background image

KP04AE/KP04AET should be installed in an indoor 

location, not outside the premises for security reasons.

1.

Remove the screw at the base, hold the 

bottom of the Front Housing  pull the front 
housing from the back housing.

2.

Mount the back housing on the wall using the 
screws supplied. 

3.

Connect the 6 wires from the terminal blocks 
(JP1, JP2 , JP3) to the Comfort PCB according 

to the signal name. Note the 12V should be 
connected to the 12V terminal on Comfort, 

not

 S12V 

4.

If more than one Keypad  is used, connect 

their 12V and ground wires back to Comfort 
individually, not in series to avoid excessive  

voltage drop along the cable. 

  

CM9001 Text Synchronisation 

If the LCD displays “Wrong Text. Press *1 to sync”. 
press and hold the “*” followed by “1” keys to  sync the

KP04 text with Comfort. The screen shows  
“Downloading” with status bar. After the process 

completes, the keypad will reset and “beep”. If this 
does not work, sign in on the keypad and check if the 

Voice menu is heard. 

KP04A Settings

The KP04A has  ID set to 1 as default. There are no 
shunts for configuration or setting in KP04A as all 

setting is done through the Settings Menu.

Since the keypad is supplied as ID=1 by default, if 
there is another Keypad with the same ID in the 

system, this will cause a clash of Ids when the new 
keypad is connected.   To change the ID, wait for 20 

seconds before trying to go into the Settings menu.

Press and hold the * key for 4 seconds until “Enter 
Engineer Code” is seen. If Engineer Code has NOT 

been enabled, a message “Engineer Sign in Option is
OFF”. Press F0 on the keypad and try again. The 

following keys have the functions shown;

Содержание KP04AE

Страница 1: ... has a 2 line x 16 character LCD which shows alarms Zones Inpuuts Warnings Temperature Humidity and other sensor readings for CM9001 EMS Environmental Monitoring System KP04AET has a bullt in Temperature sensor while KP04AE does not include the Temperature sensor ...

Страница 2: ...re 7 153 above Contents KP04AE or KP04AET keypad 2 wall plugs and screws for mounting 3 x 2 way removable terminal blocks Connections to Comfort JP1 12V COM Connected to 12V COM Comfort JP2 KA KB Connected to KA KB Comfort JP3 VOICE MIC Connected to KP VOICE MIC CM9001 LEDs on PCB D15 Red RS485 reply to poll D16 Green RS485 Poll by Comfort Both D15 and D16 should be blinking when communicating wth...

Страница 3: ... e g Phone line cut RS485 comms failure Trouble Condition is displayed Arm Red Steady System armed No alarm Blinking Alarm Alert condition AC Red Steady Mains Power failure Blinking CM9001 Battery voltage low due to prolonged power failure Battery may need to be replaced Msg Green Not in Use Mic Red Not in Use ...

Страница 4: ...Installation Connections ...

Страница 5: ...ress and hold the followed by 1 keys to sync the KP04 text with Comfort The screen shows Downloading with status bar After the process completes the keypad will reset and beep If this does not work sign in on the keypad and check if the Voice menu is heard KP04A Settings The KP04A has ID set to 1 as default There are no shunts for configuration or setting in KP04A as all setting is done through th...

Страница 6: ...p Backlight Automatic Always On Always Off LCD Keyboard Backlight setting IR Receiver Enable Disable IR Receiver Voice Broadcast Enable Disable Broadcast Voice siren Keypad Tamper Enable Disable Internal Tamper Date Format DD MM YY etc Select date format Time Format 12 Hr 24 Hr Select Time format LCD Contrast 0 63 def 37 LCD Contrast Backlight Off 0 31 def 1 LCD level for backlight OFF Factory Def...

Страница 7: ... Sign in Option is OFF appears wait for 20 seconds and try again F0 on the keypad is not needed in this case Key Beep This determines the volume of the key beep when any key is pressed Select Soft Loud or Disable default Soft Alert Beep This determines the volume of Alert tones generated by the KP04A e g Error beep short beeps Continuous beeps Select Soft Loud or Disable default Soft Backlight Thi...

Страница 8: ...tween various date formats Time Format Select between various time formats LCD Contrast Select LCD Contrast 0 to 63 BackLight Off Select the brightness of the backlight when it is in the off state after timeout Values 0 to 31 Higher value allows the LCD to be read even when backlight is off Save Menu Save and Apply Yes No default NO Yes causes settings to be saved and KP04AT to reset No causes cha...

Страница 9: ...l Modules This will detect that KP04A is connected if all keypads have unique IDs Select the KP04A on the left pane Note that KP04AT will be displayed as KP04A in Comfigurator Comfigurator does not distinguish between the two products The right pane shows the display below ...

Страница 10: ...Alarm EMS Mode If CM9001 EMS Controller is installed instead of CM9001 ULT set to EMS Mode to display up to 8 Sensor values including the built in Temperature Sensor ...

Страница 11: ......

Страница 12: ...egister to the built in Temperature sensor in KP04AT Refer to CM9001 EMS Manual for details of EMS Mode Write to Keypad will write the settings to the KP04AT Read from Keypad will read the settings from KP04AT 90 x 150 mm PR02 0051 Revised Sept 2019 ...