Daikin McQuay 910121754 Скачать руководство пользователя страница 11

IM 1171-3 / Page 11 of 16

Front Panel Button Operation

  Up & Down Setpoint Buttons  

  

(Temp Or Humidity):

Press the Setpoint “Up/Down” Buttons once to enter the 

Setpoint Adjustment Mode. View the display to see whether 

the unit is in Temperature or Humidity Setpoint mode. If 
needed, press the “System Mode” Button once to toggle to 
the desired Setpoint. The current setpoint value will display 

for 5 seconds. When the “Up/Down” Buttons are pressed in 

this mode, the temperature or humidity setpoint will change 

in one degree or percent (%) increments. It will only change 

within the temperature setpoint range that was ordered (or the 
setpoint range that was set via the Program Mode).

The humidity setpoint is always between 40% to 90%. After 

5 seconds of no buttons being pushed, the sensor will go into 

the standard display mode.

  System Mode Button (FCU Has 

Heat/Cool/Auto/Off) Or (WSHP Has 
Heat/Cool/Auto/Off/Dhum):

When the “System” Button is pushed, the unit switches be-
tween system modes.

   Fan Mode Button (FCU Has Auto/ 

  High/Medium/Low/Off) (WSHP Has  
   Auto/On):

When the “Fan” Button is pushed, the fan speed changes in 
order from one speed to another. 

Optional Technician Adjustments

Note:  The sensor setup is factory set per your order. Setup 

adjustments are not required

The unit is shipped ready to install per the order and does 
not require any special setup or programming. The following 
Program Menu Changes are available if the installer decides 

to change the factory settings. The Setpoint Up/Down Buttons 

and System Mode Button are used in the Programming Mode 

to make Menu changes and selection.

Set-Up Jumper (J50) Configuration: 

(Factory Set Per Order)

 CAUTION

 

Turn off power to the unit before reconfiguring the jumper set

-

tings.  Damage  to  the  sensor  board  can  occur  if  jumpers  are 

moved while there is power to the unit and sensor.

Figure 10: J50 Jumper (see 

Figure 3 on page 5

 for location)

Label Description Setting

PRG  

Program Mode   Program Mode = Jumper installed  
or Run Mode 

for Program Mode (See Program  

 

Menu below).

 

 

Run Mode = Jumper removed for  

 

Run Mode (Place jumper on one  

 

pin only).

F/C  

ºC Indication  

ºC = Jumper installed for ºC .

 

or ºF Indication  ºF = Jumper removed for ºF 

 

 

Indication (Place jumper on one  

 

pin only).

MDL   Sets the Model  910113679 = Jumper removed for  

FCU or WSHP  FCU (Default for units ordered  

 

as FCU).

 

 

910121754 = Jumper installed for  

 

WSHP (Default for units ordered  

 

as WSHP).

Program Mode Menu Pages: (Display 
Required)

Note:   Both J50 “F/C” and J50 “MDL” jumpers must be 

configured first before entering the program “PRG” 

mode.

Entering Program Mode And Making 
Changes:

1.  Install the J50 “PRG” jumper onto both pins to enter 

Program Mode.

2.  Press the Up/Down Buttons to advance to the desired 

program parameter from P1 through P14 (Parameters 
described below).

3.  Press the System Mode Button to select the specific 

program parameter to change.

4.  Change the parameter value as described in the Mode 

Menus section below. (Usually with the Up/Down Button)

5.  Press the System Mode Button again to set the selected 

parameter.

6.  Press the Up/Down Buttons to proceed to the next 

parameter (as in Step 2 above).

7.  When done making changes, remove the J50 “PRG” 

jumper (and place over one pin). This action will end the 
Programming Mode and store all the values. The sensor is 
now in the Run Mode.

Program Mode Menu Pages:

P1 

Setpoint Mode

 (Factory set to temperature value “S1”. 

J50 ºF/ºC must be set before entering the program 

“PRG” mode).

 

•  S1

 – “UP/DOWN” to select setpoint to absolute 

temperature setpoint value. Actual setpoint value set in 

P4 and P5. 

Example:

 55ºF (13º C) to 95ºF (35º C).

 

•  S2

  – “UP/DOWN” to select setpoint to relative 

temperature setpoint value. Actual setpoint value set 

in P4 and P5. 

Example:

 ±5.0ºF (±2.8ºC) or ±3.0ºF 

(±1.6ºC) for Enfinity systems.

Содержание 910121754

Страница 1: ...432 1342 www mcquay com Digitally Adjustable Display Sensor Used With Water Source Heat Pumps WSHP Sensor Part No 910121754 SmartSource Units Models GS GT Enfinity Units with MicroTech III Controls M...

Страница 2: ...ication FCU Only 10 Heat Cool Auto Off 10 Fan Speed Indication FCU Only 10 Auto High Medium Low 10 System Mode Indication WSHP Only 10 Heat Cool Auto Off Dhum 10 Fan Indication WSHP Only 10 Auto On 10...

Страница 3: ...ware jumper and menu change during configuration The sensor has a digital display for Temperature Humidity Occupancy Fan Speed System Mode Alarm Setpoint and Status indica tion Controls include six bu...

Страница 4: ...mp applications is shown in Table 2 Table 2 Water source heat pump application guide Units Product Models Applications Cool ing Heat ing Dehumidification Electric Heat Water side Econo mizer Stages Sm...

Страница 5: ...00 1 125 Termination Daikin McQuay recommends using a twisted shielded pair of at least 22AWG for the power wire connections The shield should be earth grounded only at the power source Larger gauge w...

Страница 6: ...Signal Common Fan Speed Select Fan Coil Version Only Emergency Shut down Unoccupied Dehumidification Sensor Digitally Adjustable Room Temperature Sensor Part No 910121754 Figure 5 Fan Coil MicroTech I...

Страница 7: ...re the cover by backing out the lock down screws using a 1 16 Allen wrench until it is flush with the sides of the cover Note in any wall mount application the wall temperature and the temperature of...

Страница 8: ...1 from the controller is different from the sensor occupied state then the occupied icon will flash the desired occupancy state every 8 seconds indicating to the user a mismatch of the desired occupi...

Страница 9: ...lay shows the actual room temperature or humidity Status Word Dot On The Display The Status Dot on the display indicates the unit status or alarm condition It is turned On and Off by interpreting the...

Страница 10: ...display means the unit will not provide cooling heating dehumidification or fan operation E terminal goes Low Dhum on the display means that only dehumidification will operate There should always be...

Страница 11: ...ur if jumpers are moved while there is power to the unit and sensor Figure 10 J50 Jumper see Figure 3 on page 5 for location Label Description Setting PRG Program Mode Program Mode Jumper installed or...

Страница 12: ...ion No Sensor Fan button control FCU Models Fd Locks fan to the Fan Medium speed position No Sensor Fan button control FCU Models FL Locks fan to the Fan Low speed position No Sensor Fan button contro...

Страница 13: ...Button Enabled Factory default Obd Occupancy Button Disabled P14 Firmware Version XXX X P15 For Units with a BACnet or LonWorks Communications Module Setpoint Calibration Offset Factory set to 0 UP t...

Страница 14: ...ode to DHUM and check terminal DH for voltage Change the RH setpoint above and below the ambient RH to prove the output contact Replace unit if it still doesn t work Occupied Not Working Verify that t...

Страница 15: ...stem status 5VDC max Termination 10 Terminals 16 to 22 AWG Mounting Standard 2 4 J Box or Drywall Field Setup Jumper J50 PRG Program Mode On Program Off Run F C Display Units On C Off F MDL MODEL On W...

Страница 16: ...rsuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin McQuay Representative for warranty details Refer to Form 933 430285Y To find your local...

Отзывы: