background image

                                                  

ENGLISH

                                    

 

 

23 

 

11. TROUBLESHOOTING 

 

Error conditions 

FAULTS 

CHECKS 

(possible causes) 

REMEDIES 

1. 

The pumps gives no water. 

A.  Water  level  in  the  well  lower  than 

pump suction nozzle. 

B.  Blocked valve. 

 

C.  Leaks in the delivery pipe. 
D.  Voltage  lower  than  the  rated  value 

and absorption higher than normal. 
 

E.  Absorbed  current  lower  than  normal 

due to air in the pump. 
 

F.  Clogged grid because of suspended 

solids. 

G.  Unexpected fiction losses 

A.  Increase the pump depth. 

 

B.  Kick  the  pipe  line  with  a  hammer 

trying to unblock the valve. 

C.  Check delivery pipe by the flanges. 
D.  Increase voltage. 

Change  the  supply  cable  with  a 
larger one. 

E.  Start and stop the pump at intervals 

of about a minute. 
 

F.  Clean the pump. 

 

G.  Check  calculations  and  use  larger 

pipes if necessary. 

2. 

The pump is not starting but 
fuses  don’t  blow  up  and 
starter relays do not trip. 

A.  No voltage in the line. 

 
 

B.  The circuits is cut off by the cable on 

in motor windin. 
 
 
 
 

C.  Open circuit in the starter. 

 

A.  Check  voltage  ratings  on  main  and 

on starter terminals. 

B.  Remove  starter  fuses  and  connect 

one Ohmmeter conductor to delivery 
pipe;  Check  then  motor  cables 
terminals  one  by  one  with  the  other 
conductor.  The  reading  of  each 
terminal  shloud  be  at  least  10 
Megahoms. 

C.  Check  circuit  integry  referring  to 

electric diagrams. 

3. 

The starter trips or the fuses 
blow-out  when  the  pump  is 
running. 

A.  Too low voltage. 
B.  Overload  due  to  sand  clogging; 

bearings tend to saize. 

C.  Single  phase:  a  voltage  1.5/2  times 

higher  than  normal  runs  through 
motor  windings,  so  the  starter  trips 
stopping the unit. 

D.  The starter is installed in a too warm 

place. 

E.  The 

starter 

in 

not 

correctly 

calibrated. 

 
 

F.  Electropump  blocked  in  a  crooked 

sinkhole  with  consequent  abnormal 
value of the absorbed current. 

G.  Cut-off conductors in the starter. 

H.  Grounded,  short-circuited  or  cut-off 

cable joint or motor windings. 

A.  Increase supply cable diameter. 
B.  Pull on the pump and clean it. 

 

C.  Check  voltage  on  all  three  phases. 

Check the conditions of starter fuses 
and contact. 
 

D.  Set  starter  overload  relays  on  the 

highest value. 

E.  If  the  amperometer  shows  normal 

voltage  and  the  starter  trips  also 
after  different  calibrations,  replace 
the overload relay. 

F.  Move the unit so to straighten it and 

it again. 
 

G.  See point 2.C 

H.  See point 2.B 

4. 

The  pump  runs  with  a  low 
capacity or head. 

A.  Wrong motor rotation. 

 

B.  The  delivery  pipe  leaks;  flange  or 

coupling not well fastened. 

C.  Voltage 

lower 

than 

normal, 

absorbed 

current 

higher 

than 

normal. 

D.  Clogged grid. 
E.  Worm impellers and diffusers. 

F.  The  manometric  head  has  been 

wrongly calculated. 

A.  Lift  the  pump  out  of  the  well  and 

check the delivery pipe. 

B.  Move the unit so to straighten it and 

start it again. 

C.  Lift  the  pump  out  of  the  well  and 

check the delivery pipe. 
 

D.  Clean the pump. 
E.  Replace worm parts. 

F.  Calculate  again  the  manometric 

head;  replace  the  unit  with  a  more 
suited one. 

 

Содержание SS6

Страница 1: ...NDERHOUD INSTRUCCIONES PARA LA INSTALACION Y EL MANTENIMIENTO INSTALLATIONS OCH UNDERHÅLLSANVISNING Ο ΗΓΙΕΣ ΓΙΑ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΚΑΙ ΤΗ ΣΥΝΤΗΡΗΣΗ KULLANIM VE BAKIM TALİMATLARI ИНСТРУКЦИИ ПО МОНТАЖУ И ТЕХНИЧЕСКОМУ ОБСЛУЖИВАНИЮ INSTRUCŢUNI PENTRU INSTALARE ŞI ÎNTREŢINERE INSTRUÇÕES PARA A INSTALAÇÃO E A MANUTENÇÃO INSTRUKCJE OBSŁUGI I KONSERWACJI INSTALLÁCIÓS ÉS KARBANTARTÁSI UTASÍTÁS ا دات إر وا SS6...

Страница 2: ...AIS page 9 ENGLISH page 17 DEUTSCH seite 24 NEDERLANDS bladz 32 ESPAÑOL pág 40 SVENSKA sid 48 ΕΛΛΗΝΙΚΑ σελ 56 TÜRKÇE sayfa 64 РУССКИЙ cтр 72 LIMBA ROMÂNĂ pag 80 PORTUGUÊS pág 88 POLSKI str 96 MAGYAR oldal 104 112 ªRte IZk ...

Страница 3: ...hat they do not play with the appliance Ensure that the product has not suffered any damage during transport or storage Check that the outer casing is unbroken and in excellent conditions 1 1Safety Use is allowed only if the electric system is in possession of safety precautions in accordance with the regulations in force in the country where the product is installed for Italy CEI 64 2 1 2 Respons...

Страница 4: ...antifreeze mixture to prevent internal freezing up to 30 C Motors should not be stored or installed with lower temperatures or for periods longer than 12 months however if this is unavoidable turn the shaft by hand once a month If the motor has been stored for more than 12 months disassemble it and check rotating parts and thrust bearing Just before installation drain completely the motor from the...

Страница 5: ...brackets placed alternately on the pump column pipe Proceed in the following way a Connect the first column section to the pump delivery nozzle after having placed a splitted supporting bracket at the opposite end of the pipe In case of threaded column pipes place by the upper end the suited threaded sleeve to avoid possible sliding between pipe and bracket b Move the assembly with a hoist and low...

Страница 6: ...no cuts cracks scratches or other damages If two cables have to be joined in parallel pay extreme attention when connecting cables of the same color 6 2 Electric system The motor is connected by the supply cable to the control panel which contains the necessary control and protection devices Since every difficulty either mechanical or electric will damage almost automatically the motor windings it...

Страница 7: ...ages when lowering the pump in the well If the results are negative lift the group again and check it thoroughly For three phases units the electric resistance value should be nearly the same for each phase Check insulation resistance to the ground i e between cable end and discharge pipe using a megahoms meter Minimum value to the ground for a new pump is 10 megahoms with cold motor However if so...

Страница 8: ...onstruction features the pump and motor group easily disassembled and re assembled with normal metric size shop tools If the pump adopts a non return valve consider the additional weight of the water filled column besides the group weight and use therefore a suited hoist We suggest to employ specialized personnel for assembling and disassembling 9 2 Assembling the pump motor group Check the free r...

Страница 9: ...he pump is running A Too low voltage B Overload due to sand clogging bearings tend to saize C Single phase a voltage 1 5 2 times higher than normal runs through motor windings so the starter trips stopping the unit D The starter is installed in a too warm place E The starter in not correctly calibrated F Electropump blocked in a crooked sinkhole with consequent abnormal value of the absorbed curre...

Отзывы: