Planning the Installation

Preparing for Installation

Duct Work Equivalent Lengths

eQuivAlent lengths 

piece

subtract

piece

subtract

8” 90° elbow

7 feet

10” 90° elbow

5 feet

8” 45° elbow

3 feet

10” 45° elbow

2 feet

3¼” X 10”

to round 90° 

transition

25 feet

3¼” X 10” to

8”/10” round 

transition

4 feet

Roof cap

*

Wall cap with 

damper

*

* The equivalent lengths of roof and wall caps vary with 

model and configuration. For equivalent length, contact the 

manufacturer or a qualified HVAC specialist.

Duct Work Design Tips

Wherever possible, reduce the number of transitions 

• 

and turns to as few sharp angles as possible. Two 

staggered 45° angles are better than one 90°.

Keep turns as far away from the hood exhaust as pos-

• 

sible, and as much space between bends as possible.
For best performance, use round duct instead of rect-

• 

angular, especially when elbows are required.
If multiple elbows are used, try to keep a minimum of 

• 

24” straight duct between them.
Avoid “S” or “back to back” use of adjacent elbows.

• 

In regions where the weather gets extremely cold, use 

• 

thermal breaks, such as a short section of non-metallic 

duct, to avoid indoor heat loss. Locate the break as 

close as possible to the outside pass through point.
Do not use flexible metal duct.

• 

Do not

• 

 use duct work that is smaller in cross-sectional 

area than the recommended types above.

Verify the Package Contents

Unpack the parts box and verify that all parts have been 

included according to the parts list on page 5. If any item 

is missing or damaged, please contact the dealer immedi-

ately. Do not install a damaged or incomplete appliance.
Make sure you have everything necessary for proper instal-

lation before proceeding.

Mounting Location Preparation

 wArning

The electrical service to the range hood should be 

• 

installed only by a licensed electrician.
Observe all governing codes and ordinances during 

• 

site preparation and installation. Contact your local 

building department for further information.
Failure to properly anchor the hood to the wall may 

• 

result in personal injury due to the unit falling off the 

wall.
To avoid an electric shock hazard and property dam-

• 

age, locate electric wires and water pipes and avoid 

drilling or cutting in the vicinity.
Use the temporary mounting brackets only to hold 

• 

the hood in place until permanent anchoring is 

installed.

Temporary mounting brackets, and the 

• 

screws and anchors to hold them in place 

during installation are provided with the 

hood. Two anchors and screws are used 

per bracket.
Determine the number, size and type of 

• 

anchors required to attach the hood permanently to the 

wall and/or the cabinets based on the type of installa-

tion and the weight chart on page 3.
Make sure the mounting surface is properly reinforced 

• 

to handle the full weight 

of the hood. If mounting 

the unit to a drywall or 

plastered surface, install 

a reinforced mounting 

block between the studs 

behind all hood mounting 

locations. You may attach 

screws directly to the 

studs and cabinets if they 

line up with the mounting 

holes in the back and top 

of the hood. If mount-

ing the hood to brick or 

masonry, select anchors 

capable of holding the full 

weight of the hood.

Содержание Epicure EH3612

Страница 1: ...e with models EH30 EH36 EH42 EH48 EH54 MH30 MH36 and MH48 Part No 102139 Rev J Approved for use with all dacor ranges and cooktops Tested in accordance with the latest edition of ANSI UL 507 standard...

Страница 2: ...lems read these installation instructions completely and care fully before you begin the installation process Leave these installation instructions with the customer Customer Keep these installation i...

Страница 3: ...amage personal injury or death warning WARNING TO REDUCE THE RISK OF FIRE ELECTRIC SHOCK OR INJURY TO PERSONS OBSERVE THE FOLLOWING Use this unit only in the manner intended by the manufacturer If you...

Страница 4: ...ead the use and care manual completely before using the appliance Clean the appliance only as instructed in the use and care manual Use only the cleaners specified Do not tamper with the controls Neve...

Страница 5: ...Model Number EH48 MH48 EH54 EH42 EH30 MH30 EH36 MH36 Lights 3 2 2 Filters 4 3 2 Exhaust Outputs 2 1 1 Fan Rating 1200 CFM 600 CFM 600 CFM Product Specifications Weight Specifications Model Weight EH30...

Страница 6: ...Dimensions Dual exhaust models Standard 8 duct connection Single exhaust models Standard 8 duct connection Front of hood 1 3 8 cm 3 7 6 cm 4 10 2 cm 9 7 8 25 1 cm 6 1 8 15 6 cm 19 50 2 cm Electrical a...

Страница 7: ...612 35 7 8 91 1 cm EH4212 41 7 8 106 4 cm EH4812 47 7 8 121 6 cm MH3012 29 7 8 75 9 cm 25 1 2 64 8 cm MH3612 35 7 8 91 1 cm MH4812 47 7 8 121 6 cm EH3018 29 7 8 75 9 cm 26 7 8 68 3 cm 18 45 7 cm 6 1 8...

Страница 8: ...ons are met or exceeded Dimensions shown provide minimum clearances unless otherwise noted All contact surfaces between the hood and any cabi nets or walls must be solid and at right angles Install th...

Страница 9: ...damper at the duct outlet may also be required Make sure duct work does not interfere with floor joists or wall studs On dual exhaust models the two 8 exhausts may be merged into one 10 duct using Dac...

Страница 10: ...age 5 If any item is missing or damaged please contact the dealer immedi ately Do not install a damaged or incomplete appliance Make sure you have everything necessary for proper instal lation before...

Страница 11: ...o raise the hood into place The owner is responsible to make sure the hood is properly installed Start by removing the filters from the bottom of the 1 hood Put them in a safe location so that they wi...

Страница 12: ...he panel on the right side inside the hood Also cut the two 2 cable ties that hold the wiring harness to the brace inside the hood on the right side See below Remove and save the nut that holds the wi...

Страница 13: ...the blower motor assembly into 13 the hole inside the back of the hood The connector on the motor must be toward the bottom of the hood Attach it using four 4 nuts Route the wiring harness as shown S...

Страница 14: ...ove the filters from the under side of the hood 5 Locate the wiring harness Cut the cable tie that takes 6 up the slack in the cable It is located behind the panel on the right side inside the hood Al...

Страница 15: ...8 MH3618 EH4218 Models that are 18 inches high equipped with a single blower Place the hood assembly on a large flat surface 1 Remove and save the four 4 screws and the duct col 2 lar from the top of...

Страница 16: ...ow Attach the wiring harness to the brace inside the hood 12 on the right side using two 2 supplied cable ties Use a cable tie to take up any remaining slack that may 13 exist in the wiring harness St...

Страница 17: ...in the cable It is located behind the panel on the right side inside the hood Also cut the two 2 cable ties that hold the wiring harness to the brace inside the hood on the right side Remove and save...

Страница 18: ...with duct tape Route the wiring harness as shown Secure the har 11 ness to the motor assemblies using the cable clamps supplied with the hood in the positions shown below Attach the wiring harness to...

Страница 19: ...raw the horizontal center line for the temporary 1 mounting brackets on the wall The center line for the brackets is 2 1 8 54 cm below where the top of the hood will be located The horizontal line mar...

Страница 20: ...the outside of the 1 hood Remove the filter s to reduce weight and avoid dam 2 age Lift the hood up on both sides and slip the mounting 3 slots over the tabs on the mounting brackets Lift the hood int...

Страница 21: ...CSA approved NEMA strain relief To house circuit breaker panel or fuse box To range hood Junction box Wire nut 3 places Final Electrical Installation warning To avoid electric shock or fire hazard pr...

Страница 22: ...nsert it into one of the light fixtures 2 Screw it into place and remove the suction cup 3 Repeat for the remaining light fixtures 4 2 3 1 Insulated Pipe Jumper if necessary GREEN GREEN WHITE WHITE BL...

Страница 23: ...yourself If you need service be sure to have the model and serial numbers available when you call See the inside cover for location Do not attempt to repair the appliance yourself Dacor is not respon...

Страница 24: ...HOOD LIGHTS 75W 120V EACH HOOD POWER AND CONTROL BOARD CONNECT TO 120V 60HZ 15A SINGLE PHASE POWER SUPPLY CHASSIS GROUND POWER SWITCH WIRE COLOR CODE W WHITE B BLUE Y YELLOW O ORANGE R RED BL BLUE BR...

Страница 25: ...115V HOOD LIGHT 75W 120V HOOD LIGHT 75W 120V HOOD POWER AND CONTROL BOARD CONNECT TO 120V 60HZ 15A SINGLE PHASE POWER SUPPLY CHASSIS GROUND POWER SWITCH WIRE COLOR CODE W WHITE B BLUE Y YELLOW O ORANG...

Страница 26: ...24 Notes...

Страница 27: ......

Страница 28: ...Dacor 600 Anton Blvd Suite 1000 Costa Mesa CA 92626 Phone 800 793 0093 Fax 626 403 3130 www Dacor com...

Страница 29: ...er For use with models EHR30 EHR36 EHR42 EHR48 EHR54 Part No 103781 Rev E Approved for use with all dacor ranges and cooktops Tested in accordance with the latest edition of ANSI UL 507 standard for e...

Страница 30: ...completely and care fully before you begin the installation process Leave these installation instructions with the customer Customer Keep these installation instructions for future reference and the l...

Страница 31: ...amage personal injury or death warning WARNING TO REDUCE THE RISK OF FIRE ELECTRIC SHOCK OR INJURY TO PERSONS OBSERVE THE FOLLOWING Use this unit only in the manner intended by the manufacturer If you...

Страница 32: ...ning device such as a tag to the electrical panel Read the use and care manual completely before using the appliance Clean the appliance only as instructed in the use and care manual Use only the clea...

Страница 33: ...ac 75 W halogen Model Specific Model Number EHR48 EHR54 EHR42 EHR30 EHR36 Lights 3 2 2 Filters 4 3 2 Exhaust Outputs 2 1 1 Product Specifications Weight Specifications Model Weight EHR3012 39 lbs 18 k...

Страница 34: ...mensions Dual exhaust models Standard 8 duct connection Single exhaust models Standard 8 duct connection Front of hood 1 3 8 cm 3 7 6 cm 4 10 2 cm 9 7 8 25 1 cm 6 1 8 15 6 cm 19 50 2 cm Electrical acc...

Страница 35: ...cm EHR4818 47 7 8 121 6 cm EHR5418 53 7 8 136 8 cm See diagram on facing page A Parts List Hood assembly with filters size and style varies with model 2 temporary mounting brackets Temporary mounting...

Страница 36: ...ceeded Dimensions shown provide minimum clearances unless otherwise noted All contact surfaces between the hood and any cabi nets or walls must be solid and at right angles Install the range hood and...

Страница 37: ...duct work and connecting it to the hood on one end and the remote blower on the other There are 7 8 access holes in the top and back of the hood for connecting the conduit The customer must supply co...

Страница 38: ...missing or damaged please contact the dealer immedi ately Do not install a damaged or incomplete appliance Make sure you have everything necessary for proper instal lation before proceeding Mounting L...

Страница 39: ...alfway between the cabinets at the installation location or the same as the center line of the cooktop or range The line will be used to line up the mounting brackets during installa tion Locate the c...

Страница 40: ...Remove the duct collar s 4 Remove and save the cover plate screws and the 5 cover plate s on the back of the hood Using the existing screws attach the cover plate 6 removed in step 5 to the top of the...

Страница 41: ...g sheet metal screws not included Seal the base of of the transition with duct tape 2 1 8 Bracket location Bracket location Hood location F F Reinforced drywall Top mounting shown Mounting Bracket Ins...

Страница 42: ...om the hood and working 2 toward the remote blower Observe the specifications on page 7 and 8 Fasten all joints with sheet metal screws and seal with 3 duct tape or certified silver tape Final Electri...

Страница 43: ...om the junction box as shown GREEN GREEN WHITE WHITE BLACK BLACK 3 Wire Connection to Junction Box UL CSA approved NEMA strain relief To house circuit breaker panel or fuse box To range hood Junction...

Страница 44: ...ssure continuity to ground See above UL CSA approved NEMA strain relief Fasten clamp tightly on pipe Separate No 10 minimum copper ground wire To house circuit breaker panel or fuse box To range hood...

Страница 45: ...37 3226 Do not attempt to repair the appliance yourself If you need service be sure to have the model and serial numbers available when you call See the inside cover for location Do not attempt to rep...

Страница 46: ...N G GREEN V VIOLET W Y W Y B B B B W W R R R BL BL G G G G R W W W W W W W W W W R Y B W W 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 REMOTE FAN BOARD P1 P2 P3 P4 MICROPROCESSOR PROGRAMMING HEADER P3 2...

Страница 47: ...WN G GREEN V VIOLET W Y W Y R W Y R W W W W W W W W W W R Y B W W 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 REMOTE FAN BOARD P1 P2 P3 P4 MICROPROCESSOR PROGRAMMING HEADER P3 2 4 6 8 10 1 3 5 7 9 CONTR...

Страница 48: ...Dacor 600 Anton Blvd Suite 1000 Costa Mesa CA 92626 Phone 800 793 0093 Fax 626 403 3130 www Dacor com...

Отзывы: