D-M-E Company
VCTB-4000
Page 14
ED-0109-OT-024-( Preliminarry Rev E)
-
OR –
Connect the
VCTB04
eight zone control cable to the “alternate”
output connector of the VCTBA02.
P/N: VCTBA05
A twelve-zone control cable connection can be made using the
twelve-zone accessory output mating cable connector kit
VCTBA05.
Step 10.
Mount the temperature control mainframe to the
MFS512G mainframe floorstand.
A standard MFP12G is shown above. To mount a standard
MFP8G, use the mainframe adapter plates provided with the
MFS512G floorstand kit.
Alternative Mounting:
The VCTBA03 mounting plate can also
be mounted below the standard mainframe as shown above. To
use this mount, the VCTB-4000 mounting studs on the mounting
plate must be installed in the lower position. Also, will be
necessary to route the VCTBA02 control and trigger cables
between the mainframe and mounting plate before either is
mounted to the stand.