SFLC-211-185
25
Setting mode 2. Function table (1)
Setting
No.
Function
Functional description
Default setting
Important
setting
Page
211
Voltage range
Sets the voltage-measurement range
(primary voltage).
3φ3W 6600V (
15
)
○
44~47
1φ3W 110.0V
1φ2W 3300V (
15
)
212
Digit number of voltage
range
Sets the digit number of voltage range.
3φ3W 4 digits
44~47
1φ3W 4 digits
1φ2W 4 digits
213
Current range
Sets the current-measurement range
(primary current).
3φ3W 100.0A
○
44~47
1φ3W 500.0A
1φ2W 50.00A
214
Current display
intrinsic sensitivity
Sets the full scale of current meter.
3φ3W 100.0A
44~47
1φ3W 500.0A
1φ2W 50.0A
215
Digit number of current
range
Sets the digit number of current range.
3φ3W 4 digits
44~47
1φ3W 4 digits
1φ2W 4 digits
216
Active power polarity
Sets the deflection display of active
power meter.
One-way deflection
44~47
217
Active power range
Sets the full scale of active power
meter.
3φ3W 1200kW (
16
)
44~47
1φ3W 100.0kW
1φ2W 150.0kW (
17
)
218
Digit number of active
power range
Sets the digit number of active power
range.
3φ3W 4 digits
44~47
1φ3W 4 digits
1φ2W 4 digits
219
Reactive power range
Sets the full scale of reactive power
meter.
3φ3W 600.0kvar (
16
)
44~47
1φ3W 50.00kvar
1φ2W 75.00kvar (
17
)
21A
Digit number of reactive
power range
Sets the digit number of reactive
power range.
3φ3W 4 digits
44~47
1φ3W 4 digits
1φ2W 4 digits
21B
Power-factor range
Sets the full scale of power-factor
meter. And, sets the output range of
analog output.
0.5~1~0.5
44~47
21C
Frequency range
Sets the full scale of frequency meter.
And, sets the output range of analog
output.
45.0~65.0Hz
44~47
21D
Digit number of
frequency range
Sets the digit number of frequency
range.
3 digits
44~47
221A
(
14
)
AO1 output factor
Sets the output factor of AO1 (analog
output 1).
3φ3W
A(Y)
○
48
1φ3W
A(R)
1φ2W
A
222A
(
14
)
AO2 output factor
Sets the output factor of AO2 (analog
output 2).
3φ3W
V(RY)
○
48
1φ3W
V(RW)
1φ2W
V
223A
(
14
)
AO3 output factor
Sets the output factor of AO3 (analog
output 3).
W
○
48
224A
(
14
)
Current output intrinsic
sensitivity
Sets the analog output sensitivity (%
of a rated input power value to an output
upper limit) of current.
100.0%
48
Note(
14
) A setting item is not displayed in case there is no corresponding option.
Note(
15
) It is set to
“
220.0V (4-digits)
”
in 220V input.
Note(
16
) It is set to "40.00kW (4-digits)" and "20.00kvar (4-digits)" in 220V input.
Note(
17
) It is set to "10.00kW (4-digits)" and "5.000kvar (4-digits)" in 220V input.