5. Connection 

 

Refer to the terminal name on the front name plate of the main unit, and connect according to the wiring  
diagram below or the wiring diagram name plate on the lower side of the main unit. 
Use the included M4 screws to connect the auxiliary power supply, input voltage, input current, output,  
and ground terminals. 
 
〔Applicable solderless terminal〕 

Solderless terminal for M4 screw 
Outer diameter of terminal, 8.5mm or less 
Tightening torque:1.0 to 1.3 N・m 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

■ Connection diagram 

 Standard:2-phase (S-phase) current measurement   

 1-phase (R-phase) current measurement 

 
 
 
 
 
 
 
 
 
 
 
 

 

 3-phase (T-phase) current measurement 

 
 
 
 
 
 

・By changing the wiring, 1-phase (R-phase) current 

and 3-phase (T-phase) current can be measured. 

・Grounding is class D grounding (grounding  

resistance 100Ω or less). 

・If there is a power line that causes noise or a 

sharp voltage fluctuation, separate the output 
wiring as much as possible.  In addition, use 
twisted cable or shielded twisted cable. 

・This product will not be damaged even if the output terminal is left open in the current output  

specifications. 

・After completing the wiring work, attach the terminal cover. 

 

Input current terminal 
2S, 2L 
 
Input voltage terminal 
P1, P2, P3 
 
 
 
Ground terminal 

+ 

~ 

- 

~ 

Auxiliary supply terminal  Output terminal 

S1(  ), S2(  )  A(+), B(-) 

Содержание FAETT2-92A-33

Страница 1: ...Q 222 030 INSTRUCTION MANUAL POWER FLOW CURRENT TRANSDUCER FAETT2 92A 33...

Страница 2: ...ase do not install in the place where sunlight hits directly Discoloration and degradation of a name plate and deformation of the case by the surface temperature rise may occur If the average daily te...

Страница 3: ...our company Failure caused by violating various conditions regarding use storage etc specified by the supplier When the faults or defects are caused by a reason not belongs to purchased or delivered p...

Страница 4: ...thod 4 5 Connection 6 6 Handling explanation 7 7 Specification 7 1 Rating 8 7 2 Performance 8 7 3 Electrical strength Mechanical strength 9 7 4 Noise immunity 9 7 5 EMC 10 7 6 Structure and environmen...

Страница 5: ...ipment 3 Bundled items Inspection certificate 1 Packed in an envelope Terminal screw in a bag M4 screw 10 piece set 1 4 Mounting method Please install indoors in a place with low mechanical vibration...

Страница 6: ...this product from the IEC DIN rail Please insert a flathead screwdriver in the hole where a slider is square Next a slider is lowered in the direction of an arrow This product can be removed from the...

Страница 7: ...N m Connection diagram Standard 2 phase S phase current measurement 1 phase R phase current measurement 3 phase T phase current measurement By changing the wiring 1 phase R phase current and 3 phase...

Страница 8: ...t will be burdened Especially for voltage output products do not short circuit the output This product will not be damaged even if the output terminal is left open in the current output specifications...

Страница 9: ...1 5A or less 5 3ms DC48V 3 1A or less 5 3ms Note Refer to the specification code for other ratings 7 2 Performance Item Specification Class index 0 5 Response time 1 second or less Ripple 1 p p or les...

Страница 10: ...ond of rated voltage 10 times 10 second intervals 40 times 1 second and 20 times 4 seconds and 10 times 16 seconds of rated current 2 times 1 minute intervals 10 times 1 second of rated current 5 time...

Страница 11: ...61000 4 6 Power frequency magnetic field immunity test Frequency 50 60Hz Field strength 30A m Performance standard A During testing Within 20 error After test Within inherent error EN61000 6 2 EN61000...

Страница 12: ...its 10 to 55 5 to 90 RH Non condensing Storage temperature limits 40 to 70 Product warranty period One year period 7 7 Technical standards Item Specification Transducer JIS C 1111 2019 IEC 60688 2012...

Страница 13: ...ent and attach the VR cap and terminal cover after adjustment 1 For the output load connect an actual load within the output load range indicated on the name plate or a simulated load with the same re...

Страница 14: ...or more Power receiving DC3 to 5V 6 Power transmission DC 5 to 0V 600 or more Power receiving DC0 to 5V 7 Power transmission DC 10 to 0V 2k or more Power receiving DC0 to 10V A Power transmission DC0...

Отзывы: