ENGLISH
GB
29
8.2.4 Outputs
With reference to Figure 9 the digital outputs available are:
Output
Terminal no.
Type of
contact
Associated function
OUT1
1
NC
Presence/Absence of alarms in the
system
2
COM
3
NO
OUT2
4
NC
Pump running/Pump stopped
5
COM
6
NO
The outputs OUT1 and OUT2 are available on the pull-out 6-pole terminal
ERDUGDVVSHFL¿HGLQ7DEOHZKLFKDOVRVKRZVWKHW\SHRIFRQWDFW1&
Normally Closed, COM = Common, NO = Normally Open).
The electrical characteristics of the contacts are shown in Table 6.
In the example shown in Figure 8 the light L1 is lit when there is an
alarm in the system and it goes off when no kind of malfunction is found,
whereas the light L2 is lit when the pump is running and goes off when
Table 5: Outputs OUT1 and OUT2
the pump is stopped.
Characteristics of the output contacts
Max. bearable voltage [V]
250
Max. bearable current [A]
5
If resistive load
2,5
If inductive load
Max. accepted cable section [mm²]
2,5
8.3 Connections for Twin Systems
3HUUHDOL]]DUHXQVLVWHPDJHPHOODUHqVXI¿FLHQWHFROOHJDUHFLUFRODWRUL
EVOPLUS utilizzando il cavo fornito in dotazione inserendolo nel connet-
tore apposito (si veda Tabella 2).
For correct operation of the twin system, all the external connec-
tions of the pull-out 13-pole terminal board must be connected in
parallel between the 2 EVOPLUS respecting the numbering of the
individual terminals.
For the possible operating modes of twin systems see par. 12 Page 8.0
of the EVOPLUS menu.
9. START
All the starting operations must be performed with the cover of
the EVOPLUS control panel closed.
Start the system only when all the electrical and hydraulic con-
nections have been completed.
Avoid running the circulator when there is no water in the sy-
stem.
Table 6: Characteristics of the output contacts
Figure 9: Pull-out 6-pole terminal board: example of output connection