IM 1171-3 / Page 9 of 16

Display Descriptions

Fan Status & Speed Indicators:

  The Fan Shape, 

4 Wavy Lines and “Auto”

 word 

indicate Fan and Speed status. 

 

“Fan & No Wavy Lines”

 indicate the fan is Off.

 

Fan & 2 Wavy Lines

 indicate Low.

 

Fan & 3 Wavy Lines

 indicate Medium.

 

Fan & 4 Wavy Lines

 indicate High, 

and the 

word “Auto”

 indicate fan Auto mode.

System Mode “Heat/Cool/Auto/Off/Dhum 
Indicators:

The 

“Heat/Cool/Auto/Off/Dhum”

 Mode Indicators on the 

bottom of the display describe each of the sensor’s modes. 

The mode is changed by pushing the System Mode button on 

the sensor. (Dhum is only used on WSHP units.)

Alarm Word On The Display:

The 

“Alarm”

 word indicator on top illuminates when the 

sensor interprets the “Status” input code from the controller 
as an alarm. See 

Table 4 on page 9

.

E-Save Word On The Display:

The 

“E-Save”

 word indicator on top illuminates when the 

sensor interprets the “Status” input code from the controller 

as Standby Mode (See 

Table 4 on page 9

).

Setpoint Word On The Display:

The 

“Setpoint”

 word on top illuminates when the sensor is 

displaying the setpoint on the numerical display (Tempera-
ture or Humidity). When this “Setpoint” indicator is off, the 
numerical display shows the actual room temperature or 
humidity.

Status Word & Dot On The Display:

The Status “Dot” on the display indicates the unit status or 

alarm condition. It is turned “On” and “Off” by interpreting 
the status input from the controller on terminal 1. See 

Figure 

3 on page 5

Table 4

 shows the alternating conditions and sensor status.

Table 4: WSHP unit status input timing definition

Status Dot "ON" 

(+ 5 vdc) time

Status Dot 

"OFF" (0 vdc) 

Time

WSHP 

Availability

Display 

Indication

0.5 seconds

0.5 seconds

Controller Off (or 

Network

“Wink” operation 

active)

“ALARM” On

0.0 seconds

Continuous

Unit running in 

Night

Setback Override 

Mode or

no power to the 

unit

“OVERRIDE” On

0.5 seconds

5.5 seconds

Unoccupied 

Mode

Hollow Occupied 

Icon

5.5 seconds

0.5 seconds

Standby Mode

“E-SAVE” On

Continuous

0.0 seconds

Occupied Mode

Solid Occupied 

Icon

Table 5: Fan Coil (FCU) unit status input timing definition

Status Dot "ON" 

(+ 5 vdc) time

Status Dot 

"OFF" (0 vdc) 

Time

Fan Coil 

Availability

Display 

Indication

0.3 seconds

0.3 seconds

Alarm Active

“ALARM” On

0.0 seconds

Continuous

Unit running in 

Night

Setback Override 

Mode or

no power to the 

unit

“OVERRIDE” On

0.5 seconds

5.5 seconds

Unoccupied 

Mode

Hollow Occupied 

Icon

5.5 seconds

0.5 seconds

Standby Mode

“E-SAVE” On

Continuous

0.0 seconds

Occupied Mode

Solid Occupied 

Icon

3.0 seconds

3.0 seconds

Calibration 

Mode/Network 

Wink

No Change

Содержание 910121754

Страница 1: ...432 1342 www mcquay com Digitally Adjustable Display Sensor Used With Water Source Heat Pumps WSHP Sensor Part No 910121754 SmartSource Units Models GS GT Enfinity Units with MicroTech III Controls M...

Страница 2: ...ication FCU Only 10 Heat Cool Auto Off 10 Fan Speed Indication FCU Only 10 Auto High Medium Low 10 System Mode Indication WSHP Only 10 Heat Cool Auto Off Dhum 10 Fan Indication WSHP Only 10 Auto On 10...

Страница 3: ...ware jumper and menu change during configuration The sensor has a digital display for Temperature Humidity Occupancy Fan Speed System Mode Alarm Setpoint and Status indica tion Controls include six bu...

Страница 4: ...mp applications is shown in Table 2 Table 2 Water source heat pump application guide Units Product Models Applications Cool ing Heat ing Dehumidification Electric Heat Water side Econo mizer Stages Sm...

Страница 5: ...00 1 125 Termination Daikin McQuay recommends using a twisted shielded pair of at least 22AWG for the power wire connections The shield should be earth grounded only at the power source Larger gauge w...

Страница 6: ...Signal Common Fan Speed Select Fan Coil Version Only Emergency Shut down Unoccupied Dehumidification Sensor Digitally Adjustable Room Temperature Sensor Part No 910121754 Figure 5 Fan Coil MicroTech I...

Страница 7: ...re the cover by backing out the lock down screws using a 1 16 Allen wrench until it is flush with the sides of the cover Note in any wall mount application the wall temperature and the temperature of...

Страница 8: ...1 from the controller is different from the sensor occupied state then the occupied icon will flash the desired occupancy state every 8 seconds indicating to the user a mismatch of the desired occupi...

Страница 9: ...lay shows the actual room temperature or humidity Status Word Dot On The Display The Status Dot on the display indicates the unit status or alarm condition It is turned On and Off by interpreting the...

Страница 10: ...display means the unit will not provide cooling heating dehumidification or fan operation E terminal goes Low Dhum on the display means that only dehumidification will operate There should always be...

Страница 11: ...ur if jumpers are moved while there is power to the unit and sensor Figure 10 J50 Jumper see Figure 3 on page 5 for location Label Description Setting PRG Program Mode Program Mode Jumper installed or...

Страница 12: ...ion No Sensor Fan button control FCU Models Fd Locks fan to the Fan Medium speed position No Sensor Fan button control FCU Models FL Locks fan to the Fan Low speed position No Sensor Fan button contro...

Страница 13: ...Button Enabled Factory default Obd Occupancy Button Disabled P14 Firmware Version XXX X P15 For Units with a BACnet or LonWorks Communications Module Setpoint Calibration Offset Factory set to 0 UP t...

Страница 14: ...ode to DHUM and check terminal DH for voltage Change the RH setpoint above and below the ambient RH to prove the output contact Replace unit if it still doesn t work Occupied Not Working Verify that t...

Страница 15: ...stem status 5VDC max Termination 10 Terminals 16 to 22 AWG Mounting Standard 2 4 J Box or Drywall Field Setup Jumper J50 PRG Program Mode On Program Off Run F C Display Units On C Off F MDL MODEL On W...

Страница 16: ...rsuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin McQuay Representative for warranty details Refer to Form 933 430285Y To find your local...

Отзывы: