-Machine 

Interface) port to set up all of the user functionality identified in 

Settings. For each parameter, use the following sequence: 

•  Press the occupancy override button to edit the 

parameter

•  Press the plus/minus buttons to scroll through the various 

options available for each parameter to display the 

desired option

•  Press the occupancy override button again to move to the 

next user adjustable parameter

• 

When finished, remove the passkey from the HMI port 

carefully . User setting changes will be saved when the 

passkey is removed

Figure 5: Inserting the Passkey    

 

 

 

 

 

Mode

Passkey

Normal

Laptop

Unoccupied Mode

Occupied Mode

User Settings

View/Change

Set Point

Occupancy

Override

  Occupied Mode        Unoccupied Mode  

 

 

  Occupied Mode        Unoccupied Mode  

 

 

 
 

HMI PORT

PASSKEY

Содержание 2508032

Страница 1: ...ble of Contents Introduction 2 Revision History 2 Reference Documents 2 Limited Warranty 2 Notice 2 General Information 2 Hazard Identification Messages 2 Operation 3 Operation Modes 3 Normal Mode 3 Occupied Mode 3 Setpoint Adjustment Mode 3 Passkey Mode 3 Settings 4 Laptop Pass thru Mode 5 Set up of Displayed Temperature Units 5 ...

Страница 2: ...asskey 2508045 Hazard Identification Messages CAUTION Cautions indicate potentially hazardous situations which can result in personal injury or equipment damage if not avoided WARNING Warnings indicate potentially hazardous situations which can result in property damage severe personal injury or death if not avoided DANGER Dangers indicate a hazardous situation which will result in death or seriou...

Страница 3: ... recognized Figure 2 Unoccupied Icon Figure 3 Occupied Icon Setpoint Adjustment Mode The temperature setpoint is adjusted by using the plus and minus buttons The resulting changes in setpoint are shown on the display in 1 0 F or 0 5 C increments The setpoint adjustment will be displayed and will stay on the screen for three seconds If during those three seconds a setpoint button is pressed again t...

Страница 4: ... determines whether the occupancy status should be displayed The default value is YES if the device offers occupancy override capability NOTE This does not enable disable the Occupancy override button functionality just the display of the occupancy status T Cal allows the user to field calibrate the temperature display and output through a bias adjustment The default value is 0 F Adjustments may b...

Страница 5: ...displayed on the lower right icon section of the display and the upper portion of the display should continue to display temperature and humidity values NOTE This error will appear whenever BACnet VAV Actuator subpoints are not available or the actuator or its subpoints are not responding to commands No Sensor No temperature or humidity sensor detected on the PCA This error will be displayed until...

Страница 6: ...ant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representative go to www DaikinApplied com Aftermarket Services To find your local parts office visit www DaikinApplied com or call 800 37PARTS 800 377 2787 To find your local service office visit www DaikinAppli...

Отзывы: