Wired Controller
CDV-46
11
5.1 INSTALLATION OF WIRED CONTROLLER
5.1.1 Communication Line Selection
Fig. 5.2 Length of communication line
Wire material
type
Total length of
communication line
between indoor unit
and wired controller
L (m/feet)
Wire size
(mm
/AW
G)
Material
standard
Remarks
Light/Ordinary
Polyvinyl
chloride
sheathed
cord.
(60227 IEC 52
/60227 IEC
53)
L
İ
250m
(L
İ
820-1/5feet)
2×0.75
mm
~2×
1.25 mm
(2×AWG1
8~2×AWG
16)
IEC
60227-5:2
007
(1)Total length of
communication line can't
exceed 250m (820-1/5feet).
(2)The cord shall be Circular
cord (the cores shall be
twisted together).
(3)If unit is installed in
places with intense
magnetic field or strong
interference, it is necessary
to use shielded wire.
Note:
ķ
If the air conditioner is installed at the strong electromagnetic interference
place, communication line of the wired controller must use shielding
twisted pair.
Содержание CDV-46
Страница 2: ......
Страница 20: ...Wired Controller CDV 46 14 Fig 5 5 One wired controller controls multiple indoor units simultaneously ...
Страница 43: ...Wired Controller CDV 46 37 Fig 6 5 Timer Off setting in unit On status in Celsius g g ...
Страница 46: ...Wired Controller CDV 46 40 ...
Страница 47: ...Wired Controller CDV 46 41 Fig 6 7 Unit On Off time setting in unit On status in Celsius ...
Страница 48: ...Wired Controller CDV 46 42 Fig 6 8 Unit On Off time setting in unit On status in Fahrenheit ...
Страница 51: ...Wired Controller CDV 46 45 Fig 6 9 Setting of Quiet function in Celsius ...
Страница 54: ...Wired Controller CDV 46 48 Fig 6 11 Turn on Air Function in Celsius ...
Страница 55: ...Wired Controller CDV 46 49 Fig 6 12 Turn on Air Function in Fahrenheit ...
Страница 58: ...Wired Controller CDV 46 52 Fig 6 13 Save Setting for Cooling in Celsius ...
Страница 59: ...Wired Controller CDV 46 53 Fig 6 14 Save Setting for Cooling in Fahrenheit ...
Страница 62: ...Wired Controller CDV 46 56 Fig 6 15 Turn on Filter Clean Reminder Function in Celsius ...
Страница 74: ......