Installation Requirement
s
Electrical Requirements
English
1
9
Follow these directions to reduce risk of property damage, personal injury, or death.
WARNING
The owner shall ensure that the electrical service meets requirements and that the electrical outlet
is installed by a licensed electrician.
All Ranges
•
Do not use an extension cord or adapter plug with this range.
•
This range must be plugged in to a properly grounded outlet. (Check with a qualified electrician
if you doubt that the outlet is properly grounded.)
•
Do not alter the power plug. Have a proper outlet installed by a qualified electrician.
•
All wiring/grounding must comply with local codes or, in their absence, with the National
Electrical Code, ANSI/NFPA No. 70 – Latest Revision (US), or the Canadian Electrical Code CSA
C22.1 – Latest Revisions and local codes.
•
The wiring diagram is on the back of the range.
•
A dedicated circuit breaker is recommended.
•
Use this chart to identify the minimum recommended dedicated circuit protection.
KW Rating (240 V)
Recommended Circuit Size (Dedicated)
7.3 KW - 9.6 KW
40 Amp
9.7 KW - 12.0 KW
50 Amp