Encoding of groups – DIP-Switch S1 ... S5
Following functions can be adjusted for each group separately with
DIP switch S1 - S5
on motherboard
of control panel and on group plug-in unit, if available.
The delivery state of all DIP-switches is OFF.
1 = ON
Drives
CLOSE
up to final position by
single pressing
on respective vent button.
1 = OFF
Drives are closing
only so long as
the vent button is
pressed
.
2 = ON
Drives
OPEN
up to final position by
single pressing
on vent button.
2 = OFF
Drives are opening
only so long as
the vent button is
pressed
.
3 = ON
Drives are
automatically closed
by trigger of function „
Central CLOSE
",
e.g. by rain detector or room temperature control.
3 = OFF
Drives can be closed
only by pressing
the respective
vent button
.
4 = ON
Drives are
automatically opened
by trigger of function „
Central OPEN
",
e.g. by room temperature control.
4 = OFF
Drives can be opened
only by pressing
the respective
vent button
.
*
The vent button of the respective group.
Wiring plan (Paragon)
230 VAC, 50 Hz
to further ones
see line lenghts and cross sections
window drive
control panel
vent button
ca. 1,2 m above
upper edge
firm flooring
external
control
4x 0,8 Ø
4x 0,8 Ø
2x 0,8 Ø
4x 0,8 Ø
rain sensor
room temperature
control
Line lenghts and cross sections
Output voltage 24 VDC!
Do not run cables together with power lines!
In case of a cable with
ground wire
(e.g. green / yellow) this must
not be used
!
total current
0,5
240
400
640
1
120
200
320
1,5
80
130
213
2
60
100
160
2,5
48
80
128
3
40
65
107
3,5
34
55
91
4
30
50
80
4,5
27
44
71
5
24
40
64
5,5
22
36
58
6
20
33
53
6,5
18
31
49
7
17
28
46
7,5
16
27
43
8
15
25
40
m
m
m
type
2x 1,5 mm²
2x 2,5 mm²
2x 4 mm²
Connection – Vent buttons and Window drives
Line lengths and
cross sections
see page 12
4
5
6
7
GVL 8408-M
–
Mot.b
Mot.a
X
A
Z
L
(open signal, only L
T
43U-SD)
LT
MOT
1
2
3
Vent button
(e.g. LT 84-U-SD)
L
P
Mot.b
Mot.a
24 VDC
Window Drives
Mot.b
Mot.a
4
GVL 8408-M
+G
Az
Zz
–
1
2
3
External control
for central closing
(e.g. timer)
Drive group 1 ... 5 (6)
Ask your local D+H partner for further connection examples.
230 VAC supply
Covering
Place enclosed protection cap
over supply terminal after mains
cable has been connected.
L
N
PE
230 VAC, 50 Hz
GVL 8408-M
GVL 8408-M
12/16
13/16
English
English
Cross section (mm²) =
cable lenght (m) x total current
80
99.823.56 1.2/11/15
99.823.56 1.2/11/15
X1