background image

English

Maximum  pressure  load  of  the  toothed  rack  is  not 
automatically identical with the maximum pressure 
force of the drive!

Pressure load diagram

500

600

800

1000

1

100

1200

1300

1400

1500

1600

0

200

400

600

800

1000

1200

1400

max. Load (N)

Stroke (mm)

- Swivel radius of the drive must have clearance

across the entire range of the stroke, otherwise
the rack and pinion drive and the suspension can
be damaged

- Drives with a stroke of ≥800

 

mm

 

must

 

not

 

be

mounted

 

„hung up  at the bottom“ (e.g. bracket UK)

- Eyebolt has to be adjusted so, that the drive is

disconnected with closed flap through it’s inside
stop position damping. Brackets can be damaged
by to rigid adjustment!

- Technical clarification is required with D+H in case

of only tensile force applications of more than 500 N

Mounting information

Safety notes

Operating voltage 230 VAC!
Risk of injury from electric shock
Do not reverse L+N! Connect PE!

- Connection must be carried out by a certified

electrical technician

- Danger of crushing hands and fingers!
- Keep people away from the operating area of the drive
- Keep children away from the control
- Observe pressure load diagram of the rack and

pinion drive rack

- Use only in dry rooms
- Suitable for indoor mounting only.

Use rain detector in locations if there is a risk of rain

- Use option "-W" if mounted outdoors!
- Use unmodified original D+H parts only
- Observe the bracket-set mounting instructions

Observe enclosed red safety note!

Intended use

- Rack and pinion drive for electric opening and

closing of windows and flaps in the facade and
roof area

- Operating voltage 230 VAC
- Usable for smoke extraction, D+H Euro-SHEV in

accordance with DIN EN 12101-2 as well as daily
ventilation

- Suitable for indoor mounting only

Drive unit with 2.5 m silicone cable. Depending on 
the  type  of  window,  different  bracket  sets  are 
available separately.

Scope of supply

99.823.58 2.6/02/16

ZA 105-K

 

ZA 105-K

5/12

Type 

ZA 105-K

Rated voltage 

230 V AC, +10%/-15%
50 Hz

Performance 

27 W / 30 VA

Nominal force 

1000 N*

Runtime /100 mm 

10 sec.

Nominal locking force 

1100 N

Service life 

>20 000 double strokes

Duty cycle 

30 % S2 (EN 60034-1)
no continuous voltage

Housing  

Aluminium, PC

Protective system 

IP 65 (“-W“ = IP 54)

Temp.range 

-5 ... +75 °C

Emission sound 

LpA ≤ 70 dB(A)

pressure level
Nominal stroke length 

See type plate

* + approx. 20 % cut-off reserve (temporary)

Technical data

10 ... 20 mm

1. Move out toothed rack about 10 ... 20 mm.

   Disconnect drive from electric Voltage!

2. Take off drive unit and shift
3. Attention! Moving direction of drive is changed.

Drive cable on the shutdown pcb, switch
red (+) with black (-)

Shifting of drive cable

Disconnect drive from electric voltage!

Shifting of Motor

Electrical devices, accessories, batteries and packa-
ging  should  be  sorted  for  environmental-friendly 
recycling.  Do  not  dispose  electrical  devices  and 
batteries into household waste!
Only for EC countries:
According the European Guideline 2012/19/EU for 
waste  electrical  and  electronic  equipment  and  its 
implementation into national right, electrcal devices 
that are no longer usable must be collected separa-
tely  and  disposed  of  in  an  environmentally  correct 
manner.

Disposal

Declaration of Conformity

We  declare  under  our  sole  responsibility  that  the 
product  described  under  “Technical  Data”  is  in 
conformity with the following directives:

2014/30/EU, 2014/35/EU

Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek

Dirk Dingfelder

Maik Schmees

Member of the Board 

Authorized signatory, Technical Director

17.11.2015

Maintenance and cleaning

Inspection  and  maintenance  has  to  be  carried  out 
according  to  D+H  maintenance  notes.  Only  original 
D+H spare parts may be used. Repair is to be carried 
out exclusively by D+H.
Wipe away debris or contamination with a dry, soft 
cloth.
Do not use cleaning agents or solvents.

Guarantee

You will get 2 years guarantee for all D+H products 
from date of verified handing over of the system up to 
maximal  3  years  after  date  of  delivery, when 
mounting  and  starting  has  been  carried  out  by  an 
authorized D+H-distributor.
D+H guarantee is expired, with connection of D+H 
components with external systems or with mixing of 
D+H products with parts of other manufacturers.

WARNING

Read all safety warnings, instructions, illustrations 
and specifications provided with this product.
Failure to follow all instructions listed below may 
result in electric shock, fire and/or serious injury.
Save all warnings and instructions for future 
reference.