background image

Q-222-031 

 

 

5. Connection 

 

Refer to the terminal name on the front name plate of the main unit, and connect according to the wiring  
diagram below or the wiring diagram name plate on the lower side of the main unit. 
Use the included M4 screws to connect the auxiliary power supply, input voltage, input current, output,  
and ground terminals. 
 
〔Applicable solderless terminal〕 

Solderless terminal for M4 screw 
Outer diameter of terminal, 8.5mm or less 
Tightening torque:1.0 to 1.3 N・m 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

■ Connection diagram 

AUX.SUPPLY

P1

1S

3

1

2

S1

(-)

1L

3S

S2

P2

(+)

OUTPUT

A

B

3L

P3

E

LOAD

 

 

・Grounding is class D grounding (grounding resistance 100Ω or less). 
・If there is a power line that causes noise or a sharp voltage fluctuation, separate the output wiring  

as much as possible.  In addition, use twisted cable or shielded twisted cable. 

・This product will not be damaged even if the output terminal is left open in the current output  

specifications. 

・After completing the wiring work, attach the terminal cover. 

 

Input current terminal 
1S, 1L, 3S, 3L 
 
 
 

Input voltage terminal 
P1, P2, P3 
 
 
 

Ground terminal 

Auxiliary supply terminal  Output terminal 

S1(  ), S2(  )  A(+), B(-) 

+ 

~  

- 

~ 

Содержание FWVTT2-92A-33

Страница 1: ...Q 222 031 INSTRUCTION MANUAL POWER FLOW THREE PHASE REACTIVE POWER TRANSDUCER FWVTT2 92A 33...

Страница 2: ...ase do not install in the place where sunlight hits directly Discoloration and degradation of a name plate and deformation of the case by the surface temperature rise may occur If the average daily te...

Страница 3: ...our company Failure caused by violating various conditions regarding use storage etc specified by the supplier When the faults or defects are caused by a reason not belongs to purchased or delivered p...

Страница 4: ...thod 4 5 Connection 6 6 Handling explanation 7 7 Specification 7 1 Rating 8 7 2 Performance 8 7 3 Electrical strength Mechanical strength 9 7 4 Noise immunity 9 7 5 EMC 10 7 6 Structure and environmen...

Страница 5: ...with a width of 35mm The terminal cover is standard equipment 3 Bundled items Inspection certificate 1 Packed in an envelope Terminal screw in a bag M4 screw 5 piece set 1 M4 screw 7 piece set 1 4 Mo...

Страница 6: ...this product from the IEC DIN rail Please insert a flathead screwdriver in the hole where a slider is square Next a slider is lowered in the direction of an arrow This product can be removed from the...

Страница 7: ...orque 1 0 to 1 3 N m Connection diagram AUX SUPPLY P1 1S 3 1 2 S1 1L 3S S2 P2 OUTPUT A B 3L P3 E LOAD Grounding is class D grounding grounding resistance 100 or less If there is a power line that caus...

Страница 8: ...be burdened Especially for voltage output products do not short circuit the output This product will not be damaged even if the output terminal is left open in the current output specifications Howev...

Страница 9: ...ess 5 3ms DC48V 3 1A or less 5 3ms Note Refer to the specification code for other ratings 7 2 Performance Item Specification Class index 0 5 Response time 1 second or less Ripple 1 p p or less Fluctua...

Страница 10: ...ond of rated voltage 10 times 10 second intervals 40 times 1 second and 20 times 4 seconds and 10 times 16 seconds of rated current 2 times 1 minute intervals 10 times 1 second of rated current 5 time...

Страница 11: ...61000 4 6 Power frequency magnetic field immunity test Frequency 50 60Hz Field strength 30A m Performance standard A During testing Within 20 error After test Within inherent error EN61000 6 2 EN61000...

Страница 12: ...its 10 to 55 5 to 90 RH Non condensing Storage temperature limits 40 to 70 Product warranty period One year period 7 7 Technical standards Item Specification Transducer JIS C 1111 2019 IEC 60688 2012...

Страница 13: ...g term use please adjust in the next way Remove the terminal cover and VR cap before adjustment and attach the VR cap and terminal cover after adjustment 1 For the output load connect an actual load w...

Страница 14: ...D 400 to 0 to LAG 400var Z Other Z Other Rated current Output Output load range Auxiliary supply 1 AC1A 2 Power transmission DC0 to 0 5 to 1V 200 or more AC80 to 264V Z Other Power receiving DC0 to 0...

Страница 15: ...t Output load range Auxiliary supply 2 AC5A 2 Power transmission DC0 to 0 5 to 1V 200 or more AC80 to 264V Z Other Power receiving DC0 to 0 5 to 1V F DC80 to 264V 3 Power transmission DC0 to 2 5 to 5V...

Страница 16: ...oad range Auxiliary supply 1 AC1A 2 Power transmission DC0 to 0 25 to 0 5V 200 or more AC80 to 264V Z Other Power receiving DC0 5 to 0 75 to 1V F DC80 to 264V 3 Power transmission DC0 to 1 25 to 2 5V...

Страница 17: ...ge Auxiliary supply 2 AC5A 2 Power transmission DC0 to 0 25 to 0 5V 200 or more AC80 to 264V Z Other Power receiving DC0 5 to 0 75 to 1V F DC80 to 264V 3 Power transmission DC0 to 1 25 to 2 5V 600 or...

Страница 18: ...Hitotsuya 1 chome Adachi ku Tokyo 121 8639 JAPAN TEL 81 3 3885 2411 FAX 81 3 3858 3966 Kyoto Office 1 19 Ichinobe Nishikawahara Jyoyou shi Kyoto 610 0114 JAPAN TEL 81 774 55 1391 FAX 81 774 54 1353 R...

Отзывы: