99.828.01 1.1/08/19
7/24
English
99.828.01 1.1/08/19
6/24
English
LDx 1x00-1-PLP/-ACB
LDx 1x00-1-PLP/-ACB
Technical Data
* Programmable with software SCS ** Running direction programmable with SCS
Type
LDx-1400-1-PLP
LDx-1400-1-ACB
LDx-1800-1-PLP
LDx-1800-1-ACB
Power supply
24 V DC / ± 20 %
Nominal force
Nominal current
1400 N
1,4 A
1800 N
1,6 A
Stroke length
max. 90 mm
±
2 % *
Nominal locking force
Service life
Duty cycle
Housing
Ingress protection
Temp. range
Fire stability
Ambient humidity
Emission sound pressure level
Additional functions*
approx. 5000 N (Depending on the fastening)
>20.000 double strokes
30 %, With cycle time 10 minutes
Aluminium, silver anodised EV1
IP 40 (IP 44 with inserted gaskets)
-5 ... +75 °C
B300 (30 min / 300 °C)
≤ 90 %, not condensing
LpA ≤ 45 dB(A)
Closing edge protection = activated (3 repetitions of stroke)
Locking relief = activated
Closing edge protection
In the "CLOSE" direction the drive has an active
protection for the main closing edge. If there is an
overload in the closing ranges C3 and C2, the drive
runs "OPEN" for 10 seconds, then "CLOSE" again. If
closing is not possible after three attempts, the drive
remains in this position.
In addition, the drive is equipped with passive
protection. The closing speed in closing range C2
and C1 is reduced to 1 mm/s.
Significantly greater forces can be
exerted at the secondary closing edges.
Danger of crushing hands and fingers!
Opening and Closing Ranges LDx-1400 (LDx-1800)*
CLOSED**
OPEN**
Drive unit with 2.5 m silicone cable.
The louvre-specific tappet driver and the gaskets for
increasing the ingress protection to IP 54 are
available separately.
Scope of supply
WARNING
Read all safety warnings, instructions, illustrations
and specifications provided with this product.
Failure to follow all instructions listed below may
result in electric shock, fire and/or serious injury.
Save all warnings and instructions for future
reference.
Declaration of Conformity
We declare under our sole responsibility that the
product described under “Technical Data” is in
conformity with the following directives:
2014/30/EU, 2014/35/EU
Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek
Dirk Dingfelder
Maik Schmees
Member of the Board
Authorized signatory, Technical Director
24.06.2019
Guarantee
You will get 2 years guarantee for all D+H products
from date of verified handing over of the system up to
maximal 3 years after date of delivery, when
mounting and starting has been carried out by an
authorized D+H-distributor.
D+H guarantee is expired, with connection of D+H
components with external systems or with mixing of
D+H products with parts of other manufacturers.
Safety notes
Safety extra low voltage 24 V DC!
Do not connect directly to the mains supply!
- Connection has to be carried out only by an
authorized electrical specialist
- Danger of violent pressure in handaccessible area
- Keep away People from the operating area of the
drive
- Keep away children from the control
- Use only in dry rooms
- Only for inside mounting.
Use rain detector with danger of rain
- Just use unchanged original D+H parts
Observe enclosed r
ed safety slip!
Features
- Protection system for the main closing edge
- Relief of pressure on window gasket after closing
- Connection via plug connector
Especially LDx-1-PLP:
- Stroke programming with magnet
- Adjusting of stroke with PLP1 directly at the drive
- Individually programmable via Powerline (PLP1
and SCS)
Especially LDx-1-ACB:
- ACB (Advanced Communication Bus) bus
interface with ModBus protocol for the
connection to compatible D+H control panels or
direct integration into building management
systems, for example
- BSY+ electronics for reliable and accurate
synchronous operation of up to 8 drives
(Tandem programming required by SCS-
Software)
- Individually programmable via software SCS
- Direct connection of additional closing edge
protection at the drive possible (SKS option)
Intended use
- Drive for electric opening and closing for
louvre windows
- The louvre must be prepared by the louvre
manufacturer for the application of the drive
- Operating voltage 24 V DC
- Useable for smoke ventilation as well as daily
natural ventilation
- See also ACB planning manual
- Suitable for indoor mounting only
O1*
3 mm
1400 N (1800 N)
2 mm/s
O2*
85 mm
1400 N (1800 N)
2 mm/s
O3*
2 mm
1400 N (1800 N)
1 mm/s
C3*
65 mm
800 N (1000 N)
2 mm/s
C2*
20 mm
400 N (500 N)
1 mm/s
C1*
5 mm
800 N (1000 N)
1 mm/s