Malfunction Analysis
Malfunction code
Chassis is full of water.
Malfunction of ambient
temperature sensor.
Please contact professional person to deal
with it.
Malfunction of evaporator
temperature sensor.
Please contact professional person to deal
with it.
1. Pour out the water inside chassis.
2. If "H8" still exits, please contact professional
person to maintain the unit.
● If there're following phenomenon, please turn off the air conditioner and discon-
nect the power immediately, and then contact dealer immediately.
● If operate the air conditioner under abnormal condition, it may cause malfunc-
→ Power cord is overheating or damaged.
→ Abnormal sound during operation.
→ Water leakage
F0
F2
F1
H8
H3
E8
F4
1.Refrigerant is leaking
2.System is blocked
1. Re-energize the unit after turning off and
pulling out the plug for 30min;
2. If there's still malfunction, please contact
after-sales service.
Overload protection for compressor
Overload malfunction
1.Check if the unit is under high-temperature
and high-humidity environment; if ambient
temperature is too high, power off the unit and
then energize it for operation after the ambient
temperature drops to 35
℃
below.
2. Check if the evaporator and condenser are
blocked by some objects; if yes, take away the
objects, power off the unit and then energize
it for operation.
3. If the malfunction still occur, please contact
our after-sales service center.
Outdoor tube temperature
sensor is open/short-circuited.
Please contact after-sale service person
to deal with it.