19
(1) When the remote controller is lost, damaged or the battery is discharged, the Emergency operation can be
used to run the unit.
(2) The setting conditions of Emergency operation are as follows.
• Operation mode: AUTO
• Preset temperature: 26°C
• Fan speed: LOW
¡
You cannot operate with remote controller.
Emergency Operation
Frost Prevention of Indoor Unit
When the unit operates at low ambient temperature, frost may appear on the Evaporator. When the indoor coil
temperature is lower than 0°C at the end of 10 minutes of continuous compressor operation from the start, the
microcomputer of the unit stops the compressor to protect the unit from the frost. The control procedure for
indoor coil freeze protection.
1) The compressor and outdoor fan turn off.
2) Indoor fan operates according to user set speed.
3) The normal operation returns when the indoor coil temperature is higher than 7°C or equal to 7°C.
0
°
C
7
°
C
Compressor and
Outdoor Fan
OFF
OFF
ON
Set Speed
Indoor Fan
(Indoor coil temperature)
3 min. Time Delay of Compressor
In normal operation, there is a time delay of three minutes between turn off and turning back on including initial
power up.
Содержание DSB-070L
Страница 37: ...PCBDRIVINGDESCRIPTION ...
Страница 53: ...49 5 U9 KIA7042P RESET IC KIA70 42P OUTLINE INPUT GROUND OUTPUT VCC 1 3 2 OUT GND ...
Страница 58: ...54 3 EXPLODED DIAGRAM Indoor Unit DSB 070L DSB 091L ...
Страница 60: ...56 DSB 121L ...
Страница 63: ...59 4 EXPLODED DIAGRAM Outdoor Unit DSB 070L DSB 091L DSB 121L After ...
Страница 66: ...62 DSB 121L Before ...
Страница 69: ...65 5 CONTROL BOX ASSEMBLY 4 3 9 8 5 6 1 0 7 2 DSB 070L DSB 091L ...
Страница 71: ...67 6 5 4 3 1 2 7 8 H1 H3 H2 S H3 DSB 121L ...