17
EN / CZone® Control 1
1. Connect High-Current Outputs (OUT-H)
1. Referring to the load list, strip and crimp the High Current cables with the appropriate Deutsch contact and
crimp tool.
2. Insert the contacts into the DTP06-4S plug following the plugs position numbers and secure using the
locking wedge.
3. Any unused pins in the connector should be plugged with sealing plugs to maintain the IPX5 rating.
4. Insert the connector into the Control 1 and lock into place.
5. Load negatives are not connected to the Control 1, they must be connected to a common negative bus.
Best wiring practice is to locate the negative connections close to the Control 1 so positive & negative
wires run together minimizing magnetic fields.
6. Secure and neaten up the cables against the bulkhead to reduce the strain on the connectors.
2. Connect Low-Current Outputs (OUT-L):
1. Referring to the load list, strip and crimp the Low Current cables with the appropriate Deutsch contact and
crimp tool.
2. Insert the contacts into the DT06-12SA plug following the plugs position numbers and secure using the
locking wedge.
3. Any unused pins in the connector should be plugged with sealing plugs to maintain the IPX5 rating.
4. Insert the connector into the Control 1 and lock into place.
5. Load negatives are not connected to the Control 1, they must be connected to a common negative bus.
Best wiring practice is to locate the negative connections close to the Control 1 so positive & negative
wires run together minimizing magnetic fields.
6. Secure and neaten up the cables against the bulkhead to reduce the strain on the connectors.
3. Connect Analogue Inputs (IN-A)
1. The analogue inputs can be used to connect mechanical switches to control outputs (switch to pos or
switch to neg) or analogue sensors (0-32V, 0-1000
Ω
or 4-20mA). CZone will convert analogue sensor
values into NMEA 2000 digital sentences.
2. Referring to the input list, strip and crimp the Analogue Input cables with the appropriate Deutsch contact
and crimp tool.
3. Insert the contacts into the DT06-08SA plug following the plugs position numbers and secure using the
locking wedge.
4. Any unused pins in the connector should be plugged with sealing plugs to maintain the IPX5 rating.
5. Insert the connector into the Control 1 and lock into place.
6. Secure and neaten up the cables against the bulkhead to reduce the strain on the connectors.
4. Connect NMEA2000 network
1. Connect an NMEA2000 drop cable from the Control 1 to an NMEA2000 backbone.
2. Ensure the NMEA2000 network is properly terminated and connected to a 12V power source (Do not
power up network yet).