OMM 1087-1
AGZ 025D through 190D
77
have liquid leave the cylinder and vapor enter
the compressor.
Overcharging of refrigerant will raise the
compressor discharge pressure due to filling of
the condenser tubes with excess refrigerant.
Service Issues
With R-410A, fractionalization, if due to leaks
and recharge has a minimal effect on
performance or operation.
Special tools will be required due to higher
refrigerant pressures with R-410A. Oil-less/hp
recovery units, hp recovery cylinders (DOT
approved w/525# relief), gauge manifold 30”-
250 psi low/0-800 psi high, hoses w/800 psi
working & 4,000 psi burst.
All filter driers and replacement components
must be rated POE oils and for the refrigerant
pressure (R-410A 600psig typical).
R-410A compressor internal relief is 600-650
psid.
Brazed connections only. No StayBrite or
solder connections (solder should never be
used with any refrigerant). K or L type
refrigeration tubing only. Use nitrogen purge.
Higher R-410A pressures and smaller molecule
size make workmanship more critical.
R-410A must be charged from cylinder as a
liquid unless entire cylinder is used. Use a
Refrigerant flow restrictor if charging liquid to
suction or to a system at pressure below a
saturated temperature of 32° F.
EPA recovery and handling requirements for
R-410A are the same as R-22.
Cooling the recovery cylinder will speed
recovery and lessen stress on recovery
equipment.
!
WARNING
Service on this equipment is to be performed by qualified refrigeration personnel
familiar with equipment operation, maintenance, correct servicing procedures, and the
safety hazards inherent in this work. Causes for repeated tripping of equipment
protection controls must be investigated and corrected.
Disconnect all power before doing any service inside the unit.
Servicing this equipment must comply with the requirements set forth by the EPA in
regards to refrigerant reclamation and venting.
Filter-Driers
Replace the filter-drier any time excessive
pressure drop is read across the filter-drier
and/or when bubbles occur in the sight glass
with normal subcooling. The maximum
recommended pressure drops across the filter-
drier are shown in
The filter-drier should also be changed if the
moisture indicating liquid line sight glass
indicates excess moisture in the system.
During the first few months of operation the
filter-drier replacement can be necessary if the
pressure drop across the filter-drier exceeds the
values listed in the paragraph above. Any
residual particles from the condenser tubing,
compressor and miscellaneous components are
swept by the refrigerant into the liquid line and
are caught by the filter-drier.
MAXIMUM RECOMMENDED
PRESSUREDROP ACROSS
FILTER DRIER PSIG (KPA)