7. Installation details
7.1 Wrench torque sheet for installation
Outside diameter
Torque
mm inch Kgf·m
Ф
6.35 1/4 1.8
Ф
9.52 3/8 4.2
Ф
12.7 1/2 5.5
7.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Grade
Unit 9K
12K
mm
2
1.0
1.5
7.3 Pipe length and the elevation
Capacity
Btu/h
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Elevation
A (m)
Additional
refrigerant
(g/m)
G
as
Liquid
9k~12K
3/8’’ (
Ф
9.52) 1/4’’
(
Ф
6.35)
5 8 20
30
1/2’’ (
Ф
12.7) 1/4’’
(
Ф
6.35)
5 8 20
30
Caution:
Capacity is base on standard length and maximum allowance length is base of reliability.
Oil trap should be installed per 5-7 meters.
7.4 Air purging of the piping and indoor unit
Required tools:
Hexagonal wrench; adjustable wrench; torque wrenches, wrench to hold the joints and gas leak detector.
Note:
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration piping, it will affect the
Содержание DSB-F1216LH-DV
Страница 3: ...9 5 Refrigerant cycle diagram ...
Страница 4: ...10 6 Wiring diagram 6 1 Indoor Unit DSB F1216LH DV ...
Страница 5: ...11 6 2 Outdoor Unit DSB F1216LH DV ...
Страница 14: ...DSB F1216LH DV 220 240V 50Hz 1Phase Exploded View Parts for Model ...
Страница 17: ...Exploded View Parts for Model DSB 1216LH DV 220 240V 50Hz 1Phase ...