16
Dehumidification Mode
Air Discharge Direction(only remocon operation)
The air discharge direction procedure is below.
Fixed Up/Down
Fixed
Up/Down
Fixed Left/Right
Auto Mode I
(1) When the room temperature is higher than 28 ºC (Cooling Mode)
!
Compressor and lndoor Fan
@
The fan will automatically operate as following Figure
-1
0
1
°
C
OFF
ON
(Room temperature-
Desired temperature)
H
M
L
0
+1
+2
+3
°
C
(Room temerature-
Desired temperature)
!
Desired temperature < Room temperature
Outdoor Fan, Compressor : ON
Indoor Fan : Low speed
@
Desired temperature
¡ˆ
Room temperature
Compressor : 3 min/ON, 5 min/OFF
Indoor Fan : 3 min 30 second/ON, 4 min 30 second/OFF
Fan Speed : Ultra low speed
#
Room temperature
¡´
18°C
Compressor : OFF
Indoor Fan : 1 min/ON, 7 min/OFF