ENGLISH
GB
15
otherwise contact a DAB assistance centre (www.dabpumps.com).
3- USER INTERFACE
On the e.sylink there are
leds
indicating the system operating status.
Table 4 describes the meaning of each
leds
on the user interface:
Characteristics of the
leds
LEDS
COLOUR
Description
POWER
White
On: e.sylink powered
Off: e.sylink not powered
FAULT
Red
Off: no fault
On or blinking: see Table 5
IN
Green
Off: Input not energised
On: Input energised
OUT
Yellow
Off: relay contact open
On: relay contact closed
Blue
Off: e.sylink not connected
and wireless configuration
not present
On: e.sylink connected
Blinking: e.sylink not
connected, but with wireless
configuration present
Green
Pressure Sensor connected
Table 5 described the possible faults that may be found by e.sylink
Fault
LED FAULT
General
On with fixed light
Supply voltage not sufficient
for correct relay control
3 blinks every 4 seconds
Supply voltage not sufficient to
power the pressure sensor
2 blinks every 4 seconds
Wireless protocol version not
compatible.
1 blink every 4 seconds
Table 5: Faults
Figure 5: e.sylink Interface
Table 4:
leds